UL 1277 XHHW/XLPO Type TC Control Cable 600V

UL 1277 XHHW/XLPO Type TC Control Cable is a 600V multicore industrial control cable with stranded bare annealed copper conductors, flame-retardant XLPE insulation and a low-smoke halogen-free polyethylene (XLPO) outer jacket. It is intended for Type TC control and power circuits where compact construction, flame performance and reduced smoke/halogen emissions are important.

PRODUCT OVERVIEW

The cable uses stranded bare annealed copper conductors insulated with flame-retardant and moisture-resistant cross-linked polyethylene (XLPE). The overall jacket is low-smoke halogen-free polyethylene (XLPO), with black preferred unless another colour is requested.

The product data identifies typical installations in cable trays, raceways and outdoor messenger-supported routes. It is also listed for direct burial, Class 1, Division 2 hazardous locations and Class 1 control circuits. Constructions with three or more conductors are stated as suitable for exposed runs (TC-ER) per NEC 336.10, and conductors may be used in wet or dry locations at temperatures up to 90°C.

KEY FEATURES

  • UL 1277 Type TC control / tray cable product basis.
  • 600V product rating.
  • Wet or dry location use up to 90°C as stated in the source data.
  • Stranded bare annealed copper conductors.
  • Flame-retardant and moisture-resistant XLPE insulation.
  • Low-smoke halogen-free polyethylene (XLPO) outer jacket.
  • Direct burial and Class 1, Division 2 applications stated in the source.
  • TC-ER exposed-run construction stated for 3 or more conductors.
  • AWG 14, 12 and 10 parameter schedules.

CABLE CONSTRUCTION

Conductor

Stranded bare annealed copper

Conductor Sizes

AWG 14, AWG 12 and AWG 10

Insulation

Flame-retardant and moisture-resistant Cross-Linked Polyethylene (XLPE)

Outer Jacket

Low-smoke halogen-free polyethylene (XLPO)

Jacket Colour

Upon request; black preferred

Voltage Rating

600V

Temperature

Wet or dry locations, not exceeding 90°C

Screen / Armour

None stated

STANDARD REFERENCE & COMPLIANCE

Item

Details

Referenced Standard

UL 1277 – Electrical Power and Control Tray Cables

Current Status

Active

Current Edition

Edition 6

Current Published Revision

May 29, 2025

Product Designation

XHHW/XLPO Type TC Control Cable, 600V

Compliance Note

Confirm the required UL listing/marking and specific ratings such as TC-ER, direct burial, wet location, outdoor use and hazardous-location use on the offered cable documentation.

UL 1277 is the main product standard for this cable family because it addresses the complete electrical power/control tray-cable assembly. The currently published standard remains Edition 6 with the latest formal revision dated May 29, 2025; later 2026 CSDS proposals should not be presented as an already-effective revision.

UL 1277 TYPE TC DESIGN FOCUS

UL 1277 Focus

How It Applies to This Cable

Complete Cable Assembly

Multicore XLPE-insulated conductors under an overall XLPO jacket

Cable Tray / Raceway Use

Primary installations include cable trays and raceways

Outdoor Installation

Outdoor messenger-supported locations are stated

Direct Burial

Listed in the source product application

Wet / Dry Locations

Both are stated up to 90°C

Hazardous Locations

Class 1, Division 2 use is stated; full installation requirements still apply

TC-ER

3 or more conductors are stated as listed for exposed runs

WHY XLPO JACKET?

The key differentiator of this product is the XLPO outer jacket. The source identifies it as a low-smoke halogen-free polyethylene jacket, making this construction suitable for projects that prefer reduced smoke and halogen emissions compared with conventional halogen-containing jacket systems.

The XLPO jacket should not be treated as automatically equivalent to every LSOH or low-smoke formulation on the market. Where a tender specifies particular smoke, halogen or flame-test limits, confirm the required test standards and supporting reports for the offered XLPO construction.

XHHW/XLPO VS XHHW/PVC VS XHHW/CPE

Feature

XHHW/XLPO

XHHW/PVC

XHHW/CPE

Insulated Conductors

XLPE

FRXLPE

FRXLPE

Outer Jacket

Low-smoke halogen-free polyethylene (XLPO)

Flame-retardant PVC

Flame-retardant CPE

Primary Procurement Difference

Low-smoke / halogen-free jacket requirement

PVC-jacketed Type TC requirement

CPE-jacketed Type TC requirement

Typical Page Intent

LSZH/XLPO Type TC cable

PVC Type TC cable

CPE Type TC cable

PRODUCT APPLICATIONS

  • Industrial power and control circuits where compact flame-retardant cable is required.
  • Cable trays and raceways.
  • Outdoor messenger-supported installations.
  • Direct-burial routes where the required cable marking is confirmed.
  • Wet or dry industrial locations up to 90°C.
  • Class 1, Division 2 hazardous-location projects as stated in the source.
  • TC-ER exposed-run applications for qualifying constructions with 3 or more conductors.
  • Projects that prefer a low-smoke halogen-free polyethylene jacket.

The following schedule reproduces the listed XHHW/XLPO Type TC cable dimensions and approximate weights for AWG 14, AWG 12 and AWG 10 constructions.

AWG Cores Jacket in Jacket mm OD in OD mm Weight lb/kft Weight kg/km
14 2 0.045 1.14 0.349 8.86 63 94
14 3 0.045 1.14 0.370 9.40 87 129
14 4 0.045 1.14 0.403 10.24 106 157
14 5 0.045 1.14 0.440 11.18 125 186
14 6 0.045 1.14 0.479 12.17 146 218
14 7 0.045 1.14 0.479 12.17 164 245
14 8 0.060 1.52 0.549 13.94 201 299
14 9 0.060 1.52 0.588 14.94 223 332
14 10 0.060 1.52 0.638 16.21 247 367
14 12 0.060 1.52 0.659 16.74 285 424
14 15 0.060 1.52 0.730 18.54 347 517
14 19 0.060 1.52 0.765 19.51 424 630
14 20 0.060 1.52 0.808 20.52 446 664
14 25 0.080 2.03 0.938 23.83 582 866
14 30 0.080 2.03 0.991 25.17 680 1012
14 37 0.080 2.03 1.067 27.10 818 1217
12 2 0.045 1.14 0.384 9.75 85 127
12 3 0.045 1.14 0.408 10.36 115 172
12 4 0.045 1.14 0.445 11.30 147 219
12 5 0.045 1.14 0.487 12.37 171 255
12 6 0.060 1.52 0.562 14.27 217 323
12 7 0.060 1.52 0.562 14.27 244 363
12 8 0.060 1.52 0.607 15.42 275 410
12 9 0.060 1.52 0.651 16.54 307 457
12 10 0.060 1.52 0.709 18.01 340 506
12 12 0.060 1.52 0.732 18.59 396 589
12 15 0.080 2.03 0.813 20.65 484 721
12 19 0.080 2.03 0.896 22.76 628 934
12 20 0.080 2.03 0.942 23.93 661 984
12 25 0.080 2.03 1.043 26.49 811 1207
12 30 0.080 2.03 1.104 28.04 953 1418
12 37 0.080 2.03 1.190 30.23 1152 1714
10 2 0.045 1.14 0.431 10.95 116 172
10 3 0.045 1.14 0.459 11.66 161 239
10 4 0.045 1.14 0.502 12.75 205 306
10 5 0.060 1.52 0.581 14.76 260 387
10 6 0.060 1.52 0.632 16.05 306 455
10 7 0.060 1.52 0.632 16.05 346 514
10 8 0.060 1.52 0.685 17.40 392 583
10 9 0.060 1.52 0.736 18.69 437 651
10 10 0.060 1.52 0.803 20.40 485 721
10 12 0.080 2.03 0.870 22.10 599 892
10 15 0.080 2.03 0.964 24.49 733 1091
10 19 0.080 2.03 1.014 25.76 901 1340
10 20 0.080 2.03 1.066 27.08 949 1412
10 25 0.080 2.03 1.184 30.07 1168 1739
10 30 0.080 2.03 1.254 31.85 1379 2052
10 37 0.080 2.03 1.355 34.42 1674 2491

Request the Complete Data Sheet

If you need a specific product catalogue or related standard file, please contact us.

From Production to Delivery

From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.

cable production line with finished cable being wound onto a reel

Production

Stranded bare annealed copper conductors are insulated with XLPE, assembled into the required multicore construction and finished with the low-smoke halogen-free XLPO jacket.

Cable and conductor quality inspection and testing

Inspection

Inspection focuses on conductor construction, insulation and jacket condition, finished dimensions, cable weight, cable marking and the documentation required by the project.

Overhead conductors packed on wooden drums for shipment

Packaging

Finished cable is wound on reels or drums according to cable size, weight and ordered length. Product identification can include AWG size, core count, standard reference, length and project reference.

Wooden drums of overhead conductors loaded into shipping container

Shipping

Before shipment, cable identification, packing and requested test / approval documents are checked against the order. Project-specific documentation requirements should be agreed before production.

Frequently Asked Questions

When should I choose XHHW/XLPO instead of XHHW/PVC or XHHW/CPE?

Choose XHHW/XLPO when the project specifically values a low-smoke halogen-free polyethylene outer jacket. The PVC and CPE versions remain separate constructions with different jacket materials and approval bases. The correct choice should follow the tender specification, environmental requirements and required fire/smoke documentation.

No. The source describes the jacket as low-smoke halogen-free polyethylene, but it does not list specific IEC 60754, IEC 61034 or other LSZH test results on this product sheet. If a project specifies exact smoke, halogen or flame limits, request the applicable test reports for the offered XLPO construction.

Type TC identifies the tray-cable product category. TC-ER applies to qualifying exposed-run constructions outside the tray under the relevant installation rules. The source states that constructions with three or more conductors are listed for exposed runs; confirm the exact ordered cable carries the required TC-ER marking.

The product data lists direct burial and Class 1, Division 2 applications. Formal project approval still depends on the actual cable markings/listing, fittings, seals, installation method and governing electrical code.

Confirm whether the project simply requires an XLPO/low-smoke halogen-free jacket or whether it specifies exact smoke-density, halogen-acid-gas or flame-test standards. Those detailed performance requirements should be stated before quotation so the supplier can match the construction and supporting documentation.

Provide AWG size, number of cores, total length, installation method and required Type TC / TC-ER markings. Also state direct-burial, outdoor, wet-location, hazardous-location, RoHS and any low-smoke/halogen-free test-document requirements, plus reel length and cable marking.

Request for Free Consultation

Contact Information

Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.

Explore More

Related Products
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Compatible Hardware
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Knowledge Articles
Customer Visits Our Factory for Product Inspection and Quality Verification
AAAC all aluminium alloy conductor stranded wire
AAAC Conductor Selection Guide: How to Choose the Right AAAC for Overhead Lines
International Airport Expansion Project in Saudi Arabia

For Immediate Assistance, Please Contact us Now!