LV Aerial Bundled Cable for Low-Voltage Distribution
LV aerial bundled cable combines individually insulated aluminium conductors in a compact 0.6/1 kV overhead distribution assembly. Depending on the applicable standard or utility specification, the conductors use PE or XLPE insulation and form either a self-supporting bundle or a neutral-messenger arrangement. Available configurations include phase, neutral and public-lighting cores for urban, rural and street-lighting networks, with conductor sizes, identification and delivery lengths selected for the required system.
Product Overview
The electrical and mechanical functions of an LV ABC are distributed differently according to its construction. Equal-core self-supporting designs share the suspended load through the assembled insulated cores, whereas neutral-messenger designs use a designated supporting conductor. The insulation material, lay direction, core marking and reduced-size lighting cores also vary between standards, so these features must remain connected to the exact cable configuration.
BS 7870-5, HD 626, NF C 33-209, AS/NZS 3560.1 and utility-specific designs are not automatically interchangeable. Selection should begin with the governing specification and network drawing, followed by the complete core formula, conductor sizes, support arrangement, route conditions and required fittings. LV ABC is a multi-core low-voltage bundle; it should not be confused with a single covered line wire or a medium-voltage aerial bundle.
Key Features
- Aluminium conductor construction:Stranded or compacted aluminium conductors provide the specified current-carrying area while keeping the completed overhead bundle lighter than an equivalent copper assembly, which supports handling and pole-line installation.
- PE or XLPE core insulation:Each live core receives the insulation material and thickness required by the selected standard or utility design, providing separation within the bundle and weather resistance for outdoor service.
- Core identification:Phase, neutral and optional public-lighting cores carry the colour, stripe, ridge or printed identification specified by the applicable standard, allowing installers to distinguish each circuit function consistently.
- Equal-core and messenger support:Equal-core and neutral-messenger designs distribute mechanical load differently; retaining the correct support concept helps suspension clamps, anchor fittings and span calculations work with the cable construction.
Product Applications
- Urban and suburban pole routes where compact insulated cores help manage restricted clearances and frequent service connections
- Rural low-voltage distribution and building service branches designed around an equal-core or neutral-messenger ABC system
- Public-lighting networks that incorporate one or more identified lighting cores within the specified aerial bundle
Technical Specifications
Aerial Bundled Cables can be manufactured to different international, national and utility-specific requirements. The applicable standard is normally determined by the project specification, local regulations, utility requirements or tender documents. Please check the required standard before selecting the technical data below. If you are unsure which standard applies to your project, send us the relevant specification or project requirements, and our technical team can help you identify the appropriate cable specification.
0.6/1 kV ABC Cable AS NZS 3560.1
| Number of cores x nominal cross section | min. breaking load of conductor strand | Current rating in the air | Outer diameter | Total weight |
|---|---|---|---|---|
| mm^2 | kN | A | mm | kg/km |
| 2x16 RM | 4.4 | 78 | 15.0 | 140 |
| 2x25 RM | 7.0 | 105 | 17.6 | 210 |
| 2x35 RM | 9.8 | 125 | 19.6 | 270 |
| 2x50 RM | 11.4 | 150 | 22.8 | 370 |
| 2x95 RM | 15.3 | 230 | 30.6 | 680 |
| 3x25 RM | 8.8 | 97 | 19.0 | 310 |
| 3x35 RM | 9.8 | 120 | 21.1 | 410 |
| 3x50 RM | 11.4 | 140 | 24.6 | 550 |
| 4x16 RM | 8.8 | 74 | 18.1 | 290 |
| 4x25 RM | 14.0 | 97 | 21.2 | 410 |
| 4x35 RM | 19.6 | 120 | 23.7 | 550 |
| 4x50 RM | 28.0 | 140 | 27.5 | 740 |
| 4x70 RM | 39.2 | 175 | 31.9 | 1000 |
| 4x95 RM | 53.2 | 215 | 36.9 | 1370 |
| 4x120 RM | 67.2 | 250 | 40.6 | 1690 |
| 4x150 RM | 84.0 | 280 | 43.9 | 2020 |
0.6/1 kV ABC Cable BS 7870-5
| number of cores x nomina | cross section | max. conductor- resistance | min. breaking load of conductor strand | Current rating in the air | Outer diameter | Total weight |
|---|---|---|---|---|---|---|
| mm^2 | Ohm/km | kN | A | mm | kg/km | |
| 1x 16 RM | 1,910 | 2,5 | 72 | 8.0 | 74 | |
| 1x 25 RM | 1,200 | 4,0 | 107 | 9.0 | 106 | |
| 1x 35 RM | 0,868 | 5,5 | 132 | 10.5 | 138 | |
| 1x 50 RM | 0,641 | 8,0 | 165 | 11.8 | 182 | |
| 1x 70 RM | 0,443 | 10,7 | 205 | 13.0 | 252 | |
| 1x 95 RM | 0,320 | 13,7 | 240 | 15.4 | 333 | |
| 1x 120 RM | 0,253 | 18,6 | 290 | 17.0 | 408 | |
| 1x 150 RM | 0,206 | 23,2 | 334 | 19.0 | 502 | |
| 1x 185 RM | 0,164 | 28,7 | 389 | 21.0 | 611 | |
| 1x 240 RM | 0,125 | 37,2 | 467 | 24.0 | 801 | |
| 2x 16 RM | 1,910 | 2,5 | 72 | 15.6 | 147 | |
| 2x 25 RM | 1,200 | 4,0 | 107 | 18.0 | 208 | |
| 2x 35 RM | 0,868 | 5,5 | 132 | 20.0 | 277 | |
| 2x 50 RM | 0,641 | 8,0 | 165 | 23.5 | 361 | |
| 2x 70 RM | 0,443 | 10,7 | 205 | 25.4 | 505 | |
| 2x 95 RM | 0,320 | 13,7 | 240 | 30.3 | 666 | |
| 2x 150 RM | 0,206 | 23,2 | 334 | 38.0 | 1004 | |
| 4x 16 RM | 1,910 | 2,5 | 72 | 18.8 | 286 | |
| 4x 25 RM | 1,200 | 4,0 | 107 | 21.2 | 430 | |
| 4x 35 RM | 0,868 | 5,5 | 132 | 24.1 | 553 | |
| 4x 50 RM | 0,641 | 8,0 | 165 | 27.8 | 746 | |
| 4x 70 RM | 0,443 | 10,7 | 205 | 31.8 | 1009 | |
| 4x 95 RM | 0,320 | 13,7 | 240 | 37.8 | 1332 | |
| 4x 120 RM | 0,253 | 18,6 | 290 | 54.4 | 1632 | |
| 4x 50 + 1x 25 RM | 0,641/1,200 | 8,0/4,0 | 165/107 | 31.9 | 814 | |
| 4x 50 + 1x 35 RM | 0,641/0,868 | 8,5/5,5 | 165/132 | 31.9 | 845 | |
| 4x 70 + 1x 25 RM | 0,443/1,200 | 10,7/4,0 | 205/107 | 36.0 | 1105 | |
| 4x 70 + 2x 25 RM | 0,443/1,200 | 10,7/4,0 | 205/107 | 40.0 | 1217 | |
| 4x 95 + 1x 25 RM | 0,320/1,200 | 13,7/4,0 | 240/107 | 41.8 | 1438 | |
| 4x 95 + 2x 25 RM | 0,320/1,200 | 13,7/4,0 | 240/107 | 42.0 | 1544 | |
| 4x120 + 1x 25 RM | 0,253/1,200 | 18,6/4,0 | 290/107 | 59.0 | 2050 |
0.6/1 kV Aerial Bundled Cable – DES/LVC/ABC & IEC 60502
| Number of cores x nominal cross section | min. breaking load of conductor strand | Current rating in the air | Outer diameter | Total weight |
|---|---|---|---|---|
| mm^2 | kN | A | mm | kg/km |
| 4x25 RM | 3.5 | 84 | 21.5 | 420 |
| 4x35 RM | 4.9 | 104 | 23.9 | 550 |
| 4x120+1x25 RM | 16.8 | 246 | 43.8 | 1800 |
| 4x185+1x25 RM | 25.9 | 332 | 50.7 | 2700 |
0.6/1 kV Aerial Bundled Cable – HD 626 S1
| Number of cores x nominal cross section | min. breaking load of conductor strand | Current rating in the air | Outer diameter | Total weight |
|---|---|---|---|---|
| mm^2 | kN | A | mm | kg/km |
| 2x 16 RM | 1,910 | 2,5 | 72 | 147 |
| 2x 25 RM | 1,200 | 4,0 | 107 | 208 |
| 2x 35 RM | 0,868 | 5,5 | 132 | 277 |
| 2x 50 RM | 0,641 | 8,0 | 165 | 361 |
| 4x 16 RM | 1,910 | 2,5 | 72 | 286 |
| 4x 25 RM | 1,200 | 4,0 | 107 | 430 |
| 4x 35 RM | 0,868 | 5,5 | 132 | 553 |
| 4x 50 RM | 0,641 | 8,0 | 165 | 746 |
| 4x 70 RM | 0,443 | 10,7 | 205 | 1009 |
| 4x 95 RM | 0,320 | 13,7 | 240 | 1332 |
| 4x 120 RM | 0,253 | 18,6 | 290 | 1632 |
| 4x 35 + 1x 35 RM | 0,868/0,868 | 5,5/5,5 | 132/132 | 694 |
| 4x 50 + 1x 25 RM | 0,641/1,200 | 8,0/4,0 | 165/107 | 814 |
| 4x 50 + 1x 35 RM | 0,641/0,868 | 8,5/5,5 | 165/132 | 845 |
| 4x 70 + 1x 25 RM | 0,443/1,200 | 10,7/4,0 | 205/107 | 1105 |
| 4x 70 + 2x 25 RM | 0,443/1,200 | 10,7/4,0 | 205/107 | 1217 |
| 4x 70 + 1x 35 RM | 0,443/0,868 | 10,7/5,5 | 205/132 | 1150 |
| 4x 70 + 2x 35 RM | 0,443/0,868 | 10,7/5,5 | 205/132 | 1289 |
| 4x 95 + 1x 25 RM | 0,320/1,200 | 13,7/4,0 | 240/107 | 1438 |
| 4x 95 + 1x 35 RM | 0,320/0,868 | 13,7/5,5 | 240/132 | 1467 |
| 4x 95 + 2x 25 RM | 0,320/1,200 | 13,7/4,0 | 240/107 | 1544 |
0.6/1 kV Aerial Bundled Cable – IEC 60502 & TNB Requirements
| Number of cores x nominal cross section | min. breaking load of conductor strand | Current rating in the air | Outer diameter | Total weight |
|---|---|---|---|---|
| mm^2 | kN | A | mm | kg/km |
| 1x16+1x 25 RM | 6.4 | 61 | 15.3 | 160 |
| 3x16+1x 25 RM | 6.4 | 61 | 19.0 | 290 |
| 3x25+1x 25 RM | 6.4 | 84 | 23.2 | 400 |
| 3x35+1x 25 RM | 6.4 | 104 | 25.6 | 500 |
| 3x50+1x 35 RM | 8.9 | 129 | 30.0 | 680 |
| 3x70+1x 50 RM | 12.1 | 167 | 34.9 | 920 |
| 3x95+1x 70 RM | 18.0 | 209 | 40.6 | 1270 |
| 3x120+1x 70 RM | 18.0 | 246 | 44.1 | 1510 |
| 3x150+1x 95 RM | 24.2 | 283 | 49.2 | 1870 |
| 3x185+1x120 RM | 30.8 | 332 | 54.9 | 2340 |
| 3x25+1x25+1x16 RM | 6.4 | 84 | 23.2 | 470 |
| 3x35+1x25+1x16 RM | 6.4 | 104 | 25.6 | 560 |
| 3x50+1x35+1x16 RM | 8.9 | 129 | 30.0 | 740 |
| 3x70+1x50+1x16 RM | 12.1 | 167 | 34.9 | 980 |
| 3x95+1x70+1x16 RM | 18.0 | 209 | 40.6 | 1330 |
| 3x120+1x70+1x16 RM | 18.0 | 246 | 44.1 | 1580 |
| 3x150+1x95+1x16 RM | 24.2 | 283 | 49.2 | 1940 |
| 3x185+1x120+1x16 RM | 30.8 | 332 | 54.9 | 2410 |
0.6/1 kV Aerial Bundled Cable – NFC 33-209
| Number of cores x nominal cross section | max. conductor- resistance | min. breaking load of conductor strand | Current rating in the air | Outer diameter | Total weight |
|---|---|---|---|---|---|
| mm^2 | Ohm/km | kN | A | mm | kg/km |
| 2x10 RM | 3.080 | 1.5 | 38 | 12.8 | 93 |
| 4x10 RM | 3.080 | 1.5 | 38 | 15.4 | 183 |
| 2x16 RM | 1.910 | 2.3 | 72 | 14.8 | 129 |
| 2x16 RN + 2x1.5 RE | 1.910/12.100 | 2.3 | 72 | 14.8 | 176 |
| 4x16 RM | 1.910 | 2.3 | 72 | 17.8 | 257 |
| 4x16 RN + 2x1.5 RE | 1.910/12.100 | 2.3 | 72 | 17.8 | 304 |
| 2x25 RM | 1.200 | 3.8 | 107 | 18.0 | 202 |
| 2x25 RM + 2x1,5 RE | 1.200/12.100 | 3.8 | 107 | 18.0 | 249 |
| 4x25 RM | 1.200 | 3.8 | 107 | 21.7 | 404 |
| 4x25 RM + 2x1,5 RE | 1.200/12.100 | 3.8 | 107 | 21.7 | 451 |
| 2x35 RM | 0.868 | 5.2 | 132 | 20.8 | 269 |
| 2x35 RM + 2x1,5 RE | 0.868/12.100 | 5.2 | 132 | 20.8 | 316 |
| 4x35 RM | 0.868 | 5.2 | 132 | 25.1 | 539 |
| 4x35 RM + 2x1,5 RE | 0.868/12.100 | 5.2 | 132 | 25.1 | 586 |
| 2x50 RM | 0.641 | 7.6 | 165 | 23.4 | 352 |
| 2x50 RM + 2x1,5 RE | 0.641/12.100 | 7.6 | 165 | 23.4 | 399 |
| 1x54.6 RM + 3x25 RM | 0.630/1.200 | 3.8 | 107 | 21.7 | 507 |
| 1x54.6 RM + 3x25 RM + 1x16 RM | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 | 24.3 | 573 |
| 1x54.6 RM + 3x25 RM + 2x16 RM | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 | 29.7 | 639 |
| 1x54.6 RM + 3x25 RM + 3x16 RM | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 | 31.1 | 705 |
| 1x54.6 RM + 3x35 RM | 0.630/0.868 | 5.2 | 132 | 25.1 | 615 |
| 1x54.6 RM + 3x35 RM + 1x16 RM | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 | 28.1 | 680 |
| 1x54.6 RM + 3x35 RM + 2x16 RM | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 | 34.3 | 748 |
| 1x54.6 RM + 3x35 RM + 3x16 RM | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 | 35.9 | 814 |
| 1x54.6 RM + 3x35 RM + 1x25 RM | 0.630/0.868/1.200 | 5.2/3.8 | 132/107 | 28.1 | 714 |
| 1x54.6 RM + 3x50 RM | 0.630/0.641 | 7.6 | 165 | 28.2 | 741 |
| 1x54.6 RM + 3x50 RM + 1x16 RM | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 | 31.6 | 806 |
| 1x54.6 RM + 3x50 RM + 2x16 RM | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 | 38.6 | 875 |
| 1x54.6 RM + 3x50 RM + 3x16 RM | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 | 40.4 | 940 |
| 1x54.6 RM + 3x50 RM + 1x25 RM | 0.630/0.641/1.200 | 7.6/3.8 | 165/107 | 31.6 | 841 |
| 1x54.6 RM + 3x70 RM | 0.630/0.443 | 10.2 | 205 | 33.0 | 950 |
| 1x54.6 RM + 3x70 RM + 1x16 RM | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 | 37.0 | 1014 |
| 1x54.6 RM + 3x70 RM + 2x16 RM | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 | 45.2 | 1083 |
| 1x54.6 RM + 3x70 RM + 3x16 RM | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 | 47.3 | 1148 |
| 1x54.6 RM + 3x70 RM + 1x25 RM | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 | 37.0 | 1048 |
| 1x54.6 RM + 3x70 RM + 2x25 RM | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 | 45.2 | 1150 |
| 1x54.6 RM + 3x70 RM + 3x25 RM | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 | 47.3 | 1250 |
| 1x54.6 RM + 3x95 RM | 0.630/0.320 | 13.5 | 240 | 37.4 | 1176 |
| 1x54.6 RM + 3x95 RM + 1x16 RM | 0.630/0.320/1.910 | 13.5/2.3 | 240/72 | 41.9 | 1243 |
Request the Complete Data Sheet
From Production to Delivery
From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.
Production
Aluminium wires are stranded or compacted to the required conductor design, each core receives the specified PE or XLPE insulation, and the completed cores are assembled into the selected self-supporting or neutral-messenger bundle.
Inspection
Inspection covers conductor construction, insulation thickness and surface, core identification, lay length, finished dimensions and the electrical or mechanical tests listed in the purchase specification and applicable cable schedule.
Packaging
The completed bundle is wound on a drum sized for its diameter and requested delivery length, with cable ends sealed and the outer layers protected against crushing, abrasion and contamination during handling.
Shipping
Before dispatch, drum markings and shipping records identify the voltage designation, complete core formula, standard, length and manufacturing batch so that the receiving team can match each drum to its installation section.
Frequently Asked Questions
Which LV ABC construction is likely to suit my network?
The first decision is whether the governing utility system uses an equal-core self-supporting bundle or a dedicated neutral-messenger construction. The required voltage, core formula, route, span duty and fittings then narrow the available range. Share those details with us and we will present the matching construction and table in the quotation.
Can you quote LV ABC to different national standards?
Yes. BS 7870-5, HD 626, NF C 33-209 and AS/NZS 3560.1 define different conductor, core and support arrangements. Tell us the required standard and edition, and we will quote the corresponding construction with its complete core formula and technical data.
Can a public-lighting core be included in the bundle?
Where the selected standard provides that arrangement, we can include the specified lighting core or cores. Please tell us the number, conductor size and identification requirement; our quotation will show the complete core formula so your team can review the distribution and lighting circuits together.
Can AMPO help with clamps and insulation-piercing connectors?
We can include compatible accessory options when the bundle type, conductor sizes, messenger material and pole arrangement are provided. This lets us match suspension or anchoring hardware and connection products to the finished cable diameter, rather than offering accessories from the nominal phase size alone.
What installation information helps you select drum lengths?
A route schedule, pole spacing, pulling or stringing method, maximum acceptable drum mass and preferred section lengths are helpful. We use these details to discuss practical manufacturing and packing lengths, reduce unnecessary joints and prepare drum identification that follows the customer’s installation plan.
What should I send for an accurate LV ABC quotation?
Please provide voltage, standard and edition, phase and neutral sizes, complete core configuration, support concept, quantity, delivery lengths, installation environment, required accessories and inspection documents. If part of the information is not yet fixed, we can identify the missing selection points before finalising the commercial offer.