UL 1277 Multi-Conductor CU 600V FR-XLPE CPE Jacket Control Cable
UL 1277 Multi-Conductor CU 600V FR-XLPE CPE Jacket Control Cable is a silicone-free industrial control cable with Class B compressed bare-copper conductors, flame-retardant XLPE insulation and a chlorinated-polyethylene (CPE) outer jacket. It is designed for wet and dry control-cable installations requiring tray-cable construction, robust thermal capability and industrial environmental resistance.
PRODUCT OVERVIEW
The cable uses 7-strand Class B compressed bare-copper conductors, FR-XLPE insulation and an overall CPE jacket. Polypropylene filler is used on cables with five or fewer conductors, while constructions with more than five conductors use a polyester flat-thread binder tape. A rip cord is included to simplify jacket removal.
The product is rated 600V and is suited for wet and dry areas, conduits, ducts, troughs, trays, direct burial and aerial routes supported by a messenger. The source lists conductor-temperature limits of 90°C for normal operation, 130°C for emergency overload and 250°C for short-circuit conditions. UL-rated constructions may be used in Class I, II and III, Division 2 hazardous locations, while constructions with three or more conductors are stated as listed for exposed runs (TC-ER).
KEY FEATURES
- UL 1277 electrical power and control tray-cable product basis.
- 600V multi-conductor copper control cable.
- 7-strand Class B compressed bare copper conductor.
- FR-XLPE insulation.
- Chlorinated Polyethylene (CPE) outer jacket.
- Silicone-free construction.
- 90°C normal / 130°C emergency overload / 250°C short-circuit conductor temperatures stated in the source.
- Direct-burial, tray, duct, conduit, trough and messenger-supported aerial applications.
- UL-rated constructions may be used in Class I, II and III, Division 2 hazardous locations.
- TC-ER exposed-run capability stated for UL-rated constructions with 3 or more conductors.
CABLE CONSTRUCTION
Conductor | 7-strand Class B compressed bare copper; source references ASTM B3 and ASTM B8 |
Insulation | Flame Retardant Cross Linked Polyethylene (FR-XLPE) |
Insulation Thickness | 30 mil stated for all listed cable sizes in the construction description |
Filler | Polypropylene filler on cables with 5 or fewer conductors |
Binder | Polyester flat-thread binder tape on cables with more than 5 conductors |
Rip Cord | Included for ease of jacket removal |
Overall Jacket | Chlorinated Polyethylene (CPE) |
Voltage Rating | 600V |
Silicone Free | Yes, stated in the source |
STANDARD REFERENCE & COMPLIANCE
Item | Details |
Referenced Product Standard | UL 1277 – Electrical Power and Control Tray Cables |
Current Status | Active |
Current Edition | Edition 6 |
Current Published Revision | May 29, 2025 |
Product Position | Multi-Conductor CU 600V FR-XLPE / CPE Jacket Control Cable |
Compliance Note | Confirm the required UL listing/marking and project ratings such as TC-ER, direct burial and hazardous-location use on the offered cable documentation before formal approval. |
UL 1277 is the main finished-product standard for this cable because it addresses the complete power/control tray-cable construction. The currently published standard remains Edition 6 with the latest formal revision dated May 29, 2025.
UL 1277 TYPE TC DESIGN FOCUS
Focus | How It Relates to This Product |
Complete Multiconductor Cable | Compressed copper conductors, FR-XLPE insulation, filler/binder and CPE jacket |
Tray / Raceway Installations | Source lists trays, troughs, conduits and ducts |
Direct Burial | Stated in the application data |
Wet / Dry Locations | Both are stated, with 90°C normal operation |
Aerial Use | Messenger-supported aerial installation is stated |
Hazardous Locations | UL-rated constructions may be used in Class I, II and III, Division 2 locations |
TC-ER | UL-rated constructions with 3 or more conductors are stated as listed for exposed runs |
PRODUCT APPLICATIONS
- Industrial control circuits requiring 600V multi-conductor tray cable.
- Wet and dry areas.
- Conduits, ducts, troughs and trays.
- Direct-burial installations.
- Aerial routes supported by a messenger.
- Projects requiring CPE-jacketed, FR-XLPE insulated control cable.
- UL-rated Class I, II and III, Division 2 hazardous-location applications.
- TC-ER exposed-run installations for qualifying UL-rated constructions with 3 or more conductors.
| AWG | Cores | Cond. Dia. in | Insul. mil | Jacket mil | OD in | Cu Wt lb/kft | Cable Wt lb/kft | DC R Ω/kft | Min Bend in | Amp 60°C | Amp 75°C | Amp 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 10 | 2 | 0.111 | 30 | 45 | 0.431 | 65 | 124 | 1.040 | 1.300 | 1.7 | 30 | 30 |
| 10 | 3 | 0.111 | 30 | 45 | 0.459 | 97 | 165 | 1.040 | 1.300 | 1.8 | 30 | 30 |
| 10 | 4 | 0.111 | 30 | 45 | 0.511 | 130 | 205 | 1.040 | 1.300 | 2.1 | 24 | 28 |
| 10 | 4 | 0.111 | 30 | 45 | 0.516 | 130 | 206 | 1.040 | 1.300 | 2.1 | 24 | 28 |
| 10 | 5 | 0.111 | 30 | 60 | 0.581 | 162 | 273 | 1.040 | 1.300 | 2.3 | 24 | 28 |
| 10 | 6 | 0.111 | 30 | 60 | 0.632 | 194 | 323 | 1.040 | 1.300 | 2.5 | 24 | 28 |
| 10 | 7 | 0.111 | 30 | 60 | 0.641 | 227 | 356 | 1.040 | 1.300 | 2.5 | 21 | 24 |
| 10 | 8 | 0.111 | 30 | 60 | 0.685 | 259 | 410 | 1.040 | 1.300 | 2.7 | 21 | 24 |
| 10 | 9 | 0.111 | 30 | 60 | 0.736 | 291 | 461 | 1.040 | 1.300 | 2.9 | 21 | 24 |
| 10 | 10 | 0.111 | 30 | 60 | 0.803 | 324 | 519 | 1.040 | 1.300 | 3.2 | 15 | 17 |
| 10 | 12 | 0.111 | 30 | 60 | 0.830 | 389 | 600 | 1.040 | 1.300 | 3.3 | 15 | 17 |
| 10 | 12 | 0.111 | 30 | 60 | 0.887 | 389 | 615 | 1.040 | 1.300 | 3.5 | 15 | 17 |
| 10 | 15 | 0.111 | 30 | 80 | 0.964 | 486 | 777 | 1.040 | 1.300 | 3.9 | 15 | 17 |
| 10 | 19 | 0.111 | 30 | 80 | 1.014 | 615 | 941 | 1.040 | 1.300 | 5.1 | 15 | 17 |
| 10 | 20 | 0.111 | 30 | 80 | 1.067 | 648 | 1001 | 1.040 | 1.300 | 5.3 | 15 | 17 |
| 10 | 25 | 0.111 | 30 | 80 | 1.184 | 810 | 1236 | 1.040 | 1.300 | 5.9 | 13 | 15 |
| 10 | 30 | 0.111 | 30 | 80 | 1.254 | 971 | 1450 | 1.040 | 1.300 | 6.3 | 13 | 15 |
| 10 | 37 | 0.111 | 30 | 80 | 1.355 | 1198 | 1755 | 1.040 | 1.300 | 6.8 | 12 | 14 |
| AWG | Cores | Cond. Dia. in | Insul. mil | Jacket mil | OD in | Cu Wt lb/kft | Cable Wt lb/kft | DC R Ω/kft | Min Bend in | Amp 60°C | Amp 75°C | Amp 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 12 | 2 | 0.087 | 30 | 45 | 0.384 | 41 | 90 | 1.660 | 2.075 | 1.5 | 20 | 20 |
| 12 | 2 | 0.087 | 30 | 45 | 0.398 | 41 | 103 | 1.660 | 2.075 | 1.6 | 20 | 20 |
| 12 | 3 | 0.087 | 30 | 45 | 0.408 | 61 | 118 | 1.660 | 2.075 | 1.6 | 20 | 20 |
| 12 | 4 | 0.087 | 30 | 45 | 0.445 | 81 | 148 | 1.660 | 2.075 | 1.8 | 16 | 20 |
| 12 | 4 | 0.087 | 30 | 45 | 0.461 | 81 | 155 | 1.660 | 2.075 | 1.8 | 16 | 20 |
| 12 | 5 | 0.087 | 30 | 45 | 0.487 | 102 | 181 | 1.660 | 2.075 | 1.9 | 16 | 20 |
| 12 | 6 | 0.087 | 30 | 45 | 0.532 | 122 | 214 | 1.660 | 2.075 | 2.1 | 16 | 20 |
| 12 | 7 | 0.087 | 30 | 45 | 0.532 | 143 | 237 | 1.660 | 2.075 | 2.1 | 14 | 17 |
| 12 | 8 | 0.087 | 30 | 60 | 0.607 | 163 | 288 | 1.660 | 2.075 | 2.4 | 14 | 17 |
| 12 | 9 | 0.087 | 30 | 60 | 0.661 | 183 | 324 | 1.660 | 2.075 | 2.6 | 14 | 17 |
| 12 | 10 | 0.087 | 30 | 60 | 0.709 | 204 | 365 | 1.660 | 2.075 | 2.8 | 10 | 12 |
| 12 | 12 | 0.087 | 30 | 60 | 0.732 | 244 | 419 | 1.660 | 2.075 | 2.9 | 10 | 12 |
| 12 | 15 | 0.087 | 30 | 60 | 0.813 | 305 | 516 | 1.660 | 2.075 | 3.3 | 10 | 12 |
| 12 | 19 | 0.087 | 30 | 80 | 0.896 | 387 | 657 | 1.660 | 2.075 | 3.6 | 10 | 12 |
| 12 | 20 | 0.087 | 30 | 80 | 0.942 | 407 | 699 | 1.660 | 2.075 | 3.8 | 10 | 12 |
| 12 | 25 | 0.087 | 30 | 80 | 1.043 | 509 | 860 | 1.660 | 2.075 | 5.2 | 9 | 11 |
| 12 | 30 | 0.087 | 30 | 80 | 1.104 | 611 | 1005 | 1.660 | 2.075 | 5.5 | 9 | 11 |
| 12 | 37 | 0.087 | 30 | 80 | 1.191 | 753 | 1211 | 1.660 | 2.075 | 6.0 | 8 | 10 |
| AWG | Cores | Cond. Dia. in | Insul. mil | Jacket mil | OD in | Cu Wt lb/kft | Cable Wt lb/kft | DC R Ω/kft | Min Bend in | Amp 60°C | Amp 75°C | Amp 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 | 2 | 0.070 | 30 | 45 | 0.349 | 26 | 63 | 2.630 | 3.288 | 1.4 | 15 | 15 |
| 14 | 3 | 0.070 | 30 | 45 | 0.370 | 38 | 87 | 2.630 | 3.288 | 1.5 | 15 | 15 |
| 14 | 4 | 0.070 | 30 | 45 | 0.403 | 51 | 109 | 2.630 | 3.288 | 1.6 | 14 | 15 |
| 14 | 5 | 0.070 | 30 | 45 | 0.440 | 64 | 132 | 2.630 | 3.288 | 1.8 | 14 | 15 |
| 14 | 6 | 0.070 | 30 | 45 | 0.479 | 77 | 155 | 2.630 | 3.288 | 1.9 | 14 | 15 |
| 14 | 7 | 0.070 | 30 | 45 | 0.479 | 90 | 171 | 2.630 | 3.288 | 1.9 | 12 | 15 |
| 14 | 8 | 0.070 | 30 | 45 | 0.519 | 102 | 195 | 2.630 | 3.288 | 2.1 | 12 | 15 |
| 14 | 9 | 0.070 | 30 | 60 | 0.588 | 115 | 236 | 2.630 | 3.288 | 2.4 | 12 | 15 |
| 14 | 10 | 0.070 | 30 | 60 | 0.638 | 128 | 266 | 2.630 | 3.288 | 2.6 | 9 | 11 |
| 14 | 12 | 0.070 | 30 | 60 | 0.669 | 154 | 303 | 2.630 | 3.288 | 2.6 | 9 | 11 |
| 14 | 15 | 0.070 | 30 | 60 | 0.730 | 192 | 371 | 2.630 | 3.288 | 2.9 | 9 | 11 |
| 14 | 19 | 0.070 | 30 | 60 | 0.768 | 243 | 446 | 2.630 | 3.288 | 3.1 | 9 | 11 |
| 14 | 20 | 0.070 | 30 | 60 | 0.808 | 256 | 475 | 2.630 | 3.288 | 3.2 | 9 | 11 |
| 14 | 25 | 0.070 | 30 | 80 | 0.937 | 320 | 619 | 2.630 | 3.288 | 3.7 | 8 | 9 |
| 14 | 30 | 0.070 | 30 | 80 | 0.991 | 384 | 719 | 2.630 | 3.288 | 4.0 | 8 | 9 |
| 14 | 37 | 0.070 | 30 | 80 | 1.067 | 474 | 862 | 2.630 | 3.288 | 5.3 | 7 | 8 |
| AWG | Cores | Cond. Dia. in | Insul. mil | Jacket mil | OD in | Cu Wt lb/kft | Cable Wt lb/kft | DC R Ω/kft | Min Bend in | Amp 60°C | Amp 75°C | Amp 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 16 | 2 | 0.057 | 25 | 45 | 0.308 | 16 | 47 | 4.180 | 5.265 | 1.2 | ||
| 16 | 4 | 0.057 | 25 | 45 | 0.355 | 32 | 77 | 4.180 | 5.265 | 1.4 | ||
| 16 | 7 | 0.057 | 25 | 45 | 0.425 | 56 | 121 | 4.180 | 5.265 | 1.7 |
Request the Complete Data Sheet
From Production to Delivery
From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.
Production
Class B compressed bare-copper conductors are prepared, insulated with FR-XLPE, assembled with polypropylene filler or polyester binder according to the number of conductors, fitted with the rip cord and finished with the CPE jacket.
Inspection
Inspection focuses on conductor construction, insulation/jacket thickness, overall diameter, conductor and cable weight, DC/AC resistance, bending-radius data, cable marking and project-specified test documentation.
Packaging
Finished cable is wound on reels or drums suitable for its diameter, weight and ordered length. Product identification can include conductor size, core count, standard reference, length and project number.
Shipping
Before shipment, cable marking, packing, inspection records and requested standard/test documents are checked against the order and project approval requirements.
Frequently Asked Questions
When is this FR-XLPE / CPE control cable a better choice than a simpler PVC control cable?
This construction is intended for projects that need a 600V tray/control cable with FR-XLPE insulation, a CPE outer jacket and the higher thermal limits stated in the product data. The choice should be driven by the project specification, environmental conditions and required UL / fire-performance documentation rather than jacket material alone.
What should I verify if TC-ER is required?
The source states that UL-rated constructions with three or more conductors are listed for exposed runs. For procurement, confirm that the exact conductor size and core count being supplied carries the required TC-ER marking/listing, because a family-level statement is not a substitute for the actual cable marking.
Can this cable be used in hazardous locations?
The source states that UL-rated constructions can be used in Class I, II and III, Division 2 hazardous locations. The complete installation still depends on cable marking, fittings, seals, wiring method and the governing NEC/project requirements.
How should the 60°C, 75°C and 90°C ampacity columns be used?
Use the column that corresponds to the permitted conductor/termination temperature in the project design, then apply any code-required derating for ambient temperature, grouping and installation conditions. The table values are source product data, not a substitute for the governing electrical-code calculation.
What information should I provide for an accurate quotation?
Provide conductor size, core count, required length, installation method and any required TC-ER, direct-burial or hazardous-location markings. Also state the applicable ampacity/temperature basis, conductor-identification requirement, reel length and all required UL / ICEA / flame-test documents.
What products do you supply for the power cable industry?
We provide a wide range of cable materials and electrical products, including aluminum conductors, aluminum rods, aluminum wires, overhead conductors, medium and low voltage power cables, cable insulation materials, filling materials, shielding materials, and cable manufacturing consumables.We provide customized solutions according to different cable manufacturing requirements.
Request for Free Consultation
Contact Information
Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.