UL 1277 CU PE PVC Insulation PVC Jacket Control Cable 600V

UL 1277 CU PE/PVC Insulation PVC Jacket Control Cable is a 600V multi-conductor industrial control cable with Class B compressed bare-copper conductors, a dual-layer polyethylene and polyvinyl chloride insulation system, and a PVC overall jacket. It is intended for wet and dry industrial control circuits where tray-cable construction, stable electrical performance and practical PVC protection are required.

PRODUCT OVERVIEW

The cable uses 7-strand Class B compressed bare-copper conductors. Each conductor is insulated with 20 mil polyethylene (PE) plus 10 mil polyvinyl chloride (PVC), giving a 30 mil combined insulation thickness. Polypropylene filler is used on cables with five or fewer conductors, while cables with more than five conductors use a polyester flat-thread binder tape. A rip cord is included for easier jacket removal, and the assembly is finished with a PVC overall jacket.

The supplied product data lists 600V service in wet and dry areas, conduits, ducts, troughs, trays, direct-burial routes and messenger-supported aerial installations. It states maximum conductor temperatures of 90°C for normal operation, 130°C for emergency overload and 250°C for short-circuit conditions. Any required TC-ER, hazardous-location, direct-burial or other listing must be confirmed on the exact offered cable documentation.

KEY FEATURES

  • UL 1277 electrical power and control tray-cable product basis.
  • 600V multi-conductor copper control cable.
  • 7-strand Class B compressed bare-copper conductors.
  • Dual-layer PE/PVC insulation: 20 mil PE plus 10 mil PVC.
  • Polyvinyl Chloride (PVC) overall jacket.
  • Silicone-free construction.
  • 90°C normal / 130°C emergency overload / 250°C short-circuit conductor temperatures stated in the source.
  • Suitable for trays, troughs, conduits, ducts, direct burial and messenger-supported aerial installations as stated in the source.
  • Conductor Identification Method 1 Table 1 is stated in the product description.
  • Project-specific UL marking and optional ratings must be confirmed on the exact ordered construction.

CABLE CONSTRUCTION

Conductor

7-strand Class B compressed bare copper; source references ASTM B3 and ASTM B8

Insulation

Dual-layer Polyethylene and Polyvinyl Chloride (PE/PVC)

Insulation Thickness

20 mil PE plus 10 mil PVC, 30 mil combined

Filler

Polypropylene filler on cables with 5 or fewer conductors

Binder

Polyester flat-thread binder tape on cables with more than 5 conductors

Rip Cord

Included for ease of jacket removal

Overall Jacket

Polyvinyl Chloride (PVC)

Voltage Rating

600V

Silicone Free

Yes, stated in the source

UL 1277 TYPE TC DESIGN FOCUS

Focus

How It Relates to This Product

Complete Multiconductor Cable

Compressed copper conductors, PE/PVC insulation, filler or binder system and PVC jacket

Tray and Raceway Installations

Source lists trays, troughs, conduits and ducts

Direct Burial

Stated in the product application; verify the exact marking

Wet and Dry Locations

Both are stated, with 90°C normal operation

Aerial Use

Messenger-supported aerial installation is stated

Conductor Identification

Method 1 Table 1 stated in the product description

Approval Scope

Confirm listing evidence and optional ratings on the exact offered cable

WHY PE PVC INSULATION

The defining construction feature is the dual-layer PE/PVC insulation system. The source specifies 20 mil polyethylene plus 10 mil polyvinyl chloride on every listed conductor size. PE provides the inner insulation layer, while PVC forms the outer insulation layer; the combined schedule is shown as 30 mil in the technical table.

The overall cable jacket is also PVC, but it is a separate protective layer outside the assembled conductors. The conductor insulation and the overall jacket must therefore be described independently in quotations, drawings and production documents.

PRODUCT APPLICATIONS

  • Industrial 600V multi-conductor control circuits.
  • Wet and dry areas.
  • Conduits, ducts, troughs and trays.
  • Direct-burial installations where the exact cable marking is confirmed.
  • Messenger-supported aerial routes.
  • Projects requiring dual-layer PE/PVC conductor insulation and a PVC jacket.
  • Control installations requiring Method 1 Table 1 conductor identification.
  • Applications requiring UL 1277 product basis, subject to confirmation of the offered cable listing and markings.

Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.

AWG Cores Cond. Dia. in Insul. mil Jacket mil OD in Cu Wt lb/kft Cable Wt lb/kft DC R Ω/kft AC R @90°C Ω/kft Min Bend in Amp 60°C Amp 75°C Amp 90°C
10 2 0.111 30 45 0.431 65 124 1.040 1.300 1.7 30 30 30
10 3 0.111 30 45 0.459 97 165 1.040 1.300 1.8 30 30 30
10 4 0.111 30 45 0.502 130 210 1.040 1.300 2.0 24 28 30
10 5 0.111 30 60 0.581 162 273 1.040 1.300 2.3 24 28 30
10 6 0.111 30 60 0.632 194 323 1.040 1.300 2.5 24 28 30
10 7 0.111 30 60 0.632 227 358 1.040 1.300 2.5 21 24 28
10 8 0.111 30 60 0.685 259 410 1.040 1.300 2.7 21 24 28
10 9 0.111 30 60 0.736 291 461 1.040 1.300 2.9 21 24 28
10 10 0.111 30 60 0.803 324 519 1.040 1.300 3.2 15 17 20
10 12 0.111 30 60 0.830 389 600 1.040 1.300 3.3 15 17 20
10 15 0.111 30 80 0.964 486 777 1.040 1.300 3.9 15 17 20
10 19 0.111 30 80 1.014 615 941 1.040 1.300 5.1 15 17 20
10 20 0.111 30 80 1.067 648 1001 1.040 1.300 5.3 15 17 20
10 25 0.111 30 80 1.184 810 1236 1.040 1.300 5.9 13 15 18
10 30 0.111 30 80 1.254 971 1450 1.040 1.300 6.3 13 15 18
10 37 0.111 30 80 1.355 1198 1755 1.040 1.300 6.8 12 14 16

Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.

AWG Cores Cond. Dia. in Insul. mil Jacket mil OD in Cu Wt lb/kft Cable Wt lb/kft DC R Ω/kft AC R @90°C Ω/kft Min Bend in Amp 60°C Amp 75°C Amp 90°C
12 2 0.087 30 45 0.384 41 90 1.660 2.075 1.5 20 20 20
12 3 0.087 30 45 0.408 61 118 1.660 2.075 1.6 20 20 20
12 4 0.087 30 45 0.445 81 148 1.660 2.075 1.8 16 20 20
12 5 0.087 30 45 0.487 102 181 1.660 2.075 1.9 16 20 20
12 6 0.087 30 45 0.532 122 214 1.660 2.075 2.1 16 20 20
12 7 0.087 30 45 0.532 143 237 1.660 2.075 2.1 14 17 20
12 8 0.087 30 60 0.607 163 288 1.660 2.075 2.4 14 17 20
12 9 0.087 30 60 0.651 183 324 1.660 2.075 2.6 14 17 20
12 10 0.087 30 60 0.709 204 365 1.660 2.075 2.8 10 12 15
12 12 0.087 30 60 0.732 244 419 1.660 2.075 2.9 10 12 15
12 15 0.087 30 60 0.813 305 516 1.660 2.075 3.3 10 12 15
12 19 0.087 30 80 0.896 387 657 1.660 2.075 3.6 10 12 15
12 20 0.087 30 80 0.942 407 699 1.660 2.075 3.8 10 12 15
12 25 0.087 30 80 1.043 509 860 1.660 2.075 5.2 9 11 13
12 30 0.087 30 80 1.104 611 1005 1.660 2.075 5.5 9 11 13
12 37 0.087 30 80 1.191 753 1211 1.660 2.075 6.0 8 10 12

Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.

AWG Cores Cond. Dia. in Insul. mil Jacket mil OD in Cu Wt lb/kft Cable Wt lb/kft DC R Ω/kft AC R @90°C Ω/kft Min Bend in Amp 60°C Amp 75°C Amp 90°C
14 2 0.070 30 45 0.349 26 68 2.630 3.288 1.4 15 15 15
14 3 0.070 30 45 0.378 38 92 2.630 3.288 1.5 15 15 15
14 4 0.070 30 45 0.403 51 109 2.630 3.288 1.6 14 15 15
14 5 0.070 30 45 0.440 64 132 2.630 3.288 1.8 14 15 15
14 6 0.070 30 45 0.479 77 155 2.630 3.288 1.9 14 15 15
14 7 0.070 30 45 0.479 90 171 2.630 3.288 1.9 12 15 15
14 8 0.070 30 45 0.519 102 195 2.630 3.288 2.1 12 15 15
14 9 0.070 30 60 0.588 115 236 2.630 3.288 2.4 12 15 15
14 10 0.070 30 60 0.638 128 266 2.630 3.288 2.6 9 11 12
14 12 0.070 30 60 0.659 154 303 2.630 3.288 2.6 9 11 12
14 15 0.070 30 60 0.730 192 371 2.630 3.288 2.9 9 11 12
14 19 0.070 30 60 0.768 243 446 2.630 3.288 3.1 9 11 12
14 20 0.070 30 60 0.808 256 475 2.630 3.288 3.2 9 11 12
14 25 0.070 30 80 0.937 320 619 2.630 3.288 3.7 8 9 11
14 30 0.070 30 80 0.991 384 719 2.630 3.288 4.0 8 9 11
14 37 0.070 30 80 1.067 474 862 2.630 3.288 5.3 7 8 10

Request the Complete Data Sheet

If you need a specific product catalogue or related standard file, please contact us.

From Production to Delivery

From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.

cable production line with finished cable being wound onto a reel

Production

Class B compressed bare-copper conductors are prepared, insulated with PE and PVC in the stated layer thicknesses, assembled with polypropylene filler or polyester binder according to conductor count, fitted with the rip cord and finished with the PVC overall jacket.

Cable and conductor quality inspection and testing

Inspection

Inspection focuses on conductor construction, insulation and jacket thickness, overall diameter, conductor and cable weight, DC and AC resistance, bending-radius data, cable marking and project-specified test documentation.

Overhead conductors packed on wooden drums for shipment

Packaging

Finished cable is wound on reels or drums suitable for its diameter, weight and ordered length. Product identification can include conductor size, core count, standard reference, length and project number.

Wooden drums of overhead conductors loaded into shipping container

Shipping

Before shipment, cable marking, packing, inspection records and requested standard or test documents are checked against the order and project approval requirements.

Frequently Asked Questions

What is PE PVC insulation in this cable

Each conductor uses two insulation materials in sequence: 20 mil polyethylene and 10 mil polyvinyl chloride. The schedule therefore shows a 30 mil combined insulation thickness. This dual-layer conductor insulation is separate from the PVC overall jacket.

Confirm the UL file or listing evidence, cable marking and exact AWG and core-count construction offered. If the project also requires TC-ER, direct burial, wet-location or hazardous-location use, those ratings should appear in the applicable documentation or marking rather than being assumed from the product family name.

Use in a hazardous location depends on the exact cable listing and marking together with the installation method, fittings, seals and governing electrical code. Confirm the complete approval package for the ordered construction before specifying this application.

Use the column permitted by the conductor and termination temperature rating, then apply the code-required corrections for ambient temperature, grouping and installation conditions. The product table is not a substitute for the governing electrical-design calculation.

The product description states Method 1 Table 1 and cites ICEA S-58-679. State the required colour or numbering schedule in the inquiry so the production identification method can be confirmed before manufacture.

The supplied source includes exact duplicate rows and visibly malformed or conflicting entries. The clean schedule retains one usable row for each published AWG and core-count combination and flags the source issue for internal confirmation before quotation.

Request for Free Consultation

Contact Information

Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.

Explore More

Related Products
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Compatible Hardware
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Knowledge Articles
Customer Visits Our Factory for Product Inspection and Quality Verification
AAAC all aluminium alloy conductor stranded wire
AAAC Conductor Selection Guide: How to Choose the Right AAAC for Overhead Lines
International Airport Expansion Project in Saudi Arabia

For Immediate Assistance, Please Contact us Now!