AS/NZS 3008 Multicore + Earth Control Cable 0.6/1kV

AS/NZS 3008 Multicore + Earth Control Cable is a 0.6/1kV PVC insulated and PVC sheathed control cable presented with installation-based current rating, resistance, reactance and voltage-drop data. Available in 1.5 mm² and 2.5 mm² from 2C+E to 50C+E, it is intended for fixed control circuits where cable size must be selected according to load, route and installation condition.

PRODUCT OVERVIEW

The cable combines plain annealed copper conductors, PVC V-90 insulation, white numbered control cores, a green/yellow earth conductor and a PVC 5V-90 outer sheath. The product range is available in 1.5 mm² and 2.5 mm² conductor sizes, with multicore configurations extending from 2C+E to 50C+E.

The main selection focus is electrical performance under different installation methods. Current ratings are provided for unenclosed-in-air, direct-buried and buried-in-duct conditions, together with maximum d.c. resistance at 20°C, maximum a.c. resistance at 75°C, reactance and three-phase voltage drop at 75°C. These values allow the buyer or engineer to compare conductor size, core configuration and route conditions before quotation.

KEY FEATURES

  • Installation-based current ratings for air, direct burial and ducts.
  • Separate ratings for 2C+E and 3-50C+E configurations.
  • Maximum DC resistance at 20°C.
  • Maximum AC resistance at 75°C.
  • Reactance values for electrical design.
  • Three-phase voltage-drop data at 75°C.
  • 5 mm² and 2.5 mm² conductor sizes.
  • 2C+E to 50C+E multicore range.

CURRENT RATING BY INSTALLATION METHOD

Area mm²

Configuration

Air A

Direct Buried A

In Ducts A

Max DC R @20°C Ω/km

Max AC R @75°C Ω/km

Reactance Ω/km

3-Phase V-Drop @75°C mV/A·m

1.5

2C+E

18

14

22

13.6

16.5

0.111

33.0

1.5

3-50C+E

15

13

19

13.6

16.5

0.111

33.0

2.5

2C+E

26

20

31

7.41

9.01

0.102

18.0

2.5

3-50C+E

22

18

26

7.41

9.01

0.102

18.0

ELECTRICAL CHARACTERISTICS

Area

DC Resistance

AC Resistance

Reactance

Voltage Drop

1.5 mm²

13.6 Ω/km @20°C

16.5 Ω/km @75°C

0.111 Ω/km

33.0 mV/A·m @75°C

2.5 mm²

7.41 Ω/km @20°C

9.01 Ω/km @75°C

0.102 Ω/km

18.0 mV/A·m @75°C

AVAILABLE PRODUCT RANGE

Area

Conductor

Core Range

Core Insul.

Earth

Earth Insul.

OD Range

1.5 mm²

7/0.50

2C+E-50C+E

0.8 mm

1.5 mm²

0.6 mm

10.6-30.8 mm

2.5 mm²

7/0.67

2C+E-50C+E

0.8 mm

2.5 mm²

0.7 mm

11.6-35.0 mm

PRODUCT APPLICATIONS

  • Commercial building control circuits.
  • Industrial plant control and auxiliary circuits.
  • Mining systems where the installation route is protected from mechanical damage.
  • Electricity-authority and utility control installations.
  • Unenclosed fixed installation.
  • Conduit installation.
  • Direct burial where mechanical damage is not expected.
  • Underground ducts.

Request the Complete Data Sheet

If you need a specific product catalogue or related standard file, please contact us.

From Production to Delivery

From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.

cable production line with finished cable being wound onto a reel

Production

Plain annealed copper conductors are stranded to the specified construction, insulated with PVC V-90, laid up with the required green/yellow earth conductor, and finished with a PVC 5V-90 outer sheath. Conductor size, core count, insulation thickness and cable dimensions follow the approved design.

Cable and conductor quality inspection and testing

Inspection

Inspection includes conductor resistance, insulation and sheath condition, core identification, overall dimensions and finished-cable electrical checks. Current-rating selection is matched to the intended installation condition.

Overhead conductors packed on wooden drums for shipment

Packaging

Finished cables are wound onto suitable drums according to ordered cable size and length. Cable ends are secured and protected, and drum identification can include cable type, conductor size, core configuration, length and project reference.

Wooden cable drums secured inside a shipping container

Shipping

Before shipment, cable drums and accompanying documents are checked against the order and packing list. Product identification, inspection records and technical documentation can be prepared according to customer and project requirements.

Frequently Asked Questions

What current rating does 1.5 mm² 2C+E have?

18 A in air, 14 A direct buried and 22 A in ducts.

26 A in air, 20 A direct buried and 31 A in ducts.

33.0 mV/A·m at 75°C for three-phase.

18.0 mV/A·m at 75°C for three-phase.

Because conductor size, core configuration and installation condition change the thermal conditions of the cable.

Request for Free Consultation

Contact Information

Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.

Explore More

Related Products
BS 7629-1 SR Insulated Fire Resistant Control Cable 300/500V
BS 7629-1 Fire Resistant Screened Control Cable 300/500V
BS 5839-9 Emergency Voice Communication Fire Resistant Screened Cable
Compatible Hardware
BS 7629-1 SR Insulated Fire Resistant Control Cable 300/500V
BS 7629-1 Fire Resistant Screened Control Cable 300/500V
BS 5839-9 Emergency Voice Communication Fire Resistant Screened Cable
Knowledge Articles
Customer Visits Our Factory for Product Inspection and Quality Verification
AAAC all aluminium alloy conductor stranded wire
AAAC Conductor Selection Guide: How to Choose the Right AAAC for Overhead Lines
International Airport Expansion Project in Saudi Arabia

For Immediate Assistance, Please Contact us Now!