BS 5467 XLPE Insulated Armoured Power Cable
BS 5467 XLPE insulated armoured power cable is designed for fixed power distribution in buildings and industrial installations. With copper conductors, XLPE insulation and a PVC sheath, the range covers 600/1000 V and 1900/3300 V designs. Single-core cables use aluminium wire armour; multicore cables use steel wire armour. Send AMPO your cable schedule to discuss the construction and supply requirements for your project.
- Wire armour helps protect the cable where the route presents a risk of mechanical damage.
- Single-core and multicore options suit different circuit arrangements.
- Two voltage ratings allow the cable specification to match the distribution system.
Product Overview
The construction places cross-linked polyethylene (XLPE) insulation around each conductor, with PVC bedding beneath the wire armour and a PVC outer sheath over it. The insulation provides electrical separation, while the armour and sheath protect the cable during fixed installation and service. This is a power cable for permanent wiring, not a flexible lead for equipment that moves repeatedly.
The copper range includes single-core and two- to five-core power cables at 0.6/1 kV, and single-core or three-core cables at 1.9/3.3 kV. Specify the voltage rating, conductor cross-section and number of cores together: the same nominal cross-section does not make different cable constructions interchangeable. For a purchase order, agree the applicable BS 5467 edition and the final technical data sheet.
Key Features
- Thermosetting insulation: XLPE supports a maximum continuous conductor temperature of 90°C. The permissible circuit load still depends on installation conditions and the temperature limits of connected equipment.
- Armour matched to the circuit: non-magnetic aluminium wire armour (AWA) is used for single-core AC cables; steel wire armour (SWA) protects multicore constructions.
- Layered mechanical protection: PVC bedding separates the insulated assembly from the armour, and the outer PVC sheath covers the armour. This does not make the cable suitable for every chemical or permanently submerged environment.
- Defined conductor construction: stranded copper conductors are specified as Class 2 to IEC 60228. Confirm round or shaped construction against the selected size and core arrangement.
Product Applications
- Building distribution feeders: fixed connections between main switchgear and distribution boards where the route requires an armoured cable.
- Industrial power circuits: fixed supplies to motor control centres, pumps and other stationary plant, using the voltage rating specified for the circuit.
- Outdoor and underground distribution: fixed runs between buildings or equipment, including direct burial where soil conditions, drainage and the installation design are suitable.
Technical Specifications
Single-core 600/1000V cables with circular stranded copper conductor
| Nominal Cross-sectional Area | Strand Type | Nominal Insulation thickness | Nominal Bedding thickness | Nominal Alum Wire dia. | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight |
|---|---|---|---|---|---|---|---|
| mm² | No./mm | mm | mm | mm | mm | mm | kg/km |
| 1x50 | 19/1.78 | 1.0 | 0.8 | 0.9 | 1.5 | 17.5 | 800 |
| 1x70 | 19/2.14 | 1.1 | 0.8 | 1.25 | 1.5 | 20.2 | 990 |
| 1x95 | 19/2.52 | 1.1 | 0.8 | 1.25 | 1.6 | 22.3 | 1280 |
| 1x120 | 37/2.03 | 1.2 | 0.8 | 1.25 | 1.6 | 24.2 | 1550 |
| 1x150 | 37/2.25 | 1.4 | 1 | 1.6 | 1.7 | 27.4 | 1900 |
| 1x185 | 37/2.52 | 1.6 | 1 | 1.6 | 1.8 | 30.0 | 2320 |
| 1x240 | 61/2.25 | 1.7 | 1 | 1.6 | 1.8 | 32.8 | 2930 |
| 1x300 | 61/2.52 | 1.8 | 1 | 1.6 | 1.9 | 35.6 | 3580 |
| 1x400 | 61/2.85 | 2.0 | 1.2 | 2.0 | 2.0 | 40.5 | 4600 |
| 1x500 | 61/3.20 | 2.2 | 1.2 | 2.0 | 2.1 | 44.2 | 5680 |
| 1x630 | 127/2.52 | 2.4 | 1.2 | 2.0 | 2.2 | 48.8 | 7160 |
| 1x800 | 127/2.85 | 2.6 | 1.4 | 2.5 | 2.4 | 55.4 | 9315 |
| 1x1000 | 127/3.20 | 2.8 | 1.4 | 2.5 | 2.5 | 60.6 | 11490 |
Single-core 600/1000V cables with solid aluminum conductor
| Nominal Cross-sectional Area | Nominal Insulation thickness | Nominal Bedding thickness | Nominal Alum Wire Armor dia. | Armour strip | Nominal Sheath thickness | Approx.Overall Diameter | Aprrox Weight | ||
|---|---|---|---|---|---|---|---|---|---|
| thickness | width | wire armor | strip armor | ||||||
| mm^2 | mm | mm | mm | mm | mm | mm | mm | mm | kg/km |
| 1x50 | 1.0 | 0.8 | 0.9 | 0.6 | 2.4 | 1.5 | 16.3 | 15.7 | 460 |
| 1x70 | 1.1 | 0.8 | 1.25 | 0.6 | 2.4 | 1.5 | 18.7 | 17.4 | 560 |
| 1x95 | 1.1 | 0.8 | 1.25 | 0.6 | 2.4 | 1.6 | 20.6 | 19.3 | 690 |
| 1x120 | 1.2 | 0.8 | 1.25 | 0.6 | 2.4 | 1.6 | 22.1 | 20.8 | 800 |
| 1x150 | 1.4 | 1 | 1.6 | 0.6 | 2.4 | 1.7 | 25.2 | 23.2 | 970 |
| 1x185 | 1.6 | 1 | 1.6 | 0.6 | 2.4 | 1.8 | 27.4 | 25.4 | 1150 |
| 1x240 | 1.7 | 1 | 1.6 | 1 | 3.6 | 1.8 | 29.9 | 28.7 | 1380 |
| 1x300 | 1.8 | 1 | 1.6 | 1 | 3.6 | 1.9 | 32.4 | 31.2 | 1640 |
Two-core 600/1000V cables with stranded copper conductors
| Nominal Cross-sectional Area | Strand Type | Nominal Insulation thick-ness | Nominal Bedding thickness | Nominal Steel Wire Armor dia. | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight | |
|---|---|---|---|---|---|---|---|---|
| Extruded bedding | Taped bedding | |||||||
| mm^2 | No./mm | mm | mm | mm | mm | mm | mm | kg/km |
| 2x1.5 | 7/0.53 | 0.6 | 0.8 | 0.9 | 1.4 | 12.1 | - | 320 |
| 2x2.5 | 7/0.67 | 0.7 | 0.8 | 0.9 | 1.4 | 13.6 | - | 365 |
| 2x4 | 7/0.85 | 0.7 | 0.8 | 0.9 | 1.4 | 14.7 | - | 440 |
| 2x6 | 7/1.04 | 0.7 | 0.8 | 0.9 | 1.4 | 15.9 | - | 470 |
| 2x10 | 7/1.35 | 0.7 | 0.8 | 0.9 | 1.5 | 18.0 | - | 800 |
| 2x16 | 7/1.70 | 0.7 | 0.8 | 1.25 | 1.5 | 20.4 | 20.4 | 900 |
| 2x25 | 7/2.14 | 0.9 | 0.8 | 1.25 | 1.6 | 24.1 | 24.1 | 1240 |
| 2x25* | 7/2.14 | 0.9 | 0.8 | 1.25 | 1.6 | 20.4 | 20.4 | 1240 |
| 2x35 | 7/2.52 | 0.9 | 1 | 1.6 | 1.7 | 27.7 | 27.3 | 1710 |
| 2x35* | 7/2.52 | 0.9 | 1 | 1.6 | 1.7 | 23.3 | 22.9 | 1710 |
| 2x50* | 19/1.78 | 1.0 | 1 | 1.6 | 1.8 | 25.8 | 25.4 | 1800 |
| 2x70* | 19/2.14 | 1.1 | 1 | 1.6 | 1.9 | 29.0 | 28.6 | 2320 |
| 2x95* | 19/2.52 | 1.1 | 1.2 | 2.0 | 2.0 | 33.1 | 32.3 | 3150 |
| 2x120* | 37/2.03 | 1.2 | 1.2 | 2.0 | 2.1 | 36.1 | 35.3 | 3880 |
| 2x150* | 37/2.25 | 1.4 | 1.2 | 2.0 | 2.2 | 39.3 | 38.5 | 4820 |
| 2x185* | 37/2.52 | 1.6 | 1.4 | 2.5 | 2.4 | 44.7 | 43.5 | 5920 |
| 2x240* | 61/2.25 | 1.7 | 1.4 | 2.5 | 2.5 | 49.0 | 47.8 | 7300 |
| 2x300* | 61/2.52 | 1.8 | 1.6 | 2.5 | 2.6 | 53.5 | 51.9 | 8770 |
| 2x400* | 61/2.85 | 2 | 1.6 | 2.5 | 2.8 | 59.0 | 57.4 | 10905 |
Two-core 600/1000V cables with solid aluminum conductors
| Nominal Cross-sectional Area | Nominal Insulation thickness | Nominal Bedding thickness | Nominal Steel Wire Armor dia. | Armour strip | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight | |||
|---|---|---|---|---|---|---|---|---|---|---|
| thick-ness | width | wire armor | strip armor | |||||||
| Extruded bedding | Taped bedding | |||||||||
| mm^2 | mm | mm | mm | mm | mm | mm | mm | mm | mm | kg/km |
| 2x16 | 0.7 | 0.8 | 1.25 | 0.6 | 2.4 | 1.5 | 19.1 | 19.1 | 17.8 | 650 |
| 2x25 | 0.9 | 0.8 | 1.25 | 0.6 | 2.4 | 1.5 | 22.4 | 22.4 | 21.1 | 915 |
| 2x25* | 0.9 | 0.8 | 1.25 | 0.6 | 2.4 | 1.6 | 18.7 | 18.7 | 17.4 | 1255 |
| 2x35 | 0.9 | 1 | 1.6 | 0.6 | 2.4 | 1.6 | 25.7 | 25.3 | 23.3 | 1255 |
| 2x35* | 0.9 | 1 | 1.6 | 0.6 | 2.4 | 1.7 | 21.4 | 21.0 | 19 | 1430 |
| 2x50* | 1.0 | 1 | 1.6 | 0.6 | 2.4 | 1.8 | 23.5 | 23.1 | 21.1 | 1430 |
| 2x70* | 1.1 | 1 | 1.6 | 1 | 3.6 | 1.9 | 26.3 | 25.9 | 24.7 | 1780 |
| 2x95* | 1.1 | 1.2 | 2.0 | 1 | 3.6 | 2 | 30 | 29.2 | 27.2 | 1950 |
Three-core 600/1000V cables with stranded copper conductors
| Nominal Cross-sectional Area | Strand Type | Nominal Insulation thickness | Nominal Bedding thickness | Nominal Steel Wire Armor dia. | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight | |
|---|---|---|---|---|---|---|---|---|
| Extruded bedding | Taped bedding | |||||||
| mm^2 | No./mm | mm | mm | mm | mm | mm | mm | kg/km |
| 3x1.5 | 7/0.53 | 0.6 | 0.8 | 0.9 | 1.3 | 12.6 | - | 340 |
| 3x2.5 | 7/0.67 | 0.7 | 0.8 | 0.9 | 1.4 | 14.1 | - | 408 |
| 3x4 | 7/0.85 | 0.7 | 0.8 | 0.9 | 1.4 | 15.3 | - | 498 |
| 3x6 | 7/1.04 | 0.7 | 0.8 | 0.9 | 1.4 | 16.6 | - | 600 |
| 3x10 | 7/1.35 | 0.7 | 0.8 | 1.25 | 1.5 | 19.5 | - | 915 |
| 3x16 | 7/1.70 | 0.7 | 0.8 | 1.25 | 1.6 | 21.6 | 21.6 | 1130 |
| 3x25 | 7/2.14 | 0.9 | 1 | 1.6 | 1.7 | 26.7 | 26.3 | 1710 |
| 3x25* | 7/2.14 | 0.9 | 1 | 1.6 | 1.7 | 23.6 | 23.2 | 1710 |
| 3x35 | 7/2.52 | 0.9 | 1 | 1.6 | 1.8 | 29.4 | 29.0 | 2100 |
| 3x35* | 7/2.52 | 0.9 | 1 | 1.6 | 1.8 | 25.7 | 25.3 | 2100 |
| 3x50* | 19/1.78 | 1.0 | 1 | 1.6 | 1.8 | 28.5 | 28.1 | 2450 |
| 3x70* | 19/2.14 | 1.1 | 1 | 1.6 | 1.9 | 32.2 | 31.8 | 3120 |
| 3x95* | 19/2.52 | 1.1 | 1.2 | 2.0 | 2.1 | 37.0 | 36.2 | 4310 |
| 3x120* | 37/2.03 | 1.2 | 1.2 | 2.0 | 2.2 | 40.4 | 39.6 | 5160 |
| 3x150* | 37/2.25 | 1.4 | 1.4 | 2.5 | 2.3 | 45.5 | 44.3 | 7160 |
| 3x185* | 37/2.52 | 1.6 | 1.4 | 2.5 | 2.4 | 49.8 | 48.6 | 8600 |
| 3x240* | 61/2.25 | 1.7 | 1.4 | 2.5 | 2.6 | 55.1 | 53.9 | 10755 |
| 3x300* | 61/2.52 | 1.8 | 1.6 | 2.5 | 2.7 | 60.2 | 58.6 | 13080 |
| 3x400* | 61/2.85 | 2 | 1.6 | 2.5 | 2.9 | 66.6 | 65.0 | 15810 |
Three-core 600/1000V cables with solid aluminum conductors
| Nominal Cross-sectional Area | Nominal Insulation thickness | Nominal Bedding thickness | Nominal Steel Wire Armor dia. | Armour strip | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight | ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| thick-ness | width | wire armor | strip armor | ||||||||||
| Extruded bedding | Taped bedding | ||||||||||||
| mm^2 | mm | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | |||
| 3x16 | 0.7 | 0.8 | 1.25 | 0.6 | 2.4 | 1.6 | 20.3 | 20.3 | 19 | 760 | |||
| 3x25* | 0.9 | 1 | 1.6 | 0.6 | 2.4 | 1.7 | 22.5 | 22.1 | 20.1 | 1020 | |||
| 3x25 | 0.9 | 1 | 1.6 | 0.6 | 2.4 | 1.7 | 24.9 | 24.5 | 22.5 | 1020 | |||
| 3x35* | 0.9 | 1 | 1.6 | 0.6 | 2.4 | 1.8 | 24.4 | 24.9 | 22 | 1200 | |||
| 3x35 | 0.9 | 1 | 1.6 | 0.6 | 2.4 | 1.8 | 27.3 | 26.9 | 24.9 | 1200 | |||
| 3x50* | 1.0 | 1 | 1.6 | 0.6 | 2.4 | 1.8 | 26.8 | 26.4 | 24.9 | 1380 | |||
| 3x70* | 1.1 | 1 | 1.6 | 1 | 3.6 | 1.9 | 30.2 | 29.8 | 28.6 | 1750 | |||
| 3x95* | 1.1 | 1.2 | 2.0 | 1 | 3.6 | 2.1 | 34.8 | 34.0 | 32 | 2420 | |||
| 3x120* | 1.2 | 1.2 | 2.0 | 1.4 | 4.8 | 2.2 | 37.8 | 37.0 | 35.8 | 2820 | |||
| 3x150* | 1.4 | 1.4 | 2.5 | 1.4 | 4.8 | 2.3 | 42.7 | 41.5 | 39.3 | 3660 | |||
| 3x185* | 1.6 | 1.4 | 2.5 | 1.4 | 4.8 | 2.4 | 46.7 | 45.5 | 43.3 | 4350 | |||
| 3x240* | 1.7 | 1.4 | 2.5 | 1.4 | 4.8 | 2.6 | 51.5 | 50.3 | 48.1 | 5220 | |||
| 3x300* | 1.8 | 1.6 | 2.5 | 1.8 | 6.4 | 2.7 | 56.2 | 54.6 | 53.2 | 6200 | |||
| Four-core 600/1000V cables with stranded copper conductors | |||||||||||||
Four-core 600/1000V cables with stranded copper conductors
| Nominal Cross-sectional Area | Strand Type | Nominal Insulation thickness | Nominal Bedding thickness | Nominal Steel Wire Armor dia. | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight | |
|---|---|---|---|---|---|---|---|---|
| Extruded bedding | Taped bedding | |||||||
| mm^2 | No./mm | mm | mm | mm | mm | mm | mm | kg/km |
| 4x1.5 | 7/0.53 | 0.7 | 0.8 | 0.9 | 1.4 | 13.3 | - | 390 |
| 4x2.5 | 7/0.67 | 0.7 | 0.8 | 0.9 | 1.4 | 15.0 | - | 470 |
| 4x4 | 7/0.85 | 0.7 | 0.8 | 0.9 | 1.4 | 16.4 | - | 580 |
| 4x6 | 7/1.04 | 0.7 | 0.8 | 1.25 | 1.5 | 18.7 | - | 805 |
| 4x10 | 7/1.35 | 0.7 | 0.8 | 1.25 | 1.5 | 21.1 | - | 1090 |
| 4x16 | 7/1.70 | 0.7 | 0.8 | 1.25 | 1.6 | 23.4 | 23.4 | 1320 |
| 4x25 | 7/2.14 | 0.9 | 1 | 1.6 | 1.7 | 28.9 | 28.5 | 1840 |
| 4x25* | 7/2.14 | 0.9 | 1 | 1.6 | 1.7 | 26.1 | 25.7 | 1840 |
| 4x35 | 7/2.52 | 0.9 | 1 | 1.6 | 1.8 | 31.9 | 31.5 | 2310 |
| 4x35* | 7/2.52 | 0.9 | 1 | 1.6 | 1.8 | 28.6 | 28.2 | 2310 |
| 4x50* | 19/1.78 | 1.0 | 1 | 1.6 | 1.9 | 32.0 | 31.6 | 2970 |
| 4x70* | 19/2.14 | 1.1 | 1.2 | 2.0 | 2.1 | 37.7 | 36.9 | 4240 |
| 4x95* | 19/2.52 | 1.1 | 1.2 | 2.0 | 2.2 | 41.7 | 40.9 | 5400 |
| 4x120* | 37/2.03 | 1.2 | 1.4 | 2.5 | 2.3 | 47.1 | 45.9 | 7000 |
| 4x150* | 37/2.25 | 1.4 | 1.4 | 2.5 | 2.4 | 51.4 | 50.2 | 8350 |
| 4x185* | 37/2.52 | 1.6 | 1.4 | 2.5 | 2.6 | 56.6 | 55.4 | 10130 |
| 4x240* | 61/2.25 | 1.7 | 1.6 | 2.5 | 2.7 | 63.0 | 61.4 | 12840 |
| 4x300* | 61/2.52 | 1.8 | 1.6 | 2.5 | 2.9 | 68.8 | 67.2 | 15530 |
| 4x400* | 61/2.85 | 2 | 1.8 | 3.15 | 3.2 | 78.1 | 76.1 | 19950 |
Four-core 600/1000V cables with solid aluminum conductors
| Nominal Cross-sectional Area | Nominal Insulation thickness | Nominal Bedding thickness | Nominal Steel Wire Armor dia. | Armour strip | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight | ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| thick-ness | width | wire armor | strip armor | ||||||||||
| Extruded bedding | Taped bedding | ||||||||||||
| mm^2 | mm | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | |||
| 4x16 | 0.7 | 0.8 | 1.25 | 0.6 | 2.4 | 1.6 | 21.8 | 21.8 | 20.5 | 980 | |||
| 4x25 | 0.9 | 1 | 1.6 | 0.6 | 2.4 | 1.7 | 26.9 | 26.5 | 24.5 | 1220 | |||
| 4x25* | 0.9 | 1 | 1.6 | 0.6 | 2.4 | 1.7 | 24.6 | 24.2 | 22.2 | 1220 | |||
| 4x35 | 0.9 | 1 | 1.6 | 0.6 | 2.4 | 1.8 | 29.5 | 29.2 | 27.1 | 1420 | |||
| 4x35* | 0.9 | 1 | 1.6 | 0.6 | 2.4 | 1.8 | 27 | 26.6 | 24.6 | 1420 | |||
| 4x50* | 1.0 | 1 | 1.6 | 1 | 2.4 | 1.9 | 30 | 29.6 | 28.4 | 1770 | |||
| 4x70* | 1.1 | 1.2 | 2.0 | 1 | 3.6 | 2.1 | 35.3 | 34.5 | 32.5 | 2500 | |||
| 4x95* | 1.1 | 1.2 | 2.0 | 1.4 | 3.6 | 2.2 | 39 | 38.2 | 37 | 2980 | |||
| 4x120* | 1.2 | 1.4 | 2.5 | 1.4 | 4.8 | 2.3 | 44 | 42.8 | 40.6 | 3950 | |||
| 4x150* | 1.4 | 1.4 | 2.5 | 1.4 | 4.8 | 2.4 | 47.9 | 46.7 | 44.5 | 4600 | |||
| 4x185* | 1.6 | 1.4 | 2.5 | 1.4 | 4.8 | 2.6 | 52.7 | 51.5 | 49.3 | 5430 | |||
| 4x240* | 1.7 | 1.6 | 2.5 | 1.8 | 4.8 | 2.7 | 58.5 | 56.9 | 55.5 | 6660 | |||
| 4x300* | 1.8 | 1.6 | 2.5 | 1.8 | 6.4 | 2.9 | 63.8 | 62.2 | 60.8 | 7770 | |||
| Five-core 600/1000 V cables with stranded copper conductors | |||||||||||||
Five-core 600/1000V cables with stranded copper conductors
| Nominal Cross-sectional Area | Strand Type | Nominal Insulation thickness | Nominal Bedding thickness | Nominal Steel Wire Armor dia. | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight | |
|---|---|---|---|---|---|---|---|---|
| Extruded bedding | Taped bedding | |||||||
| mm^2 | No./mm | mm | mm | mm | mm | mm | mm | kg/km |
| 5x1.5 | 7/0.53 | 0.6 | 0.8 | 0.9 | 1.4 | 14.3 | - | 430 |
| 5x2.5 | 7/0.67 | 0.7 | 0.8 | 0.9 | 1.4 | 16.1 | - | 545 |
| 5x4 | 7/0.85 | 0.7 | 0.8 | 0.9 | 1.5 | 17.8 | - | 680 |
| 5x6 | 7/1.04 | 0.7 | 0.8 | 1.25 | 1.5 | 20 | - | 840 |
| 5x10 | 7/1.35 | 0.7 | 0.8 | 1.25 | 1.6 | 22.9 | - | 1105 |
| 5x16 | 7/1.70 | 0.7 | 1 | 1.6 | 1.7 | 26.6 | 26.2 | 1450 |
| 5x25 | 7/2.14 | 0.9 | 1 | 1.6 | 1.8 | 31.5 | 31.1 | 2245 |
| 5x35 | 7/2.52 | 0.9 | 1 | 1.6 | 1.9 | 34.8 | 34.4 | 2840 |
| 5x50 | 19/1.78 | 1.0 | 1.2 | 2 | 2 | 40.4 | 39.6 | 3895 |
| 5x70 | 19/2.14 | 1.1 | 1.2 | 2 | 2.2 | 46.3 | 45.5 | 5145 |
Multi-core 600/1000V cables with stranded copper conductors
| Nominal Cross-sectional Area | Strand Type | Nominal Insulation thickness | Nominal Bedding thickness | Nominal Steel Wire Armor dia. | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight |
|---|---|---|---|---|---|---|---|
| mm^2 | No./mm | mm | mm | mm | mm | mm | kg/km |
| 7x1.5 | 7/0.53 | 0.6 | 0.8 | 0.9 | 1.4 | 15.2 | 500 |
| 12x1.5 | 7/0.53 | 0.6 | 0.8 | 1.25 | 1.5 | 19.4 | 820 |
| 19x1.5 | 7/0.53 | 0.6 | 0.8 | 1.25 | 1.6 | 22.2 | 1080 |
| 27x1.5 | 7/0.53 | 0.6 | 1 | 1.6 | 1.7 | 26.7 | 1550 |
| 37x1.5 | 7/0.53 | 0.6 | 1 | 1.6 | 1.7 | 29 | 1850 |
| 48x1.5 | 7/0.53 | 0.6 | 1 | 1.6 | 1.8 | 32.7 | 2250 |
| 7x2.5 | 7/0.67 | 0.7 | 0.8 | 0.9 | 1.4 | 17.1 | 730 |
| 12x2.5 | 7/0.67 | 0.7 | 0.8 | 1.25 | 1.6 | 22.4 | 1020 |
| 19x2.5 | 7/0.67 | 0.7 | 1 | 1.6 | 1.7 | 26.6 | 1530 |
| 27x2.5 | 7/0.67 | 0.7 | 1 | 1.6 | 1.8 | 30.7 | 1960 |
| 37x2.5 | 7/0.67 | 0.7 | 1 | 1.6 | 1.8 | 33.8 | 2450 |
| 48x2.5 | 7/0.67 | 0.7 | 1.2 | 2 | 2 | 39.3 | 3260 |
| 7x4 | 7/0.85 | 0.7 | 0.8 | 1.25 | 1.5 | 19.7 | 840 |
| 12x4 | 7/0.85 | 0.7 | 1 | 1.6 | 1.6 | 25.7 | 1390 |
| 19x4 | 7/0.85 | 0.7 | 1 | 1.6 | 1.7 | 29.3 | 1850 |
| 27x4 | 7/0.85 | 0.7 | 1 | 1.6 | 1.9 | 34.4 | 2350 |
| 37x4 | 7/0.85 | 0.7 | 1.2 | 2 | 2 | 39.2 | 2800 |
| 48x4 | 7/0.85 | 0.7 | 1.2 | 2 | 2.1 | 44.1 | 3250 |
Single-core 1900/3300V cables with circular stranded copper conductor
| Nominal Cross-sectional Area | Strand Type | Nominal Insulation thickness | Nominal Bedding thickness | Nominal Alum Wire Armor dia. | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight |
|---|---|---|---|---|---|---|---|
| mm^2 | No./mm | mm | mm | mm | mm | mm | kg/km |
| 1x50 | 19/1.78 | 2 | 0.8 | 1.25 | 1.6 | 20.6 | 790 |
| 1x70 | 19/2.14 | 2 | 0.8 | 1.25 | 1.6 | 22.4 | 1040 |
| 1x95 | 19/2.52 | 2 | 0.8 | 1.25 | 1.6 | 24.3 | 1330 |
| 1x120 | 37/2.03 | 2 | 1 | 1.6 | 1.7 | 27.2 | 1680 |
| 1x150 | 37/2.25 | 2 | 1 | 1.6 | 1.7 | 28.8 | 1970 |
| 1x185 | 37/2.52 | 2 | 1 | 1.6 | 1.8 | 30.8 | 2370 |
| 1x240 | 61/2.25 | 2 | 1 | 1.6 | 1.8 | 33.5 | 2960 |
| 1x300 | 61/2.52 | 2 | 1 | 1.6 | 1.9 | 36.1 | 3610 |
| 1x400 | 61/2.85 | 2 | 1.2 | 2 | 2 | 40.5 | 4600 |
| 1x500 | 61/3.20 | 2.2 | 1.2 | 2 | 2.1 | 44.2 | 5680 |
| 1x630 | 127/2.52 | 2.4 | 1.2 | 2 | 2.2 | 48.8 | 7160 |
| 1x800 | 127/2.85 | 2.6 | 1.4 | 2.5 | 2.4 | 55.4 | 9150 |
| 1x1000 | 127/3.20 | 2.8 | 1.4 | 2.5 | 2.5 | 60.6 | 11270 |
Single-core 1900/3300V cables with solid aluminum conductor
| Nominal Cross-sectional Area | Nominal Insulation thickness | Nominal bedding thickness | Nominal Alum Wire Armor dia. | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight |
|---|---|---|---|---|---|---|
| mm | mm | mm | mm | mm | mm | kg/km |
| 1x50 | 2 | 0.8 | 1.25 | 1.6 | 19.4 | 600 |
| 1x70 | 2 | 0.8 | 1.25 | 1.6 | 20.9 | 710 |
| 1x95 | 2 | 0.8 | 1.25 | 1.6 | 22.5 | 810 |
| 1x120 | 2 | 1 | 1.6 | 1.7 | 25.2 | 1065 |
| 1x150 | 2 | 1 | 1.6 | 1.7 | 26.5 | 1210 |
| 1x185 | 2 | 1 | 1.6 | 1.8 | 28.3 | 1390 |
| 1x240 | 2 | 1 | 1.6 | 1.8 | 30.5 | 1630 |
| 1x300 | 2 | 1 | 1.6 | 1.9 | 32.8 | 1900 |
Three-core 1900/3300V cables with stranded copper conductors
| Nominal Cross-sectional Area | Strand Type | Nominal Insulation thickness | Nominal Bedding thickness | Nominal Steel Wire Armor dia. | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight |
|---|---|---|---|---|---|---|---|
| mm | No./mm | mm | mm | mm | mm | mm | kg/km |
| 3x16 | 7/1.70 | 2 | 1 | 1.6 | 1.8 | 29.3 | 1600 |
| 3x25 | 7/2.14 | 2 | 1 | 1.6 | 1.8 | 32.2 | 2060 |
| 3x35 | 7/2.52 | 2 | 1 | 1.6 | 1.9 | 34.8 | 2400 |
| 3x35* | 7/2.52 | 2 | 1 | 1.6 | 1.9 | 31.1 | 2400 |
| 3x50* | 19/1.78 | 2 | 1.2 | 2 | 2 | 34.7 | 3200 |
| 3x70* | 19/2.14 | 2 | 1.2 | 2 | 2.1 | 38 | 3800 |
| 3x95* | 19/2.52 | 2 | 1.2 | 2 | 2.2 | 41.4 | 4730 |
| 3x120* | 37/2.03 | 2 | 1.4 | 2.5 | 2.3 | 45.7 | 6070 |
| 3x150* | 37/2.25 | 2 | 1.4 | 2.5 | 2.4 | 48.5 | 7010 |
| 3x185* | 37/2.52 | 2 | 1.4 | 2.5 | 2.5 | 51.9 | 8270 |
| 3x240* | 61/2.25 | 2 | 1.6 | 2.5 | 2.6 | 56.9 | 10310 |
| 3x300* | 61/2.52 | 2 | 1.6 | 2.5 | 2.7 | 61.2 | 12300 |
| 3x400* | 61/2.85 | 2 | 1.6 | 2.5 | 2.9 | 66.6 | 14500 |
Three-core 1900/3300V cables with solid aluminum conductors
| Nominal Cross-sectional Area | Nominal Insulation thickness | Nominal Bedding thickness | Nominal Steel Wire Armor dia. | Nominal Sheath thickness | Approx. Overall Diameter | Aprrox Weight |
|---|---|---|---|---|---|---|
| mm | mm | mm | mm | mm | mm | kg/km |
| 3x16 | 2 | 1 | 1.6 | 1.8 | 27.9 | 1540 |
| 3x25 | 2 | 1 | 1.6 | 1.8 | 30.4 | 1780 |
| 3x35 | 2 | 1 | 1.6 | 1.9 | 32.7 | 2040 |
| 3x35* | 2 | 1 | 1.6 | 1.9 | 29.7 | 2040 |
| 3x50* | 2 | 1.2 | 2 | 2 | 33 | 2760 |
| 3x70* | 2 | 1.2 | 2 | 2.1 | 36 | 3210 |
| 3x95* | 2 | 1.2 | 2 | 2.2 | 39.1 | 3625 |
| 3x120* | 2 | 1.4 | 2.5 | 2.3 | 43.1 | 4820 |
| 3x150* | 2 | 1.4 | 2.5 | 2.4 | 45.6 | 5410 |
| 3x185* | 2 | 1.4 | 2.5 | 2.5 | 48.7 | 6070 |
| 3x240* | 2 | 1.6 | 2.5 | 2.6 | 53.2 | 7150 |
| 3x300* | 2 | 1.6 | 2.5 | 2.7 | 57.2 | 8120 |
Request the Complete Data Sheet
From Production to Delivery
From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.
Production
Stranded annealed copper conductors are insulated with XLPE, assembled into the required multicore configuration, optionally filled and bound with polyester tape, then covered with the specified black PVC sheath.
Inspection
Inspection focuses on conductor construction, insulation condition, core identification, sheath integrity, overall diameter, conductor resistance and test-voltage requirements against the approved technical schedule.
Packaging
Finished cable is wound on suitable drums according to ordered size, weight and length. Cable ends are protected and drum identification can include cable type, conductor size, core count, length and project reference.
Shipping
Before shipment, cable drums and technical documents are checked against the order. Inspection records, identification data and requested test documentation can be prepared for the customer.
Frequently Asked Questions
Which voltage rating should I specify for my project?
Specify 600/1000 V (0.6/1 kV) or 1900/3300 V (1.9/3.3 kV) to match the circuit design. In the designation U₀/U, U₀ is the rated voltage between conductor and earth, and U is the rated voltage between conductors. The designer must also consider the system earthing arrangement and fault conditions; the two ratings are not interchangeable ordering descriptions.
Why do single-core cables use AWA rather than SWA?
An AC current in a single-core cable produces a magnetic field around that cable. Non-magnetic aluminium armour avoids the additional ferromagnetic losses associated with steel armour in this arrangement. It does not eliminate all induced voltages or circulating currents. Cable formation, armour bonding and earthing still require an engineered design.
Can this cable be buried directly or installed in wet ground?
Direct burial can be suitable when the selected cable and installation design match the site conditions. Confirm burial depth, bedding, mechanical protection, soil thermal resistivity and drainage. A PVC sheath is not, by itself, evidence of suitability for permanent immersion, waterlogged ground or chemically contaminated soil. Tell us about these conditions before the cable is selected.
Is BS 5467 cable low smoke zero halogen or fire resistant?
The PVC-sheathed construction described here is not low smoke zero halogen (LSZH). If the project requires reduced smoke and corrosive gas emissions, assess a suitable BS 6724 cable against the fire specification. Flame propagation performance is also different from maintaining circuit operation during a fire; any fire-resistance requirement needs a separately verified cable design and test evidence.
How do I choose the conductor size and current rating?
Start with the design current, circuit length, permissible voltage drop and prospective fault current. Then check the laying method, ambient or ground temperature, grouping and soil conditions. A 90°C conductor temperature limit is not a universal current rating. Use installation-specific calculations and check termination temperature limits before approving the cross-section.