BS 7629-1 Fire Resistant Screened Control Cable 300/500V

BS 7629-1 Fire Resistant Screened Control Cable is a 300/500V mica-and-silicone-rubber insulated, overall-screened LSZH control cable for circuits that must retain functionality during fire conditions. The construction combines copper conductors, fire-resistant insulation, aluminum/polyester screening with tinned-copper drain wire and a low-smoke zero-halogen sheath.

PRODUCT OVERVIEW

This 300/500V fire-resistant overall-screened control cable combines plain annealed copper conductors with a mica-glass fire-resistant tape and fire-resistant silicone-rubber insulation, an aluminum/polyester overall screen with tinned-copper drain wire, and a low-smoke zero-halogen outer sheath. The construction is designed to maintain circuit integrity during fire conditions while also providing an overall screen for control and signalling circuits.

BS 7629-1 is the basic design reference for this cable. The range includes 2-, 3-, 4-, 7-, 12- and 19-core constructions, with solid or stranded copper conductors depending on the size and cable code. The design also incorporates dedicated circuit-protective conductors or drain wires according to core count, together with specified colour coding and fire-performance characteristics.

KEY FEATURES

  • 300/500V fire-resistant screened control cable.
  • Plain annealed copper conductors: solid Class 1 or stranded Class 2 to IEC/EN 60228.
  • Mica-glass fire-resistant tape with fire-resistant silicone-rubber insulation type EI2.
  • Aluminum/polyester overall screen with tinned-copper drain wire.
  • Thermoplastic LSZH outer sheath type LTS3; thermosetting LSZH SW2-SW4 can be offered.
  • PH120 mechanical-shock circuit-integrity reference in the product designation.
  • Operating temperature: -30°C to +90°C; installation temperature: -20°C to +50°C.
  • Minimum bending radius: 7.5 × overall diameter.
  • Basic design to BS 7629-1.
  • 2-, 3-, 4-, 7-, 12- and 19-core configurations.

CABLE CONSTRUCTION

Voltage Rating

300/500V

Conductors

Plain annealed copper; solid IEC/EN 60228 Class 1 or stranded Class 2

Insulation

Mica glass fire-resistant tape + fire-resistant silicone rubber compound type EI2

Cabling

Cores cabled in concentric layers with suitable non-hygroscopic fillers

Overall Screen

Aluminum/polyester tape with tinned copper drain wire

Circuit Protective Conductor

Uninsulated tinned copper conductor, same section and class as insulated conductors in 2-, 3- and 4-core cables

Drain Wire for >4 Cores

0.5 mm² tinned copper conductor

Outer Sheath

Thermoplastic LSZH LTS3; optional thermosetting LSZH SW2-SW4

Sheath Colour

Red or white; other colours on request

Operating Temperature

-30°C to +90°C

Installation Temperature

-20°C to +50°C

Minimum Bending Radius

7.5 × overall diameter

PRODUCT APPLICATIONS

  • Fire-resistant control circuits requiring maintained circuit integrity.
  • Emergency lighting circuits.
  • Fire detection and fire alarm systems.
  • Voice alarm systems.
  • Emergency voice communication systems.
  • Building and infrastructure projects requiring screened LSZH control cable.

CONSTRUCTION PARAMETERS

Cores Cross Section mm² Insulation mm Sheath mm Overall Diameter mm Approx. Weight kg/km
2 1.0 0.6 0.9 7.9 85
2 1.5 0.7 0.9 8.8 105
2 2.5 0.8 1.0 10.2 150
2 1.5 0.7 0.9 9.2 110
2 2.5 0.8 1.0 10.3 155
2 4.0 0.8 1.1 12.2 220
3 1.0 0.6 0.9 8.4 105
3 1.5 0.7 0.9 9.3 130
3 2.5 0.8 1.0 10.8 190
3 1.5 0.7 0.9 9.4 135
3 2.5 0.8 1.0 10.9 190
3 4.0 0.8 1.1 13.0 280
4 1.0 0.6 1.0 9.3 125
4 1.5 0.7 1.0 10.3 165
4 2.5 0.8 1.1 12.0 240
4 1.5 0.7 1.0 10.5 170
4 2.5 0.8 1.1 12.1 250
4 4.0 0.8 1.2 14.4 350
7 1.0 0.6 1.0 10.5 175
7 1.5 0.7 1.1 12.1 230
12 1.0 0.6 1.1 14.5 300
12 1.5 0.7 1.2 16.0 380
19 1.0 0.6 1.2 17.5 470
19 1.5 0.7 1.3 17.5 470

Request the Complete Data Sheet

If you need a specific product catalogue or related standard file, please contact us.

From Production to Delivery

From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.

cable production line with finished cable being wound onto a reel

Production

Plain annealed copper conductors are prepared as solid Class 1 or stranded Class 2 constructions, wrapped with mica-glass fire-resistant tape, insulated with fire-resistant silicone rubber, cabled with fillers, screened with aluminum/polyester tape and a tinned-copper drain wire, then finished with the specified LSZH sheath.

Cable and conductor quality inspection and testing

Inspection

Inspection focuses on conductor class, mica/silicone insulation, screen continuity, drain/CPC arrangement, sheath integrity, dielectric test, insulation resistance, dimensions and required fire-performance documentation.

Packaged cable drums stored in the factory warehouse

Packaging

Finished cables are wound onto suitable drums according to ordered size and length. Cable ends are secured and protected, and drum identification can include cable code, core count, conductor size, length and project reference.

Wooden cable drums secured inside a shipping container

Shipping

Before shipment, cable drums and accompanying technical documents are checked against the order and packing list. Test records, product identification and project documentation can be prepared according to customer requirements.

Frequently Asked Questions

What is the rated voltage?

300/500V.

BS 7629-1.

Solid Class 1 and stranded Class 2 copper conductors to IEC/EN 60228.

Aluminum/polyester tape with tinned-copper drain wire.

Yes. Thermoplastic LSZH LTS3 is specified, with thermosetting LSZH SW2-SW4 available as an option.

7.5 times the overall cable diameter.

Request for Free Consultation

Contact Information

Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.

Explore More

Related Products
BS 7629-1 SR Insulated Fire Resistant Control Cable 300/500V
BS 7629-1 Fire Resistant Screened Control Cable 300/500V
BS 5839-9 Emergency Voice Communication Fire Resistant Screened Cable
Compatible Hardware
BS 7629-1 SR Insulated Fire Resistant Control Cable 300/500V
BS 7629-1 Fire Resistant Screened Control Cable 300/500V
BS 5839-9 Emergency Voice Communication Fire Resistant Screened Cable
Knowledge Articles
Customer Visits Our Factory for Product Inspection and Quality Verification
AAAC all aluminium alloy conductor stranded wire
AAAC Conductor Selection Guide: How to Choose the Right AAAC for Overhead Lines
International Airport Expansion Project in Saudi Arabia

For Immediate Assistance, Please Contact us Now!