ICEA S-73-532 THHN/THWN-2 Screened Control Cable 600V

ICEA S-73-532 referenced THHN/THWN-2 Screened Control Cable is a 600V, 90°C multiconductor control cable using bare annealed copper conductors, PVC-FR/nylon insulation, an aluminum-tape overall screen, a tinned-copper drain wire and a special PVC outer sheath. This page focuses on the control- and instrumentation-cable construction, identification and shielding aspects associated with the ICEA/NEMA standard framework.

PRODUCT OVERVIEW

The cable combines color-identified THHN/THWN-2 insulated conductors with an overall aluminum-tape screen and dedicated tinned-copper drain wire. The source product specification explicitly states that core identification is color coded as E2 per ICEA S-73-532, making conductor identification a particularly relevant part of this standard-focused page.

ANSI/NEMA WC 57 / ICEA S-73-532 is a control, thermocouple-extension and instrumentation cable standard covering key areas such as conductors, insulation systems, shielding and coverings. For this product, the most relevant features are the copper conductors, PVC/nylon insulation system, E2 core identification, aluminum-tape screen, drain wire and finished multicore jacketed construction.

KEY FEATURES

  • ICEA S-73-532 referenced control-cable construction.
  • E2 core identification per ICEA S-73-532 stated in the source data.
  • 600V voltage rating and +90°C temperature rating.
  • Bare annealed copper conductors.
  • PVC-FR / nylon insulated conductors.
  • Aluminum-tape overall screen.
  • Tinned-copper 16 AWG 7-strand drain wire.
  • Special black PVC outer sheath.
  • 2 to 50 core range with 10, 12 and 14 AWG options depending on core count.

CABLE CONSTRUCTION

Conductor

Bare annealed copper

Insulation

PVC-FR / Nylon (flame-retardant PVC with nylon covering)

Screen

Aluminum tape

Drain Wire

Tinned copper, 16 AWG, 7-strand

Ripcord

Nylon

Outer Sheath

Special PVC

Sheath Colour

Black

Core Identification

Color coded as E2 per ICEA S-73-532

E2 CORE IDENTIFICATION

The source specification states that the cable cores are color coded as E2 per ICEA S-73-532. For project submittals, the required identification method should be confirmed together with the core count, AWG size and any customer-specific numbering or color schedule.

ICEA S-73-532 RELATED DESIGN FEATURES

Design Feature

Product Relevance

Control-Cable Function

Multiconductor control cable for industrial control circuits

Copper Conductors

Bare annealed copper conductors; ASTM B3/B8 listed as related material/conductor references

PVC/Nylon Insulation

THHN/THWN-2 style PVC-FR / nylon insulation system

Core Identification

E2 color coding specifically stated per ICEA S-73-532

Metal Tape Shield

Aluminum-tape overall screen around the multicore assembly

Drain Wire

Tinned-copper 16 AWG 7-strand drain wire

Outer Covering

Special black PVC outer sheath

Electrical Selection Data

Nominal ampacity, dimensions and product rating provided by the product schedule

STANDARD REFERENCE & COMPLIANCE

Item

Details

Referenced Standard

ICEA S-73-532

Current Joint Designation

ANSI/NEMA WC 57 / ICEA S-73-532-2021

ANSI Approval Date

December 6, 2021

Product Rating

600V screened control cable

Compliance Note

The product specification references ICEA S-73-532 and states E2 core identification. For edition-specific or full-standard compliance, confirm the required construction and test documentation during technical review.

The current ICEA/NEMA document is ANSI/NEMA WC 57 / ICEA S-73-532-2021, Standard for Control, Thermocouple Extension, and Instrumentation Cables. The standard is still listed by ICEA under its Control and Instrumentation documents.

WHY ICEA S-73-532 MATTERS FOR THIS PRODUCT

The ICEA page should not duplicate the UL 1277 page. Its technical emphasis is the control-cable design itself: conductor construction, insulation, identification, metallic shielding and coverings. That makes it useful for engineers and buyers comparing screened control-cable designs rather than only checking tray installation eligibility.

PRODUCT APPLICATIONS

  • Multiconductor industrial control circuits.
  • Supervisory and process-control wiring where an overall screen is required.
  • Oil, gas and petrochemical control systems where the project specification calls for this cable construction.
  • Screened control routes in tray, wireway, duct or conduit.
  • Wet or dry industrial locations as stated in the source data.
  • Outdoor tray installations where the specified cable marking and sunlight-resistant requirement are satisfied.

The following dimensions and ampacity values are reproduced from the source product data for the listed 600V screened cable constructions.

Cores AWG PVC Insul. mm Nylon mm Sheath mm Overall Dia. mm Weight kg/km Nominal Ampacity A
2 10 0.51 0.10 1.14 10.87 189 40
2 12 0.38 0.10 1.14 9.35 132 30.0
3 10 0.51 0.10 1.14 11.52 251 40
3 12 0.38 0.10 1.14 9.87 174 30.0
3 14 0.38 0.10 1.14 8.67 129 25.0
4 10 0.51 0.10 1.14 12.61 290 32/40
4 12 0.38 0.10 1.14 10.74 219 24.0/30.0
4 14 0.38 0.10 1.14 9.42 159 20.0/25.0
5 10 0.51 0.10 1.52 14.57 414 32
5 12 0.38 0.10 1.14 11.69 272 24.0
5 14 0.38 0.10 1.14 10.24 190 20.0
6 10 0.51 0.10 1.52 15.82 479 32
6 12 0.38 0.10 1.14 12.70 310 24.0
6 14 0.38 0.10 1.14 11.10 220 20.0
7 10 0.51 0.10 1.52 15.82 540 28
7 12 0.38 0.10 1.14 12.70 338 21.0
7 14 0.38 0.10 1.14 11.10 243 17.5
8 10 0.51 0.10 1.52 17.35 609 28
8 12 0.38 0.10 1.52 14.53 394 21.0
8 14 0.38 0.10 1.14 12.14 277 17.5
9 10 0.51 0.10 1.52 18.69 679 28
9 12 0.38 0.10 1.52 15.60 470 21.0
9 14 0.38 0.10 1.52 13.06 307 17.5
10 10 0.51 0.10 1.52 19.95 748 20
10 12 0.38 0.10 1.52 16.61 513 21.0
10 14 0.38 0.10 1.52 14.68 362 12.5
11 10 0.51 0.10 1.52 20.24 811 20
11 12 0.38 0.10 1.52 16.84 549 15.0
11 14 0.38 0.10 1.52 14.68 388 12.5
12 10 0.51 0.10 2.03 21.89 930 20
12 12 0.38 0.10 1.52 17.34 595 15.0
12 14 0.38 0.10 1.52 15.31 421 12.5
13 10 0.51 0.10 2.03 22.27 984 20
13 12 0.38 0.10 1.52 17.64 634 15.0
13 14 0.38 0.10 1.52 15.57 443 12.5
14 10 0.51 0.10 2.03 22.98 1116 20
14 12 0.38 0.10 1.52 18.21 677 15.0
14 14 0.38 0.10 1.52 16.06 473 12.5
15 10 0.51 0.10 2.03 23.56 1173 20
15 12 0.38 0.10 1.52 18.68 717 15.0
15 14 0.38 0.10 1.52 16.46 501 12.5
16 10 0.51 0.10 2.03 24.19 1262 20
16 12 0.38 0.10 1.52 19.19 747 15.0
16 14 0.38 0.10 1.52 16.89 533 12.5
19 10 0.51 0.10 2.03 25.45 1376 20
19 12 0.38 0.10 1.52 20.19 870 15.0
19 14 0.38 0.10 1.52 17.75 615 12.5
20 10 0.51 0.10 2.03 26.21 1443 20
20 12 0.38 0.10 1.52 20.80 933 15.0
20 14 0.38 0.10 1.52 18.27 643 12.5
25 10 0.51 0.10 2.03 29.35 1771 18
25 12 0.38 0.10 2.03 24.33 1176 13.5
25 14 0.38 0.10 1.52 20.42 787 11.3
30 10 0.51 0.10 2.03 31.36 2098 18
30 12 0.38 0.10 2.03 25.94 1379 13.5
30 14 0.38 0.10 2.03 22.82 972 11.3
37 10 0.51 0.10 2.03 33.83 2544 16
37 12 0.38 0.10 2.03 27.91 1665 12.0
37 14 0.38 0.10 2.03 24.51 1174 10.0
40 10 0.51 0.10 2.03 35.13 2738 16
40 12 0.38 0.10 2.03 28.95 1827 12.0
40 14 0.38 0.10 2.03 25.40 1262 10.0
45 10 0.51 0.10 2.03 37.23 3056 14
45 12 0.38 0.10 2.03 30.63 2039 10.5
45 14 0.38 0.10 2.03 26.84 1403 8.8
50 10 0.51 0.10 2.03 38.65 3378 14
50 12 0.38 0.10 2.03 31.77 2245 10.5
50 14 0.38 0.10 2.03 27.81 1537 8.8

Request the Complete Data Sheet

If you need a specific product catalogue or related standard file, please contact us.

From Production to Delivery

From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.

cable production line with finished cable being wound onto a reel

Production

Bare annealed copper conductors are insulated with the PVC-FR / nylon system, assembled into the required multicore construction, screened with aluminum tape together with the tinned-copper drain wire, and protected by the special PVC outer sheath.

Cable and conductor quality inspection and testing

Inspection

Inspection focuses on conductor construction, PVC/nylon insulation, E2 core identification, aluminum-tape screen condition and continuity, drain-wire construction, outer-jacket integrity, dimensions and the project-required electrical and cable-performance checks.

Overhead conductors packed on wooden drums for shipment

Packaging

Finished cable is wound on suitable drums according to ordered size, weight and length. Cable ends are protected and drum identification can include the standard reference, conductor size, core count, voltage rating, length and project reference.

Wooden drums of overhead conductors loaded into shipping container

Shipping

Before shipment, cable drums and technical documents are checked against the order. Requested inspection records, technical data, certificates and project submittal documents can be prepared for review.

Frequently Asked Questions

What is the purpose of the aluminum-tape screen and drain wire?

The aluminum tape forms an overall electrostatic screen around the cable core, and the tinned-copper drain wire provides a convenient electrical path for terminating that screen. The actual grounding arrangement should follow the project EMC philosophy and connected equipment requirements.

We provide a wide range of cable materials and electrical products, including aluminum conductors, aluminum rods, aluminum wires, overhead conductors, medium and low voltage power cables, cable insulation materials, filling materials, shielding materials, and cable manufacturing consumables.We provide customized solutions according to different cable manufacturing requirements.

Choose the core count from the control schematic and include spare cores where required. Then size the 10, 12 or 14 AWG conductors using load, circuit length, voltage drop and project ampacity rules, and check the resulting overall cable diameter against the planned tray or conduit.

Those applications are stated in the source product data and are more directly associated with the UL 1277 product angle. If the project is being approved primarily against ICEA S-73-532, installation eligibility should still be checked against the applicable listing, code and cable markings.

Provide core count, AWG size, length, installation environment, required E2 identification, screen grounding requirement and any flame or hazardous-location requirements. Also state whether the customer expects UL 1277 listing documentation, ICEA/NEMA edition-specific compliance documents, or both.

Request for Free Consultation

Contact Information

Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.

Explore More

Related Products
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Compatible Hardware
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Knowledge Articles
Customer Visits Our Factory for Product Inspection and Quality Verification
AAAC all aluminium alloy conductor stranded wire
AAAC Conductor Selection Guide: How to Choose the Right AAAC for Overhead Lines
International Airport Expansion Project in Saudi Arabia

For Immediate Assistance, Please Contact us Now!