IEC 60502-1 CVV-SWA Steel Wire Armoured Control Cable 600V

IEC 60502-1 referenced CVV-SWA Control Cable is a PVC-insulated, PVC-sheathed multicore copper control cable with galvanized steel-wire armour for fixed installations requiring added mechanical protection. It is intended for duct, cable-tray and direct-buried routes, including installations where the cable may be exposed to water along the route.

PRODUCT OVERVIEW

CVV-SWA combines stranded annealed copper conductors, PVC insulation, optional non-hygroscopic filler and polyester binding tape, a black PVC inner sheath, galvanized steel-wire armour, separator tape and a black PVC outer sheath. The armour is the defining feature of this construction: it protects the multicore control cable against external mechanical stress in buried, ducted and industrial installation routes.

The listed range covers 0.5 mm² to 6 mm² conductors and 2 to 30 cores. The source data states a maximum conductor temperature of 70°C, a circuit voltage not exceeding 600V and a 3500V test voltage. A special flame-retardant outer sheath can be supplied where required.

KEY FEATURES

  • Reference Standard: IEC 60502-1.
  • Stranded annealed copper conductors, 0.5-6 mm².
  • PVC insulation and black PVC inner sheath.
  • Galvanized steel-wire armour for mechanical protection.
  • Polyester (Mylar) separator tape over the armour.
  • Black PVC outer sheath; optional special flame-retardant sheath.
  • 2-30 cores in the listed technical range.
  • Suitable for duct, cable tray and direct burial as stated in the source data.
  • Source data states the cable may be subject to water immersion along the route.
  • Maximum conductor temperature: 70°C.
  • Circuit voltage: not exceeding 600V.
  • Test voltage: 3500V.

CABLE CONSTRUCTION

Conductor

Stranded annealed copper wires, 0.5 mm² to 6 mm²

Insulation

Polyvinyl chloride (PVC)

Core Identification

2-4 cores: Black, White, Red and Green; more than 4 cores: black cores with marking numbers

Filler

Non-hygroscopic material, optional

Binding Tape

Polyester (Mylar) tape, optional

Inner Sheath

PVC, black

Armour

Galvanized steel wire

Separator Tape

Polyester (Mylar) tape

Outer Sheath

PVC, black; special flame-retardant type available

IEC 60502-1 RELATED DESIGN FEATURES

Design Feature

Product Data

Conductor

Stranded annealed copper wires

Insulation

PVC

Inner Sheath

Black PVC

Armour

Galvanized steel wire

Separator Tape

Polyester (Mylar) tape

Outer Sheath

Black PVC

Maximum Conductor Temperature

70°C

Test Voltage

3500V

Electrical Data

Maximum conductor resistance at 20°C and minimum insulation resistance at 70°C listed by size

STANDARD REFERENCE & COMPLIANCE

Item

Details

Referenced Standard

IEC 60502-1

Current Edition

IEC 60502-1:2021

Product Rating

Steel-wire-armoured control cable for circuits up to 600V

Compliance Note

IEC 60502-1 is referenced in the product specification. For projects requiring edition-specific compliance, confirm the required voltage designation and test documentation before approval.

IEC 60502-1 is used here as the reference standard stated for the CVV-SWA product family. Where a project calls for a specific IEC edition, voltage designation or approval package, those requirements should be stated during technical review or quotation.

WHY CVV-SWA USES STEEL-WIRE ARMOUR

CVV-SWA is selected when a control cable needs physical protection in addition to its electrical insulation and sheath system. The galvanized steel wires form a robust armour layer around the inner-sheathed core assembly, helping protect the cable against mechanical stress during direct burial, duct installation and industrial routing.

Steel-wire armour should not be treated as the same function as an electrostatic screen. Where interference control is a project requirement, the need for a dedicated screened control-cable construction should be reviewed separately.

PRODUCT APPLICATIONS

  • Industrial and utility control circuits requiring mechanical protection.
  • Direct-buried control-cable routes.
  • Underground duct installations.
  • Cable-tray control wiring.
  • Outdoor or plant installations where a steel-wire-armoured multicore control cable is specified.
  • Routes where water exposure is anticipated and the overall installation system is designed accordingly.

INSTALLATION ENVIRONMENT

Duct Installation

Suitable as stated in the source data

Cable Tray

Suitable as stated in the source data

Direct Burial

Suitable as stated in the source data

Water Exposure

Source data states the cable may be subject to immersion in water along the route

For projects involving continuous or repeated water exposure, sealing, cable-entry, jointing and termination requirements should be confirmed as part of the complete installation design rather than inferred from the cable description alone.

Cores Area (mm²) No. & Dia. of Wires Cond. Dia. mm Insul. mm Inner Sheath mm SWA Wire Dia. mm Outer Sheath mm Overall Dia. mm Max. R @20°C Ω/km Min. IR @70°C (source) Weight kg/km
2 0.5 7/0.30 0.9 0.8 1 0.8 1.8 14.5 36 0.0162 300
2 0.75 7/0.37 1.11 0.8 1 0.8 1.8 15 24.5 0.0142 320
2 1 7/0.43 1.29 0.8 1 0.8 1.8 15.5 18.1 0.0128 340
2 1.5 7/0.52 1.56 0.8 1 0.8 1.8 16 12.1 0.0112 370
2 2.5 7/0.67 2.01 0.8 1 0.8 1.8 17 7.41 0.0093 430
2 4 7/0.85 2.55 1 1 1.25 1.8 20 4.61 0.0092 670
2 6 7/1.04 3.12 1 1 1.25 1.8 21 3.08 0.0078 760
3 0.5 7/0.30 0.9 0.8 1 0.8 1.8 15 36 0.0162 320
3 0.75 7/0.37 1.11 0.8 1 0.8 1.8 15.5 24.5 0.0142 350
3 1 7/0.43 1.29 0.8 1 0.8 1.8 16 18.1 0.0128 370
3 1.5 7/0.52 1.56 0.8 1 0.8 1.8 16.5 12.1 0.0112 410
3 2.5 7/0.67 2.01 0.8 1 1.25 1.8 17.5 7.41 0.0093 480
3 4 7/0.85 2.55 1 1 1.25 1.8 20.5 4.61 0.0092 750
3 6 7/1.04 3.12 1 1 1.25 1.8 22 3.08 0.0078 870
4 0.5 7/0.30 0.9 0.8 1 0.8 1.8 16 36 0.0162 360
4 0.75 7/0.37 1.11 0.8 1 0.8 1.8 16.5 24.5 0.0142 390
4 1 7/0.43 1.29 0.8 1 0.8 1.8 17 18.1 0.0128 420
4 1.5 7/0.52 1.56 0.8 1 0.8 1.8 17.5 12.1 0.0112 460
4 2.5 7/0.67 2.01 0.8 1 1.25 1.8 19.5 7.41 0.0093 660
4 4 7/0.85 2.55 1 1 1.25 1.8 22 4.61 0.0092 860
4 6 7/1.04 3.12 1 1 1.25 1.8 23.5 3.08 0.0078 1010
5 0.5 7/0.30 0.9 0.8 1 0.8 1.8 16.5 36 0.0162 400
5 0.75 7/0.37 1.11 0.8 1 0.8 1.8 17.5 24.5 0.0142 430
5 1 7/0.43 1.29 0.8 1 0.8 1.8 18 18.1 0.0128 470
5 1.5 7/0.52 1.56 0.8 1 1.25 1.8 19.5 12.1 0.0112 640
5 2.5 7/0.67 2.01 0.8 1 1.25 1.8 20.5 7.41 0.0093 760
5 4 7/0.85 2.55 1 1 1.25 1.8 23.5 4.61 0.0092 990
5 6 7/1.04 3.12 1 1 1.25 1.8 25 3.08 0.0078 1170
6 0.5 7/0.30 0.9 0.8 1 0.8 1.8 17.5 36 0.0162 420
6 0.75 7/0.37 1.11 0.8 1 0.8 1.8 18 24.5 0.0142 470
6 1 7/0.43 1.29 0.8 1 1.25 1.8 19.5 18.1 0.0128 620
6 1.5 7/0.52 1.56 0.8 1 1.25 1.8 20.5 12.1 0.0112 690
6 2.5 7/0.67 2.01 0.8 1 1.25 1.8 22 7.41 0.0093 820
6 4 7/0.85 2.55 1 1 1.25 1.8 25 4.61 0.0092 1070
6 6 7/1.04 3.12 1 1 1.6 1.8 27 3.08 0.0078 1420
7 0.5 7/0.30 0.9 0.8 1 0.8 1.8 17.5 36 0.0162 430
7 0.75 7/0.37 1.11 0.8 1 0.8 1.8 18 24.5 0.0142 480
7 1 7/0.43 1.29 0.8 1 1.25 1.8 19.5 18.1 0.0128 630
7 1.5 7/0.52 1.56 0.8 1 1.25 1.8 20.5 12.1 0.0112 700
7 2.5 7/0.67 2.01 0.8 1 1.25 1.8 22 7.41 0.0093 840
7 4 7/0.85 2.55 1 1 1.25 1.8 25 4.61 0.0092 1100
7 6 7/1.04 3.12 1 1 1.6 1.8 27 3.08 0.0078 1470
8 0.5 7/0.30 0.9 0.8 1 1.25 1.8 19.5 36 0.0162 580
8 0.75 7/0.37 1.11 0.8 1 1.25 1.8 20 24.5 0.0142 640
8 1 7/0.43 1.29 0.8 1 1.25 1.8 20.5 18.1 0.0128 690
8 1.5 7/0.52 1.56 0.8 1 1.25 1.8 21.5 12.1 0.0112 770
8 2.5 7/0.67 2.01 0.8 1 1.25 1.8 23 7.41 0.0093 930
8 4 7/0.85 2.55 1 1 1.6 1.8 27 4.61 0.0092 1370
8 6 7/1.04 3.12 1 1 1.6 1.8 29 3.08 0.0078 1640
9 0.5 7/0.30 0.9 0.8 1 1.25 1.8 20 36 0.0162 640
9 0.75 7/0.37 1.11 0.8 1 1.25 1.8 21 24.5 0.0142 700
9 1 7/0.43 1.29 0.8 1 1.25 1.8 21.5 18.1 0.0128 750
9 1.5 7/0.52 1.56 0.8 1 1.25 1.8 22.5 12.1 0.0112 840
9 2.5 7/0.67 2.01 0.8 1 1.25 1.8 24 7.41 0.0093 1010
9 4 7/0.85 2.55 1 1 1.6 1.8 28.5 4.61 0.0092 1500
9 6 7/1.04 3.12 1 1 1.6 1.8 30.5 3.08 0.0078 1800
10 0.5 7/0.30 0.9 0.8 1 1.25 1.8 21 36 0.0162 680
10 0.75 7/0.37 1.11 0.8 1 1.25 1.8 22 24.5 0.0142 740
10 1 7/0.43 1.29 0.8 1 1.25 1.8 23 18.1 0.0128 810
10 1.5 7/0.52 1.56 0.8 1 1.25 1.8 24 12.1 0.0112 910
10 2.5 7/0.67 2.01 0.8 1 1.6 1.8 26.5 7.41 0.0093 1240
10 4 7/0.85 2.55 1 1 1.6 1.8 30.5 4.61 0.0092 1620
10 6 7/1.04 3.12 1 1 1.6 1.9 33 3.08 0.0078 1980
11 0.5 7/0.30 0.9 0.8 1 1.25 1.8 21.5 36 0.0162 710
11 0.75 7/0.37 1.11 0.8 1 1.25 1.8 22.5 24.5 0.0142 790
11 1 7/0.43 1.29 0.8 1 1.25 1.8 23.5 18.1 0.0128 850
11 1.5 7/0.52 1.56 0.8 1 1.25 1.8 24.5 12.1 0.0112 960
11 2.5 7/0.67 2.01 0.8 1 1.6 1.8 27 7.41 0.0093 1310
11 4 7/0.85 2.55 1 1 1.6 1.8 31 4.61 0.0092 1750
11 6 7/1.04 3.12 1 1 1.6 1.9 33.5 3.08 0.0078 2130
12 0.5 7/0.30 0.9 0.8 1 1.25 1.8 21.5 36 0.0162 720
12 0.75 7/0.37 1.11 0.8 1 1.25 1.8 22.5 24.5 0.0142 800
12 1 7/0.43 1.29 0.8 1 1.25 1.8 23.5 18.1 0.0128 860
12 1.5 7/0.52 1.56 0.8 1 1.25 1.8 24.5 12.1 0.0112 980
12 2.5 7/0.67 2.01 0.8 1 1.6 1.8 27 7.41 0.0093 1330
12 4 7/0.85 2.55 1 1 1.6 1.8 31 4.61 0.0092 1780
12 6 7/1.04 3.12 1 1 1.6 1.9 33.5 3.08 0.0078 2190
13 0.5 7/0.30 0.9 0.8 1 1.25 1.8 22.5 36 0.0162 760
13 0.75 7/0.37 1.11 0.8 1 1.25 1.8 23.5 24.5 0.0142 840
13 1 7/0.43 1.29 0.8 1 1.25 1.8 24 18.1 0.0128 920
13 1.5 7/0.52 1.56 0.8 1 1.25 1.8 26 12.1 0.0112 1190
13 2.5 7/0.67 2.01 0.8 1 1.6 1.8 28 7.41 0.0093 1430
13 4 7/0.85 2.55 1 1 1.6 1.8 32.5 4.61 0.0092 1910
13 6 7/1.04 3.12 1 1 1.6 1.9 35 3.08 0.0078 2350
14 0.5 7/0.30 0.9 0.8 1 1.25 1.8 22.5 36 0.0162 770
14 0.75 7/0.37 1.11 0.8 1 1.25 1.8 23.5 24.5 0.0142 850
14 1 7/0.43 1.29 0.8 1 1.25 1.8 24 18.1 0.0128 930
14 1.5 7/0.52 1.56 0.8 1 1.25 1.8 26 12.1 0.0112 1200
14 2.5 7/0.67 2.01 0.8 1 1.6 1.8 28 7.41 0.0093 1450
14 4 7/0.85 2.55 1 1 1.6 1.8 32.5 4.61 0.0092 1950
14 6 7/1.04 3.12 1 1 1.6 1.9 35 3.08 0.0078 2400
15 0.5 7/0.30 0.9 0.8 1 1.25 1.8 23 36 0.0162 820
15 0.75 7/0.37 1.11 0.8 1 1.25 1.8 24 24.5 0.0142 920
15 1 7/0.43 1.29 0.8 1 1.25 1.8 25 18.1 0.0128 1000
15 1.5 7/0.52 1.56 0.8 1 1.25 1.8 27 12.1 0.0112 1280
15 2.5 7/0.67 2.01 0.8 1 1.6 1.8 29 7.41 0.0093 1560
15 4 7/0.85 2.55 1 1 1.6 1.9 34 4.61 0.0092 2120
15 6 7/1.04 3.12 1 1 1.6 2 37 3.08 0.0078 2600
16 0.5 7/0.30 0.9 0.8 1 1.25 1.8 23 36 0.0162 830
16 0.75 7/0.37 1.11 0.8 1 1.25 1.8 24 24.5 0.0142 930
16 1 7/0.43 1.29 0.8 1 1.25 1.8 25 18.1 0.0128 1010
16 1.5 7/0.52 1.56 0.8 1 1.25 1.8 27 12.1 0.0112 1300
16 2.5 7/0.67 2.01 0.8 1 1.6 1.8 29 7.41 0.0093 1580
16 4 7/0.85 2.55 1 1 1.6 1.9 34 4.61 0.0092 2160
16 6 7/1.04 3.12 1 1 1.6 2 37 3.08 0.0078 2660
17 0.5 7/0.30 0.9 0.8 1 1.25 1.8 24 36 0.0162 880
17 0.75 7/0.37 1.11 0.8 1 1.25 1.8 25 24.5 0.0142 980
17 1 7/0.43 1.29 0.8 1 1.6 1.8 26.5 18.1 0.0128 1220
17 1.5 7/0.52 1.56 0.8 1 1.6 1.8 28 12.1 0.0112 1390
17 2.5 7/0.67 2.01 0.8 1 1.6 1.8 30 7.41 0.0093 1690
17 4 7/0.85 2.55 1 1 1.6 1.9 35.5 4.61 0.0092 2320
17 6 7/1.04 3.12 1 1 2 2 39.5 3.08 0.0078 3120
18 0.5 7/0.30 0.9 0.8 1 1.25 1.8 24 36 0.0162 890
18 0.75 7/0.37 1.11 0.8 1 1.25 1.8 25 24.5 0.0142 990
18 1 7/0.43 1.29 0.8 1 1.6 1.8 26.5 18.1 0.0128 1220
18 1.5 7/0.52 1.56 0.8 1 1.6 1.8 28 12.1 0.0112 1400
18 2.5 7/0.67 2.01 0.8 1 1.6 1.8 30 7.41 0.0093 1700
18 4 7/0.85 2.55 1 1 1.6 1.9 35.5 4.61 0.0092 2350
18 6 7/1.04 3.12 1 1 2 2 39.5 3.08 0.0078 3170
19 0.5 7/0.30 0.9 0.8 1 1.25 1.8 24 36 0.0162 900
19 0.75 7/0.37 1.11 0.8 1 1.25 1.8 25 24.5 0.0142 1000
19 1 7/0.43 1.29 0.8 1 1.6 1.8 26.5 18.1 0.0128 1240
19 1.5 7/0.52 1.56 0.8 1 1.6 1.8 28 12.1 0.0112 1410
19 2.5 7/0.67 2.01 0.8 1 1.6 1.8 30 7.41 0.0093 1730
19 4 7/0.85 2.55 1 1 1.6 1.9 35.5 4.61 0.0092 2390
19 6 7/1.04 3.12 1 1 2 2 39.5 3.08 0.0078 3220
20 0.5 7/0.30 0.9 0.8 1 1.25 1.8 25 36 0.0162 940
20 0.75 7/0.37 1.11 0.8 1 1.6 1.8 26.5 24.5 0.0142 1200
20 1 7/0.43 1.29 0.8 1 1.6 1.8 27.5 18.1 0.0128 1310
20 1.5 7/0.52 1.56 0.8 1 1.6 1.8 29 12.1 0.0112 1500
20 2.5 7/0.67 2.01 0.8 1 1.6 1.8 31.5 7.41 0.0093 1860
20 4 7/0.85 2.55 1 1 1.6 2 37 4.61 0.0092 2570
20 6 7/1.04 3.12 1 1.2 2 2.1 41.5 3.08 0.0078 3500
21 0.5 7/0.30 0.9 0.8 1 1.25 1.8 25 36 0.0162 950
21 0.75 7/0.37 1.11 0.8 1 1.6 1.8 26.5 24.5 0.0142 1210
21 1 7/0.43 1.29 0.8 1 1.6 1.8 27.5 18.1 0.0128 1320
21 1.5 7/0.52 1.56 0.8 1 1.6 1.8 29 12.1 0.0112 1510
21 2.5 7/0.67 2.01 0.8 1 1.6 1.8 31.5 7.41 0.0093 1870
21 4 7/0.85 2.55 1 1 1.6 2 37 4.61 0.0092 2590
21 6 7/1.04 3.12 1 1.2 2 2.1 41.5 3.08 0.0078 3540
22 0.5 7/0.30 0.9 0.8 1 1.6 1.8 26.5 36 0.0162 1150
22 0.75 7/0.37 1.11 0.8 1 1.6 1.8 27.5 24.5 0.0142 1280
22 1 7/0.43 1.29 0.8 1 1.6 1.8 28.5 18.1 0.0128 1410
22 1.5 7/0.52 1.56 0.8 1 1.6 1.8 30 12.1 0.0112 1600
22 2.5 7/0.67 2.01 0.8 1 1.6 1.9 33 7.41 0.0093 2000
22 4 7/0.85 2.55 1 1 2 2.1 39.5 4.61 0.0092 3040
22 6 7/1.04 3.12 1 1.2 2 2.2 43.5 3.08 0.0078 3810
23 0.5 7/0.30 0.9 0.8 1 1.6 1.8 26.5 36 0.0162 1160
23 0.75 7/0.37 1.11 0.8 1 1.6 1.8 27.5 24.5 0.0142 1290
23 1 7/0.43 1.29 0.8 1 1.6 1.8 28.5 18.1 0.0128 1420
23 1.5 7/0.52 1.56 0.8 1 1.6 1.8 30 12.1 0.0112 1620
23 2.5 7/0.67 2.01 0.8 1 1.6 1.9 33 7.41 0.0093 2030
23 4 7/0.85 2.55 1 1 2 2.1 39.5 4.61 0.0092 3080
23 6 7/1.04 3.12 1 1.2 2 2.2 43.5 3.08 0.0078 3870
24 0.5 7/0.30 0.9 0.8 1 1.6 1.8 27.5 36 0.0162 1210
24 0.75 7/0.37 1.11 0.8 1 1.6 1.8 28.5 24.5 0.0142 1340
24 1 7/0.43 1.29 0.8 1 1.6 1.8 29.5 18.1 0.0128 1470
24 1.5 7/0.52 1.56 0.8 1 1.6 1.8 31.5 12.1 0.0112 1680
24 2.5 7/0.67 2.01 0.8 1 1.6 1.9 34.5 7.41 0.0093 2110
24 4 7/0.85 2.55 1 1.2 2 2.1 42 4.61 0.0092 3260
24 6 7/1.04 3.12 1 1.2 2 2.2 45.5 3.08 0.0078 4070
25 0.5 7/0.30 0.9 0.8 1 1.6 1.8 28 36 0.0162 1250
25 0.75 7/0.37 1.11 0.8 1 1.6 1.8 29 24.5 0.0142 1390
25 1 7/0.43 1.29 0.8 1 1.6 1.8 30 18.1 0.0128 1530
25 1.5 7/0.52 1.56 0.8 1 1.6 1.8 32 12.1 0.0112 1760
25 2.5 7/0.67 2.01 0.8 1 1.6 1.9 35 7.41 0.0093 2200
25 4 7/0.85 2.55 1 1.2 2 2.1 43 4.61 0.0092 3400
25 6 7/1.04 3.12 1 1.2 2 2.2 46.5 3.08 0.0078 4220
26 0.5 7/0.30 0.9 0.8 1 1.6 1.8 28 36 0.0162 1260
26 0.75 7/0.37 1.11 0.8 1 1.6 1.8 29 24.5 0.0142 1400
26 1 7/0.43 1.29 0.8 1 1.6 1.8 30 18.1 0.0128 1540
26 1.5 7/0.52 1.56 0.8 1 1.6 1.8 32 12.1 0.0112 1780
26 2.5 7/0.67 2.01 0.8 1 1.6 1.9 35 7.41 0.0093 2220
26 4 7/0.85 2.55 1 1.2 2 2.1 43 4.61 0.0092 3440
26 6 7/1.04 3.12 1 1.2 2 2.2 46.5 3.08 0.0078 4270
27 0.5 7/0.30 0.9 0.8 1 1.6 1.8 28 36 0.0162 1270
27 0.75 7/0.37 1.11 0.8 1 1.6 1.8 29 24.5 0.0142 1410
27 1 7/0.43 1.29 0.8 1 1.6 1.8 30 18.1 0.0128 1550
27 1.5 7/0.52 1.56 0.8 1 1.6 1.8 32 12.1 0.0112 1790
27 2.5 7/0.67 2.01 0.8 1 1.6 1.9 35 7.41 0.0093 2240
27 4 7/0.85 2.55 1 1.2 2 2.1 43 4.61 0.0092 3470
27 6 7/1.04 3.12 1 1.2 2 2.2 46.5 3.08 0.0078 4320
28 0.5 7/0.30 0.9 0.8 1 1.6 1.8 28.5 36 0.0162 1310
28 0.75 7/0.37 1.11 0.8 1 1.6 1.8 30 24.5 0.0142 1480
28 1 7/0.43 1.29 0.8 1 1.6 1.8 31 18.1 0.0128 1630
28 1.5 7/0.52 1.56 0.8 1 1.6 1.8 33 12.1 0.0112 1880
28 2.5 7/0.67 2.01 0.8 1 1.6 1.9 36 7.41 0.0093 2350
28 4 7/0.85 2.55 1 1.2 2 2.2 44.5 4.61 0.0092 3670
28 6 7/1.04 3.12 1 1.2 2 2.3 48 3.08 0.0078 4550
29 0.5 7/0.30 0.9 0.8 1 1.6 1.8 28.5 36 0.0162 1320
29 0.75 7/0.37 1.11 0.8 1 1.6 1.8 30 24.5 0.0142 1490
29 1 7/0.43 1.29 0.8 1 1.6 1.8 31 18.1 0.0128 1640
29 1.5 7/0.52 1.56 0.8 1 1.6 1.9 33 12.1 0.0112 1900
29 2.5 7/0.67 2.01 0.8 1 1.6 1.9 36 7.41 0.0093 2370
29 4 7/0.85 2.55 1 1.2 2 2.2 44.5 4.61 0.0092 3700
29 6 7/1.04 3.12 1 1.2 2 2.3 48 3.08 0.0078 4600
30 0.5 7/0.30 0.9 0.8 1 1.6 1.8 28.5 36 0.0162 1330
30 0.75 7/0.37 1.11 0.8 1 1.6 1.8 30 24.5 0.0142 1500
30 1 7/0.43 1.29 0.8 1 1.6 1.8 31 18.1 0.0128 1650
30 1.5 7/0.52 1.56 0.8 1 1.6 1.9 33 12.1 0.0112 1910
30 2.5 7/0.67 2.01 0.8 1 1.6 1.9 36 7.41 0.0093 2400
30 4 7/0.85 2.55 1 1.2 2 2.2 44.5 4.61 0.0092 3740
30 6 7/1.04 3.12 1 1.2 2 2.3 48 3.08 0.0078 4660

Request the Complete Data Sheet

If you need a specific product catalogue or related standard file, please contact us.

From Production to Delivery

From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.

cable production line with finished cable being wound onto a reel

Production

Stranded annealed copper conductors are PVC insulated, cabled into the required multicore assembly, optionally filled and bound, covered with a black PVC inner sheath, armoured with galvanized steel wires, wrapped with separator tape and finished with the black PVC outer sheath.

Cable and conductor quality inspection and testing

Inspection

Inspection focuses on conductor size and resistance, PVC insulation and sheath condition, armour-wire diameter and continuity of the armour layer, overall dimensions, insulation resistance and test-voltage requirements.

Overhead conductors packed on wooden drums for shipment

Packaging

Finished cables are wound on suitable drums according to cable diameter, weight and ordered length. Drum identification can include cable type, conductor size, core count, length and project reference.

Wooden drums of overhead conductors loaded into shipping container

Shipping

Before shipment, drums and technical documents are checked against the order. Inspection records, product identification and requested test documents can be prepared for project approval.

Frequently Asked Questions

When should I choose CVV-SWA instead of standard CVV control cable?

Choose CVV-SWA when the route requires additional mechanical protection, especially for direct burial, duct installations or industrial locations where the cable may be exposed to external stress. The galvanized steel-wire armour adds physical protection that an unarmoured CVV cable does not provide. If the installation is fully protected and armour is unnecessary, standard CVV may be simpler and more economical.

No. The steel-wire armour is primarily a mechanical-protection layer, not a dedicated electrostatic screen. If the control circuit is sensitive to interference, the project should separately confirm whether a copper-tape or copper-braid screened cable is required.

Yes. Direct burial is explicitly listed as an intended application. The complete installation still needs suitable trench design, cable depth, mechanical protection where required, joints, glands and terminations consistent with the project specification and local installation rules.

Start with the number of control functions and spare-core requirement, then select conductor cross section according to circuit length, resistance and load. After the electrical selection, check overall diameter, cable weight, tray or duct capacity and termination space because the SWA construction can become relatively heavy at high core counts.

Yes. The product information states that a special flame-retardant outer sheath can be supplied. If the project specifies a particular flame test or fire-performance level, include that standard in the RFQ so the offered sheath construction and supporting documents can be confirmed.

We provide a wide range of cable materials and electrical products, including aluminum conductors, aluminum rods, aluminum wires, overhead conductors, medium and low voltage power cables, cable insulation materials, filling materials, shielding materials, and cable manufacturing consumables.We provide customized solutions according to different cable manufacturing requirements.

Request for Free Consultation

Contact Information

Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.

Explore More

Related Products
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Compatible Hardware
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Knowledge Articles
Customer Visits Our Factory for Product Inspection and Quality Verification
AAAC all aluminium alloy conductor stranded wire
AAAC Conductor Selection Guide: How to Choose the Right AAAC for Overhead Lines
International Airport Expansion Project in Saudi Arabia

For Immediate Assistance, Please Contact us Now!