DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V is a flexible paired PVC signal and control cable with fine stranded copper conductors, DIN 47100 colour-coded cores, polyester wrapping, an overall tinned copper braid and a grey PVC outer sheath. It is intended for measuring, control, communication and data-processing circuits.
PRODUCT OVERVIEW
LiYCY TP provides a compact screened cable for low-voltage signal transmission. The twisted-pair layout supports control and measuring circuits, while the copper braid reduces electrical interference and can provide signal earthing and fixed-potential bonding where the installation design permits.
The catalogue product is rated 250V and is available from 0.14 mm2 to 1.00 mm2 in the listed pair counts. The published service range is -30 C to +70 C and the minimum bending radius is six times the finished cable diameter.
KEY FEATURES
- DIN VDE 0814 design reference for the relevant product elements.
- Fine stranded Class 5 bare copper conductors.
- PVC Y12 core insulation and flexible PVC outer sheath.
- Twisted-pair construction with DIN 47100 colour identification.
- Overall tinned copper wire braid screen.
- 250V nominal voltage and up to 1500V catalogue test voltage.
- -30 C to +70 C catalogue temperature range.
- Flame test reference IEC 60332-1-2 / VDE 0482-265-2-1.
CABLE CONSTRUCTION
Conductor | Fine stranded bare copper, Class 5 according to VDE 0295 / IEC 60228 |
Insulation | PVC Y12 according to DIN VDE 0207 Part 4 |
Core Assembly | Cores twisted into pairs; pairs laid up in layers |
Core Identification | Colour coded according to DIN 47100 |
Wrapping | Polyester foil wrapping |
Overall Screen | Tinned copper wire braid |
Drain Wire | Tinned copper stranded drain wire when requested |
Overall Jacket | Special flexible PVC compound |
Sheath Colour | Grey RAL 7001 or pebble grey RAL 7032; other colours on request |
DIN VDE 0814 DESIGN FOCUS
Focus | How It Relates to This Product |
Flexible Cord Design | Fine-wire conductors and a flexible PVC-sheathed multi-pair construction |
Paired Assembly | Cores twisted into pairs and pairs laid up in layers |
Screening | Overall tinned copper wire braid for electromagnetic screening and equipotential bonding |
Temperature Basis | Catalogue service range -30 C to +70 C |
Core Colours | DIN 47100 colour identification |
WHY DIN VDE 0814
DIN VDE 0814 is used on this page as the principal reference for the flexible cord and cable assembly. The LiYCY TP construction combines fine stranded conductors, paired PVC insulated cores, an overall tinned copper braid and a flexible PVC sheath. Published sizes, diameters and weights remain manufacturer product data.
DIN 47100 is retained as the conductor colour-identification reference and is not presented as the complete finished-cable manufacturing standard.
ELECTRICAL AND THERMAL PERFORMANCE
Condition | Catalogue Value |
Nominal Voltage | 250V |
Test Voltage | 26 AWG: 1200V; conductor sizes larger than 26 AWG: 1500V |
Temperature Range | -30 C to +70 C |
Minimum Bending Radius | 6 x finished cable diameter |
Nominal Inductance | 0.65 mH/km |
Mutual Capacitance | Conductor/conductor 120 nF/km; conductor/screen 160 nF/km |
PRODUCT APPLICATIONS
- Measurement and instrumentation circuits.
- Low-voltage control and monitoring systems.
- Communication, office and data-processing equipment.
- Switchboards, scales and appliance engineering.
- Indoor dry or damp installations with low mechanical stress.
- Applications requiring an overall braid screen against electrical interference.
Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.
| Pairs | OD in | OD mm | Weight lb/1000 ft | Weight kg/km |
|---|---|---|---|---|
| 2 | 0.406 | 10.3 | 95 | 142 |
| 3 | 0.409 | 10.4 | 116 | 173 |
| 4 | 0.445 | 11.3 | 142 | 212 |
| 5 | 0.465 | 11.8 | 179 | 266 |
Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.
| Pairs | OD in | OD mm | Weight lb/1000 ft | Weight kg/km |
|---|---|---|---|---|
| 2 | 0.339 | 8.6 | 62 | 93 |
| 3 | 0.343 | 8.7 | 87 | 129 |
| 4 | 0.370 | 9.4 | 98 | 146 |
| 6 | 0.437 | 11.1 | 133 | 198 |
| 8 | 0.516 | 13.1 | 174 | 259 |
| 12 | 0.587 | 14.9 | 238 | 354 |
| 16 | 0.650 | 16.5 | 308 | 459 |
Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.
| Pairs | OD in | OD mm | Weight lb/1000 ft | Weight kg/km |
|---|---|---|---|---|
| 2 | 0.276 | 7.0 | 36 | 54 |
| 3 | 0.280 | 7.1 | 44 | 66 |
| 4 | 0.299 | 7.6 | 54 | 81 |
| 6 | 0.335 | 8.5 | 77 | 115 |
| 8 | 0.406 | 10.3 | 87 | 130 |
| 10 | 0.433 | 11.0 | 106 | 158 |
| 12 | 0.445 | 11.3 | 128 | 190 |
| 16 | 0.492 | 12.5 | 160 | 238 |
| 25 | 0.634 | 16.1 | 231 | 344 |
Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.
| Pairs | OD in | OD mm | Weight lb/1000 ft | Weight kg/km |
|---|---|---|---|---|
| 2 | 0.224 | 5.7 | 26 | 39 |
| 3 | 0.228 | 5.8 | 32 | 48 |
| 4 | 0.244 | 6.2 | 36 | 54 |
| 6 | 0.280 | 7.1 | 57 | 85 |
| 8 | 0.323 | 8.2 | 65 | 97 |
| 10 | 0.343 | 8.7 | 74 | 110 |
| 12 | 0.350 | 8.9 | 95 | 142 |
| 16 | 0.402 | 10.2 | 103 | 154 |
| 20 | 0.445 | 11.3 | 124 | 184 |
| 25 | 0.492 | 12.5 | 160 | 238 |
| 30 | 0.516 | 13.1 | 181 | 270 |
Request the Complete Data Sheet
From Production to Delivery
From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.
Production
Conductors are insulated, colour identified, twisted into pairs, laid up in layers, wrapped, braid screened and sheathed with the specified grey PVC compound.
Inspection
Inspection focuses on conductor construction, insulation continuity, pair identification, braid coverage, finished diameter, cable weight, voltage test and marking.
Packaging
Cable is wound on reels or drums suitable for the ordered size and length. Marking, packing, inspection records and requested standard or test documentation are checked against the order before shipment.
Shipping
Cable is wound on reels or drums suitable for the ordered size and length. Marking, packing, inspection records and requested standard or test documentation are checked against the order before shipment.
Frequently Asked Questions
What does DIN VDE 0814 mean on this product page
It identifies DIN VDE 0814 as the principal design reference for this version of the LiYCY TP landing page. The exact compliance statement must match the offered cable documentation and any applicable approval certificate.
Is DIN 47100 the complete cable standard
No. DIN 47100 is used here for core colour identification. The cable construction, electrical data and finished dimensions are defined by the product specification and the other referenced standards.
Can this cable be used as a power cable
The product is intended for low-voltage signal, measuring, communication and control circuits. Suitability for a particular installation must be confirmed against the governing electrical rules and project specification.
How should the diameter and weight values be used
Use the catalogue values for preliminary cable selection, tray or conduit planning, shipping estimates and termination design. Final production values may vary within normal manufacturing tolerances.
What information is required for an accurate quotation
Provide pair count, conductor size, required length, sheath colour, installation environment, standard edition, cable marking, test documentation and any special braid, drain-wire, flame or packaging requirements.
What products do you supply for the power cable industry?
We provide a wide range of cable materials and electrical products, including aluminum conductors, aluminum rods, aluminum wires, overhead conductors, medium and low voltage power cables, cable insulation materials, filling materials, shielding materials, and cable manufacturing consumables.We provide customized solutions according to different cable manufacturing requirements.
Request for Free Consultation
Contact Information
Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.