UL 1277 FR-XLPE Thermoset CPE Jacket Control Cable 600V

UL 1277 FR-XLPE Thermoset CPE Jacket Control Cable is a silicone-free 600V multi-conductor control cable with Class B compressed bare-copper conductors, flame-retardant XLPE insulation and a thermoset chlorinated-polyethylene (CPE) outer jacket. It is designed for industrial tray/control circuits requiring robust thermal performance and wet/dry installation capability.

PRODUCT OVERVIEW

The cable uses 7-strand Class B compressed bare-copper conductors with FR-XLPE insulation and a thermoset CPE overall jacket. Polypropylene filler is used for constructions with five or fewer conductors, while cables with more than five conductors use a polyester flat-thread binder tape. A rip cord is included to simplify jacket removal.

The product is rated 600V and is intended for wet and dry areas, conduits, ducts, troughs, trays, direct burial and aerial routes supported by a messenger. The source lists conductor-temperature limits of 90°C for normal operation, 130°C for emergency overload and 250°C for short-circuit conditions. UL-rated constructions may be used in Class I, II and III, Division 2 hazardous locations, and UL-rated constructions with three or more conductors are stated as listed for exposed runs (TC-ER).

KEY FEATURES

  • UL 1277 electrical power/control tray-cable product basis.
  • 600V multi-conductor copper control cable.
  • 7-strand Class B compressed bare-copper conductor.
  • FR-XLPE insulation.
  • Thermoset Chlorinated Polyethylene (CPE) outer jacket.
  • Silicone-free construction.
  • 90°C normal / 130°C emergency overload / 250°C short-circuit conductor temperatures stated in the source.
  • Suitable for wet/dry areas, conduit, duct, trough, tray, direct burial and messenger-supported aerial routes.
  • UL-rated constructions may be used in Class I, II and III, Division 2 hazardous locations.
  • TC-ER exposed-run capability stated for qualifying 3+ conductor constructions.

CABLE CONSTRUCTION

Conductor

7-strand Class B compressed bare copper; source references ASTM B3 and ASTM B8

Insulation

Flame Retardant Cross Linked Polyethylene (FR-XLPE)

Insulation Thickness

30 mil stated for listed 14 / 12 / 10 AWG constructions; source separately lists 25 mil for the 18 AWG row

Filler

Polypropylene filler on cables with 5 or fewer conductors

Binder

Polyester flat-thread binder tape on cables with more than 5 conductors

Rip Cord

Included for ease of jacket removal

Overall Jacket

Thermoset Chlorinated Polyethylene (CPE)

Voltage Rating

600V

Silicone Free

Yes

Screen / Armour

None stated

UL 1277 TYPE TC DESIGN FOCUS

Focus

How It Relates to This Product

Complete Cable Assembly

Compressed copper conductors, FR-XLPE insulation, filler/binder system and thermoset CPE jacket

Tray / Raceway Installations

Source lists trays, troughs, conduits and ducts

Direct Burial

Stated in the source application data

Wet / Dry Locations

Both are stated, with 90°C normal operation

Aerial Use

Messenger-supported aerial installation is stated

Hazardous Locations

UL-rated constructions may be used in Class I, II and III, Division 2 locations

TC-ER

UL-rated 3+ conductor constructions are stated as listed for exposed runs

THERMOSET CPE JACKET - WHAT IS DIFFERENT?

This product is specifically identified with a thermoset chlorinated-polyethylene (CPE) jacket. That distinguishes it from the previously reviewed CPE-jacket products that did not explicitly call out the jacket as thermoset in the product name. For procurement, the jacket designation should be kept in the product title because it is part of the construction being offered.

The source does not provide a separate comparative property table between thermoset CPE and other CPE formulations. Therefore, this page does not add unsupported claims about oil resistance, chemical resistance or mechanical superiority beyond what the source explicitly supports.

PRODUCT APPLICATIONS

  • Industrial 600V multi-conductor control circuits.
  • Wet and dry areas.
  • Conduits, ducts, troughs and cable trays.
  • Direct-burial installations.
  • Aerial routes supported by a messenger.
  • Projects requiring FR-XLPE insulation and a thermoset CPE jacket.
  • UL-rated Class I, II and III, Division 2 hazardous-location applications.
  • TC-ER exposed-run installations for qualifying UL-rated constructions with 3 or more conductors.

Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.

AWG Cores Cond. Dia. in Insul. mil Jacket mil OD in Cu Wt lb/kft Cable Wt lb/kft DC R Ω/kft AC R @90°C Ω/kft Min Bend in Amp 60°C Amp 75°C Amp 90°C
10 2 0.111 30 45 0.431 65 124 1.040 1.300 1.7 30 30 30
10 3 0.111 30 45 0.459 97 165 1.040 1.300 1.8 30 30 30
10 4 0.111 30 45 0.502 130 210 1.040 1.300 2.0 24 28 30
10 5 0.111 30 60 0.581 162 273 1.040 1.300 2.3 24 28 30
10 6 0.111 30 60 0.632 194 323 1.040 1.300 2.5 24 28 30
10 7 0.111 30 60 0.632 227 358 1.040 1.300 2.5 21 24 28
10 8 0.111 30 60 0.685 259 410 1.040 1.300 2.7 21 24 28
10 9 0.111 30 60 0.736 291 461 1.040 1.300 2.9 21 24 28
10 10 0.111 30 60 0.803 324 519 1.040 1.300 3.2 15 17 20
10 12 0.111 30 60 0.830 389 600 1.040 1.300 3.3 15 17 20
10 15 0.111 30 80 0.964 486 777 1.040 1.300 3.9 15 17 20
10 19 0.111 30 80 1.014 615 941 1.040 1.300 5.1 15 17 20
10 20 0.111 30 80 1.067 648 1001 1.040 1.300 5.3 15 17 20
10 25 0.111 30 80 1.184 810 1236 1.040 1.300 5.9 13 15 18
10 30 0.111 30 80 1.254 971 1450 1.040 1.300 6.3 13 15 18
10 37 0.111 30 80 1.355 1198 1755 1.040 1.300 6.8 12 14 16

Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.

AWG Cores Cond. Dia. in Insul. mil Jacket mil OD in Cu Wt lb/kft Cable Wt lb/kft DC R Ω/kft AC R @90°C Ω/kft Min Bend in Amp 60°C Amp 75°C Amp 90°C
12 2 0.087 30 45 0.384 41 90 1.660 2.075 1.5 20 20 20
12 3 0.087 30 45 0.408 61 118 1.660 2.075 1.6 20 20 20
12 4 0.087 30 45 0.445 81 148 1.660 2.075 1.8 16 20 20
12 5 0.087 30 45 0.487 102 181 1.660 2.075 1.9 16 20 20
12 6 0.087 30 45 0.532 122 214 1.660 2.075 2.1 16 20 20
12 7 0.087 30 45 0.532 143 237 1.660 2.075 2.1 14 17 20
12 8 0.087 30 60 0.607 163 288 1.660 2.075 2.4 14 17 20
12 9 0.087 30 60 0.651 183 324 1.660 2.075 2.6 14 17 20
12 10 0.087 30 60 0.709 204 365 1.660 2.075 2.8 10 12 15
12 12 0.087 30 60 0.732 244 419 1.660 2.075 2.9 10 12 15
12 15 0.087 30 60 0.813 305 516 1.660 2.075 3.3 10 12 15
12 19 0.087 30 80 0.896 387 657 1.660 2.075 3.6 10 12 15
12 20 0.087 30 80 0.942 407 699 1.660 2.075 3.8 10 12 15
12 25 0.087 30 80 1.043 509 860 1.660 2.075 5.2 9 11 13
12 30 0.087 30 80 1.104 611 1005 1.660 2.075 5.5 9 11 13
12 37 0.087 30 80 1.191 753 1211 1.660 2.075 6.0 8 10 12

Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.

AWG Cores Cond. Dia. in Insul. mil Jacket mil OD in Cu Wt lb/kft Cable Wt lb/kft DC R Ω/kft AC R @90°C Ω/kft Min Bend in Amp 60°C Amp 75°C Amp 90°C
14 2 0.070 30 45 0.349 26 68 2.630 3.288 1.4 15 15 15
14 3 0.070 30 45 0.370 38 87 2.630 3.288 1.5 15 15 15
14 4 0.070 30 45 0.403 51 109 2.630 3.288 1.6 14 15 15
14 5 0.070 30 45 0.440 64 132 2.630 3.288 1.8 14 15 15
14 6 0.070 30 45 0.479 77 155 2.630 3.288 1.9 14 15 15
14 7 0.070 30 45 0.479 90 171 2.630 3.288 1.9 12 15 15
14 8 0.070 30 45 0.519 102 195 2.630 3.288 2.1 12 15 15
14 9 0.070 30 60 0.588 115 236 2.630 3.288 2.4 12 15 15
14 10 0.070 30 60 0.638 128 266 2.630 3.288 2.6 9 11 12
14 12 0.070 30 60 0.659 154 303 2.630 3.288 2.6 9 11 12
14 15 0.070 30 60 0.730 192 371 2.630 3.288 2.9 9 11 12
14 19 0.070 30 60 0.768 243 446 2.630 3.288 3.1 9 11 12
14 20 0.070 30 60 0.808 256 475 2.630 3.288 3.2 9 11 12
14 25 0.070 30 80 0.937 320 619 2.630 3.288 3.7 8 9 11
14 30 0.070 30 80 0.991 384 719 2.630 3.288 4.0 8 9 11
14 37 0.070 30 80 1.067 474 862 2.630 3.288 5.3 7 8 10

Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.

AWG Cores Cond. Dia. in Insul. mil Jacket mil OD in Cu Wt lb/kft Cable Wt lb/kft DC R Ω/kft AC R @90°C Ω/kft Min Bend in Amp 60°C Amp 75°C Amp 90°C
18 20 0.046 25 60 0.638 101 237 6.54 8.34 1.4 3 3 3

Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

Request the Complete Data Sheet

If you need a specific product catalogue or related standard file, please contact us.

From Production to Delivery

From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.

cable production line with finished cable being wound onto a reel

Production

Class B compressed bare-copper conductors are prepared, insulated with FR-XLPE, assembled with polypropylene filler or polyester binder according to core count, fitted with the rip cord and finished with the thermoset CPE jacket.

Cable and conductor quality inspection and testing

Inspection

Inspection focuses on conductor construction, insulation/jacket thickness, overall diameter, conductor/cable weight, DC and AC resistance, bending-radius data, cable marking and project-specified test documentation.

Overhead conductors packed on wooden drums for shipment

Packaging

Finished cable is wound on reels or drums suitable for its diameter, weight and ordered length. Product identification can include conductor size, core count, standard reference, length and project number.

Wooden drums of overhead conductors loaded into shipping container

Shipping

Before shipment, cable marking, packing, inspection records and requested standard/test documents are checked against the approved order and project requirements.

Frequently Asked Questions

When should I specify the thermoset CPE version rather than another CPE-jacket control cable?

Specify this version when the project or buyer explicitly calls for the thermoset CPE jacket construction shown in the product data. The FR-XLPE insulation, compressed copper conductor and Type TC application remain important, but the exact jacket designation can affect the approved construction and project submittal. Do not substitute another CPE formulation without technical confirmation.

The source states that UL-rated constructions with three or more conductors are listed for exposed runs. For procurement, confirm that the exact conductor size and core count being offered carries the required TC-ER marking/listing rather than relying only on the family description.

The source states that UL-rated constructions can be used in Class I, II and III, Division 2 hazardous locations. The complete installation also depends on cable marking, fittings, seals, wiring method and the governing NEC/project requirements, so cable and installation should be reviewed together.

Select the column that matches the allowable conductor/termination temperature for the project, then apply any required derating for ambient temperature, grouping and installation conditions. The table values are product data and should be used together with the governing electrical-code calculation.

The source product table lists only one 18 AWG construction: 20 conductors. No other 18 AWG core counts are provided, so this page does not extrapolate additional sizes.

We provide a wide range of cable materials and electrical products, including aluminum conductors, aluminum rods, aluminum wires, overhead conductors, medium and low voltage power cables, cable insulation materials, filling materials, shielding materials, and cable manufacturing consumables.We provide customized solutions according to different cable manufacturing requirements.

Request for Free Consultation

Contact Information

Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.

Explore More

Related Products
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Compatible Hardware
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Knowledge Articles
Customer Visits Our Factory for Product Inspection and Quality Verification
AAAC all aluminium alloy conductor stranded wire
AAAC Conductor Selection Guide: How to Choose the Right AAAC for Overhead Lines
International Airport Expansion Project in Saudi Arabia

For Immediate Assistance, Please Contact us Now!