AS/NZS 1125 Multicore + Earth Control Cable 0.6/1kV
AS/NZS 1125 Multicore + Earth Control Cable is a 0.6/1kV PVC insulated and PVC sheathed control cable using stranded plain annealed copper conductors in 1.5 mm² and 2.5 mm² sizes. The conductor constructions are 7/0.50 mm and 7/0.67 mm respectively, with multicore-plus-earth configurations from 2C+E to 50C+E for fixed control installations.
PRODUCT OVERVIEW
The product is built around stranded plain annealed copper conductors selected for reliable electrical performance in multicore control circuits. The 1.5 mm² conductor uses seven 0.50 mm copper wires, while the 2.5 mm² conductor uses seven 0.67 mm copper wires. Both are insulated with PVC V-90 and assembled with a matching green/yellow earth conductor before application of the PVC 5V-90 outer sheath.
The conductor design directly affects resistance, voltage drop and current capacity. The 2.5 mm² conductor has lower listed d.c. and a.c. resistance than the 1.5 mm² conductor, while both sizes are available across a wide 2C+E to 50C+E control-cable range.
KEY FEATURES
- Plain annealed copper conductor.
- 5 mm²: 7/0.50 mm stranded construction.
- 5 mm²: 7/0.67 mm stranded construction.
- Maximum DC resistance data at 20°C.
- Maximum AC resistance data at 75°C.
- PVC V-90 insulation.
- Matching green/yellow earth conductor.
- 2C+E to 50C+E multicore range.
CONDUCTOR CONSTRUCTION
Nominal Area | Conductor Construction | Max DC R @20°C | Max AC R @75°C | Available Core Range |
1.5 mm² | 7/0.50 mm | 13.6 Ω/km | 16.5 Ω/km | 2C+E to 50C+E |
2.5 mm² | 7/0.67 mm | 7.41 Ω/km | 9.01 Ω/km | 2C+E to 50C+E |
WHAT 7/0.50 AND 7/0.67 MEAN
The designation 7/0.50 means seven copper wires, each with a nominal diameter of 0.50 mm, are stranded to form the listed 1.5 mm² conductor. The 7/0.67 designation similarly identifies seven 0.67 mm copper wires used for the 2.5 mm² conductor.
ELECTRICAL PERFORMANCE
The listed maximum d.c. resistance at 20°C is 13.6 Ω/km for 1.5 mm² and 7.41 Ω/km for 2.5 mm². Maximum a.c. resistance at 75°C is 16.5 Ω/km and 9.01 Ω/km respectively. The lower resistance of the 2.5 mm² conductor supports lower voltage drop and higher current capacity.
CONDUCTOR IN MULTICORE + EARTH CONSTRUCTION
Area | Core Range | Conductor | Core Insul. | Earth | Earth Insul. | OD Range | Mass Range |
1.5 mm² | 2C+E-50C+E | 7/0.50 | 0.8 mm | 1.5 mm² | 0.6 mm | 10.6-30.8 mm | 165-1290 kg/km |
2.5 mm² | 2C+E-50C+E | 7/0.67 | 0.8 mm | 2.5 mm² | 0.7 mm | 11.6-35.0 mm | 210-1925 kg/km |
PRODUCT APPLICATIONS
- Commercial building control circuits.
- Industrial plant control and auxiliary circuits.
- Mining systems where the installation route is protected from mechanical damage.
- Electricity-authority and utility control installations.
- Unenclosed fixed installation.
- Conduit installation.
- Direct burial where mechanical damage is not expected.
- Underground ducts.
Request the Complete Data Sheet
From Production to Delivery
From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.
Production
Plain annealed copper conductors are stranded to the specified construction, insulated with PVC V-90, laid up with the required green/yellow earth conductor, and finished with a PVC 5V-90 outer sheath. Conductor size, core count, insulation thickness and cable dimensions follow the approved design.
Inspection
Inspection includes conductor stranding, conductor resistance, insulation condition, earth-core identification, sheath integrity, overall dimensions and finished-cable electrical performance.
Packaging
Finished cables are wound onto suitable drums according to ordered cable size and length. Cable ends are secured and protected, and drum identification can include cable type, conductor size, core configuration, length and project reference.
Shipping
Before shipment, cable drums and accompanying documents are checked against the order and packing list. Product identification, inspection records and technical documentation can be prepared according to customer and project requirements.
Frequently Asked Questions
What conductor construction is used for 1.5 mm²?
7/0.50 mm plain annealed copper.
What conductor construction is used for 2.5 mm²?
7/0.67 mm plain annealed copper.
What is the maximum DC resistance of 1.5 mm²?
13.6 Ω/km at 20°C.
What is the maximum DC resistance of 2.5 mm²?
7.41 Ω/km at 20°C.
What core range is available?
2C+E to 50C+E.