Three Core Medium Voltage Cable to BS 6622/BS 7835

This three core medium voltage cable provides a complete three-phase power distribution solution for voltages from 3.6/6.6kV up to 19/33kV at 50Hz, built to BS 6622 and BS 7835 (LSZH Version) for enhanced fire safety in public and industrial environments. Featuring XLPE GP8 or EPR GP7 insulation to BS 7655 and a 0.3mm minimum extruded semi-conducting conductor screen, it is suitable for installation in power supply stations, indoor cable ducts, outdoor trays, underground routes, submerged applications and industrial switchboards.
Key Advantages‌
LSZH Low Smoke Zero Halogen Sheath
XLPE/EPR Insulation
Copper or Aluminium Conductor Options
BS 6622 & BS 7835 British Standard

Construction

Conductor‌Plain annealed copper or aluminium complying with IEC 60228/BS 6360. Copper conductors shall be stranded (class 2) and aluminium conductors shall be either solid or stranded (class 2).
‌Insulation‌Insulation is of cross-linked polyethylene compound XLPE (GP8) conforming to BS 7655-1.3 or EPR (GP7), conforming to BS 7655-1.2.
‌Conductor Screen‌Extruded layer of semi-conducting cross-linkable compound is applied over the conductor and shall cover the surface completely. The minimum thickness is 0.3mm and the maximum resistivity shall not exceed 500 Ohm-m at 90°C.
‌Insulation Screen‌Extruded layer of semi-conducting cross-linkable compound is applied over the insulation. The extruded semi-conducting layer shall consist of bonded or cold strippable semi-conducting compound capable of removal for jointing or terminating. As an option, a semi-conducting tape may be applied over the extruded semi-conducting layer as a bedding for the metallic layer. The minimum thickness is 0.3 mm and the maximum resistivity is 500 Ohm-m at 90°C. The screen is tightly fitted to the insulation to exclude all air voids and can be easily hand stripped on site.
‌Inner Covering & Fillers‌For cables with a collective metallic layer or cables with a metallic layer over each individual cores with additional collective metallic layers, semi-conducting inner covering and fillers shall be applied over the laid up cores. The inner covering is made of non hygroscopic material, except if the cable is to be made longitudinally watertight. The inner covering shall be extruded or lapped.
‌Metallic Layer‌The metallic layer shall be applied over each core or applied as a collective screen. The metallic screen shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires. The metallic layer provides an earth fault current path, capable of withstanding fault current to earth of 1000A for one second at maximum temperature 160°C. Copper wires are applied over the conducting water blocking layer with a minimum diameter of 0.5mm. And over the copper wires, copper tape with minimum thickness of 0.1mm can be applied helically with overlap.
‌Separation Sheath (for armored cable)‌The separation sheath comprises a layer of extruded PVC, PE or LSZH. The nominal thickness is calculated by 0.02Du + 0.6mm where Du is the fictitious diameter under the sheath in mm. The nominal separation sheath thickness shall not be less than 1.2mm.
‌Armour (for armored cable)‌The armour consists of galvanized steel wire applied over the inner covering with diameter specified as in Table 4.
‌Over Sheath‌Overall sheath comprises a layer of extruded either PVC type 9 conforming to BS 7665-4.2 or MDPE type TS2 conforming to BS 7655-10.1. LSZH can be offered as an option. The over sheath is normally black in colour. When a DC voltage test is to be performed on the over sheath, a semi-conducting layer such as graphite coating shall be applied over the surface of the extruded over sheath. The nominal over sheath thickness is calculated by 0.035+D where D is the diameter immediately under the over sheath in mm. For cables with the over sheath not applied over the armour, the nominal over sheath thickness shall not be less than 1.4mm. And for cables with over sheath applied over the armour, the nominal over sheath thickness shall not be less than 1.8mm.
‌Physical Properties‌Operating Temperature: up to 90°C  Temperature Range: -5°C (PVC or LSZH sheath); -20°C (PE sheath)  Short Circuit Temperature: 250°C (short circuit duration up to 5 seconds) Bending Radius: 15 × OD

Parameters

Nom. Cross-Section Area Unarmoured Cables Steel Wire Armoured Cables
Nom. Insulation Thickness Copper Wire Screen Area Nom. Sheath Thickness Approx. Overall Diameter Approx. Weight Copper Tape Screen Area Nom. Bedding Thickness Nom. Armour Wire Diameter Nom. Sheath Thickness Approx. Overall Diameter Approx. Weight
CU AL CU AL
mm² mm mm² mm mm kg/km mm² mm mm mm mm kg/km
25 2.5 16 2.1 37.7 2205 1740 3.4 1.2 2.0 2.2 44.5 3890 3465
35 2.5 16 2.3 41.2 2690 2010 3.6 1.2 2.5 2.3 46.8 4420 3730
50 2.5 16 2.5 44.9 3340 2350 3.8 1.3 2.5 2.5 51.5 5640 4690
70 2.5 16 2.6 48.0 4050 2730 4.3 1.3 2.5 2.6 55.0 6570 5240
95 2.5 16 2.7 51.7 5000 3180 4.7 1.4 2.5 2.7 58.9 7760 5890
120 2.5 16 2.8 54.7 5890 3590 5.0 1.5 2.5 2.8 62.1 8810 6510
150 2.5 25 2.9 58.4 6960 4160 5.3 1.5 2.5 2.9 65.8 10110 7310
185 2.5 25 3.0 61.9 8160 4650 5.8 1.6 2.5 3.0 69.5 11520 7960
240 2.6 25 3.2 68.1 10210 5530 6.3 1.7 2.5 3.2 75.9 13920 9140
300 2.8 25 3.5 73.6 12380 6670 7.0 1.8 3.15 3.5 83.1 17400 11620
400 3.0 35 3.7 83.8 16190 8430 7.7 2.0 3.15 3.7 93.0 21900 13980
Nom. Cross-Section Area Unarmoured Cables Steel Wire Armoured Cables
Nom. Insulation Thickness Copper Wire Screen Area Nom. Sheath Thickness Approx. Overall Diameter Approx. Weight Copper Tape Screen Area Nom. Bedding Thickness Nom. Armour Wire Diameter Nom. Sheath Thickness Approx. Overall Diameter Approx. Weight
CU AL CU AL
mm² mm mm² mm mm kg/km mm² mm mm mm mm kg/km
25 3.4 16 2.3 42.8 2600 2120 3.8 1.3 2.5 2.4 50.0 4930 4400
35 3.4 16 2.3 45.3 3000 2320 4.1 1.3 2.5 2.5 52.3 5380 4700
50 3.4 16 2.4 48.5 3630 2690 4.4 1.4 2.5 2.6 55.7 6210 5260
70 3.4 16 2.5 52.0 4440 3110 4.7 1.4 2.5 2.7 59.2 7200 5870
95 3.4 16 2.7 56.0 5440 3620 5.2 1.5 2.5 2.8 63.2 8420 6550
120 3.4 16 2.8 59.4 6370 4020 5.5 1.6 2.5 3.0 67.0 9580 7190
150 3.4 25 2.9 62.7 7430 4630 5.8 1.6 2.5 3.1 70.3 10830 8030
185 3.4 25 3.0 66.1 8680 5150 6.2 1.7 2.5 3.2 73.9 12290 8720
240 3.4 25 3.1 71.7 10690 5990 6.8 1.8 3.15 3.4 81.2 15620 10790
300 3.4 25 3.3 76.4 12770 7050 7.3 1.9 3.15 3.6 86.1 18030 12240
400 3.4 35 3.5 85.1 16460 8680 8.0 2.0 3.15 3.8 95.0 22350 14350
Nom.
Cross-Section Area
Unarmoured Cables Steel Wire Armoured Cables
Nom.
Insulation Thickness
Copper
Wire Screen
Area
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Approx. Weight Copper
Tape Screen
Area
Nom.
Bedding
Thickness
Nom.
Armour Wire
Diameter
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Approx. Weight
CU AL CU AL
mm² mm mm² mm mm kg/km mm² mm mm mm mm kg/km
25 4.5 16 2.4 48.4 3000 2420 4.4 1.4 2.5 2.6 55.2 5600 5100
35 4.5 16 2.5 50.4 3450 2670 4.7 1.4 2.5 2.7 57.6 6130 5440
50 4.5 16 2.6 53.7 4140 3190 4.9 1.5 2.5 2.8 61.1 7010 6060
70 4.5 16 2.7 57.2 4980 3640 5.3 1.5 2.5 2.9 64.6 8030 6700
95 4.5 16 2.8 60.6 5900 4050 5.7 1.6 2.5 3.0 68.2 9160 7330
120 4.5 16 2.9 63.9 6870 4560 6.1 1.7 2.5 3.1 71.7 10340 8030
150 4.5 25 3.0 67.9 8030 5230 6.4 1.7 2.5 3.2 75.4 11730 8930
185 4.5 25 3.1 71.1 9310 5770 6.8 1.8 3.15 3.4 80.6 14170 10570
240 4.5 25 3.3 76.9 11390 6680 7.4 1.9 3.15 3.6 86.6 16670 11810
300 4.5 25 3.5 81.6 13510 7790 7.9 2.0 3.15 3.7 91.3 19140 13340
400 4.5 35 3.7 89.9 17130 9340 8.5 2.1 3.15 4.0 100.0 23360 15410
Nom.
Cross-Section
Area
Unarmoured Cables Steel Wire Armoured Cables
Nom.
Insulation
Thickness
Copper
Wire Screen
Area
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Approx.
Weight
Copper
Tape Screen
Area
Nom.
Bedding
Thickness
Nom.
Armour Wire
Diameter
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Approx.
Weight
CU AL CU AL
mm² mm mm² mm mm kg/km mm² mm mm mm mm kg/km
35 5.5 16 2.7 51 3750 2880 5.2 1.5 2.5 2.8 62.3 6870 6140
50 5.5 16 2.8 54 4240 3250 5.4 1.5 2.5 2.9 65.6 7710 6810
70 5.5 16 2.9 58 5050 3650 5.9 1.6 2.5 3.0 69.0 8710 7370
95 5.5 16 3.0 62 6010 4110 6.2 1.7 2.5 3.2 73.1 10000 8130
120 5.5 16 3.1 65 6990 4660 6.6 1.7 3.15 3.3 77.7 12040 9730
150 5.5 25 3.2 68 8130 5330 6.9 1.8 3.15 3.4 81.7 13550 10750
185 5.5 25 3.3 72 9410 5870 7.4 1.9 3.15 3.6 85.5 15150 11610
240 5.5 25 3.5 79 11490 6880 7.8 2.0 3.15 3.7 91.3 17710 12840
300 5.5 25 3.7 84 13710 7890 8.2 2.0 3.15 3.9 96.0 20170 14360
400 5.5 35 3.9 91 17230 9440 9.0 2.2 3.15 4.1 104.8 24520 16480
Nom.
Cross-Section
Area
Unarmoured Cables Steel Wire Armoured Cables
Nom.
Insulation
Thickness
Copper
Wire Screen
Area
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Approx.
Weight
Copper
Tape Screen
Area
Nom.
Bedding
Thickness
Nom.
Armour Wire
Diameter
Nom.
Sheath
Thickness
Approx.
Overall
Diameter
Approx.
Weight
CU AL CU AL
mm² mm mm² mm mm kg/km mm² mm mm mm mm kg/km
35 5.5 16 2.7 51 3750 2880 5.2 1.5 2.5 2.8 62.3 6870 6140
50 5.5 16 2.8 54 4240 3250 5.4 1.5 2.5 2.9 65.6 7710 6810
70 5.5 16 2.9 58 5050 3650 5.9 1.6 2.5 3.0 69.0 8710 7370
95 5.5 16 3.0 62 6010 4110 6.2 1.7 2.5 3.2 73.1 10000 8130
120 5.5 16 3.1 65 6990 4660 6.6 1.7 3.15 3.3 77.7 12040 9730
150 5.5 25 3.2 68 8130 5330 6.9 1.8 3.15 3.4 81.7 13550 10750
185 5.5 25 3.3 72 9410 5870 7.4 1.9 3.15 3.6 85.5 15150 11610
240 5.5 25 3.5 79 11490 6880 7.8 2.0 3.15 3.7 91.3 17710 12840
300 5.5 25 3.7 84 13710 7890 8.2 2.0 3.15 3.9 96.0 20170 14360
400 5.5 35 3.9 91 17230 9440 9.0 2.2 3.15 4.1 104.8 24520 16480

Request the Complete Data Sheet

If you need a specific product catalogue or related standard file, please contact us.

Application

They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as forinstallation on cable trays for industries, switchboards and power stations

From Production to Delivery

From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.

cable production line with finished cable being wound onto a reel

Production

Stranded annealed copper conductors are insulated with XLPE, assembled into the required multicore configuration, optionally filled and bound with polyester tape, then covered with the specified black PVC sheath.

Cable and conductor quality inspection and testing

Inspection

Inspection focuses on conductor construction, insulation condition, core identification, sheath integrity, overall diameter, conductor resistance and test-voltage requirements against the approved technical schedule.

Overhead conductors packed on wooden drums for shipment

Packaging

Finished cable is wound on suitable drums according to ordered size, weight and length. Cable ends are protected and drum identification can include cable type, conductor size, core count, length and project reference.

Wooden drums of overhead conductors loaded into shipping container

Shipping

Before shipment, cable drums and technical documents are checked against the order. Inspection records, identification data and requested test documentation can be prepared for the customer.

faq

What is the voltage range of these three core medium voltage cables?‌

These three core cables are designed for distribution of electrical power with a nominal voltage Uo/U ranging from ‌3.8/6.6KV to 19/33KV, at a frequency of 50Hz.

Three insulation types are offered:
‌PVC (Polyvinyl Chloride)‌ — for 1.8/3kV and 3.6/6kV cables, a cost-effective and reliable option
‌XLPE (Cross-Linked Polyethylene)‌ — high temperature rating (90°C), superior electrical performance and current-carrying capacity
‌EPR/HEPR (Ethylene Propylene Rubber)‌ — excellent flexibility, cold resistance, and mechanical resilience

The outer sheath is available in PVC, PE (Polyethylene), or LSZH (Low Smoke Zero Halogen) materials. LSZH is recommended for enclosed spaces and public areas due to its low smoke emission and zero halogen content in case of fire.

Single core cables are typically preferred for:
High-current circuits where individual phase installation is required
Single-phase systems
Applications requiring easier cable pulling and installation
Circuits where individual phase replacement or maintenance may be needed
Large conductor sizes where three-core construction becomes impractical

Yes, we offer extensive customization options to meet specific project requirements including:

  • Special core configurations (e.g., 3+1E, 3+2E, 4+1E, custom multi-core)
  • Custom outer sheath colors (red, blue, grey, etc. for identification)
  • Special print marking with customer logo, project name, or custom text
  • Low smoke zero halogen (LSZH) versions for special fire safety requirements
  • UV-stabilized formulations for extreme outdoor exposure
  • Oil-resistant and chemical-resistant sheath compounds
  • Custom length drums and packaging

Custom orders typically require MOQ and may have slightly longer lead times. Contact our sales team with your specific requirements for a quote.

Typical production lead times:

  • Standard specifications (common sizes): 7-15 working days after order confirmation
  • Custom specifications or special requirements: 15-25 working days
  • Large volume orders: production schedule confirmed at time of order

We also maintain inventory of fast-moving standard sizes for immediate shipment. Transit time depends on destination port and shipping method. We can ship by sea (most cost-effective for large orders), air (urgent shipments), or rail (for Central Asian destinations).

Request for Free Consultation

Contact Information

Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.

Explore More

Related Products
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Compatible Hardware
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Knowledge Articles
Customer Visits Our Factory for Product Inspection and Quality Verification
AAAC all aluminium alloy conductor stranded wire
AAAC Conductor Selection Guide: How to Choose the Right AAAC for Overhead Lines
International Airport Expansion Project in Saudi Arabia

For Immediate Assistance, Please Contact us Now!