ICEA S-73-532 XHHW-2 Unscreened Control Cable 600V

ICEA S-73-532 referenced XHHW-2 Unscreened Control Cable is a 600V multicore control cable using bare annealed copper conductors, flame-retardant XLPE insulation and a black special-PVC outer sheath. This page focuses on the cable as a multiconductor control-cable construction rather than on only the XHHW-2 insulation designation or tray installation category.

PRODUCT OVERVIEW

The product is built around XLPE-insulated copper conductors assembled into an unscreened multicore cable with an overall special-PVC sheath. The source data lists 10 AWG and 12 AWG versions with scheduled core counts extending to 50 cores, making the product suitable for control systems that need many circuits within one overall cable.

For the ICEA S-73-532 / NEMA WC 57 landing page, the most relevant technical themes are multiconductor control-cable construction, materials, testing and engineering selection. The source brochure does not state a specific core-identification method, so core colours or numbering should be confirmed to the project requirement rather than inferred.

KEY FEATURES

  • Reference standard: ANSI/NEMA WC 57 / ICEA S-73-532.
  • Current published edition: 2021.
  • 600V and +90°C ratings stated in the product data.
  • Bare annealed copper conductors.
  • Flame-retardant XLPE insulation.
  • Unscreened multicore construction.
  • Black special-PVC outer sheath.
  • 10 AWG and 12 AWG listed sizes.
  • Scheduled constructions from 2 to 50 cores.

CABLE CONSTRUCTION

Conductor

Bare annealed copper

Insulation

Flame-retardant XLPE (Cross-Linked Polyethylene)

Binder Tape

Present in the listed construction; material not stated in the source data

Ripcord

Nylon

Metallic Screen

None

Outer Sheath

Special PVC (Polyvinyl Chloride), black

Core Identification

Not specified in the source product data; confirm project requirement

STANDARD REFERENCE & COMPLIANCE

Item

Details

Referenced Standard

ANSI/NEMA WC 57 / ICEA S-73-532

Current Published Edition

2021

Standard Focus

Materials, construction and testing of multiconductor control, thermocouple-extension and instrumentation cables

Product Position

600V XHHW-2 unscreened multicore control cable

Compliance Note

Confirm the required edition, tests, core identification and project documentation for the offered cable construction before formal approval.

The current public NEMA/ICEA documents identify ANSI/NEMA WC 57 / ICEA S-73-532-2021 as the published standard for control, thermocouple-extension and instrumentation cables. For this product, the page should focus on the control-cable material and construction framework rather than implying that every possible ICEA control/instrumentation configuration is represented.

ICEA S-73-532 / NEMA WC 57 DESIGN FOCUS

Focus

How It Relates to This Product

Multiconductor Control Cable

The product is offered as a multicore control-cable family

Conductor Material

Bare annealed copper

Insulation System

Flame-retardant XLPE around each conductor

Overall Covering

Black special-PVC sheath

Screening

This construction is unscreened; no metallic screen is listed

Engineering Data

Dimensions, weight and nominal ampacity are scheduled by AWG size and core count

Core Identification

Not stated in the source product data; must be confirmed for the project

PRODUCT APPLICATIONS

  • Multicore industrial control circuits.
  • Oil-industry control and auxiliary circuits.
  • Control panels, field wiring and station/plant control systems.
  • Tray, wireway, duct and conduit routes as stated in the source product data.
  • Wet or dry installations.
  • Outdoor and direct-burial applications where the required product markings are confirmed.

The following table reproduces the listed XHHW-2 unscreened product schedule for 10 AWG and 12 AWG multicore constructions.

Cores AWG Insulation mm Sheath mm Overall Dia. mm Weight kg/km Nominal Ampacity A
2 10 0.76 1.14 11.94 190 40.0
3 10 0.76 1.14 12.57 259 40.0
4 10 0.76 1.14 13.84 332 32/40
5 10 0.76 1.52 16.00 432 32.0
6 10 0.76 1.52 17.40 507 32.0
7 10 0.76 1.52 17.40 568 28.0
8 10 0.76 1.52 18.80 607 28.0
9 10 0.76 1.52 20.32 713 28.0
10 10 0.76 1.52 21.72 752 20.0
11 10 0.76 2.03 23.11 865 20.0
12 10 0.76 2.03 23.75 932 20.0
13 10 0.76 2.03 24.13 997 20.0
14 10 0.76 2.03 24.89 1064 20.0
15 10 0.76 2.03 25.65 1131 20.0
20 10 0.76 2.03 28.58 1463 20.0
25 10 0.76 2.03 32.00 1799 18.0
30 10 0.76 2.03 34.16 2124 18.0
35 10 0.76 2.03 36.32 2447 16.0
40 10 0.76 2.03 38.35 2770 16.0
45 10 0.76 2.03 40.77 3098 14.0
50 10 0.76 2.03 42.29 3417 14.0
2 12 0.76 1.14 10.67 140 30.0
3 12 0.76 1.14 11.30 188 30.0
4 12 0.76 1.14 12.32 238 24.0/30.0
5 12 0.76 1.14 13.59 289 24.0
6 12 0.76 1.52 15.49 366 24.0
7 12 0.76 1.52 15.49 406 21.0
8 12 0.76 1.52 16.76 432 21.0
9 12 0.76 1.52 18.03 507 21.0
10 12 0.76 1.52 19.18 530 15.0
11 12 0.76 1.52 19.56 573 15.0
12 12 0.76 1.52 20.19 619 15.0
13 12 0.76 1.52 20.57 662 15.0
14 12 0.76 1.52 21.21 708 15.0
15 12 0.76 1.52 21.84 753 15.0
19 12 0.76 1.52 24.26 975 15.0
20 12 0.76 1.52 25.27 1025 15.0
25 12 0.76 1.52 28.32 1260 13.5
30 12 0.76 1.52 30.23 1481 13.5
35 12 0.76 1.52 32.13 1700 12.0
37 12 0.76 1.52 32.13 1897 12.0
40 12 0.76 1.52 33.91 1918 12.0
45 12 0.76 1.52 35.81 2140 10.5
50 12 0.76 1.52 37.21 2354 10.5

Request the Complete Data Sheet

If you need a specific product catalogue or related standard file, please contact us.

From Production to Delivery

From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.

cable production line with finished cable being wound onto a reel

Production

Bare annealed copper conductors are insulated with flame-retardant XLPE, assembled into the required multicore construction, provided with the listed binder/ripcord arrangement and finished with the black special-PVC outer sheath.

Cable and conductor quality inspection and testing

Inspection

Inspection focuses on conductor condition, XLPE insulation thickness, sheath thickness, overall diameter, cable weight, electrical performance and consistency with the approved product schedule.

Overhead conductors packed on wooden drums for shipment

Packaging

Finished cable is wound on suitable reels or drums according to cable size, weight and ordered length. Product identification can include standard reference, AWG size, core count, length and project reference.

Wooden drums of overhead conductors loaded into shipping container

Shipping

Before shipment, cable identification, packing and requested technical documentation are checked against the order. Project-specific inspection or approval documents should be confirmed before production.

Frequently Asked Questions

What products do you supply for the power cable industry?

We provide a wide range of cable materials and electrical products, including aluminum conductors, aluminum rods, aluminum wires, overhead conductors, medium and low voltage power cables, cable insulation materials, filling materials, shielding materials, and cable manufacturing consumables.We provide customized solutions according to different cable manufacturing requirements.

No. The source brochure does not state a core-identification sequence or numbering system. For a project that requires a specific ICEA or customer identification scheme, confirm it before quotation and production.

Use the unscreened construction when the control system does not require an overall metallic screen. If the route is exposed to significant electrical interference or the specification calls for shielding, a screened control-cable design should be evaluated.

No. It is useful product data, but final sizing should also consider installation conditions, electrical-code rules, ambient temperature and any required derating. The project electrical design remains the final basis.

Specify the required edition, construction schedule, test reports, inspection documents and any customer-specific core identification or marking. If witnessed testing or approval submittals are required, include those requirements before order confirmation.

Provide AWG size, core count, cable length, installation environment, screened/unscreened requirement, core-identification requirement, reel length and the applicable ICEA/NEMA documentation package.

Request for Free Consultation

Contact Information

Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.

Explore More

Related Products
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Compatible Hardware
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Knowledge Articles
Customer Visits Our Factory for Product Inspection and Quality Verification
AAAC all aluminium alloy conductor stranded wire
AAAC Conductor Selection Guide: How to Choose the Right AAAC for Overhead Lines
International Airport Expansion Project in Saudi Arabia

For Immediate Assistance, Please Contact us Now!