BS 7629-1 SR Insulated Fire Resistant Control Cable 300/500V

BS 7629-1 SR Insulated Fire Resistant Control Cable is a 300/500V copper control cable designed for emergency services and fire-circuit control. It uses solid Class 1 plain annealed copper conductors, fire-resistant silicone-rubber insulation and a low-smoke zero-halogen outer sheath, with 2-, 3- and 4-core constructions available.

PRODUCT OVERVIEW

The cable is basically designed to BS 7629-1 for fixed fire-resistant control circuits. Plain annealed copper conductors are solid to IEC/EN 60228 Class 1 and insulated with fire-resistant silicone-rubber compound type EI2. The insulated cores are cabled together in concentric layers with suitable non-hygroscopic fillers and finished with a thermoplastic LSZH outer sheath type LTS3; a thermosetting LSZH compound type SW2-SW4 can also be offered.

The listed range covers 2-, 3- and 4-core designs in 1.5 mm² and 2.5 mm² conductor sizes, including versions with and without an earth conductor. The product is intended for emergency-service and fire-circuit control applications where circuit integrity, low smoke, halogen-free materials and defined fire-performance characteristics are required.

KEY FEATURES

  • Basic design to BS 7629-1.
  • 300/500V rated voltage.
  • Plain annealed copper conductor, solid IEC/EN 60228 Class 1.
  • Fire-resistant silicone-rubber insulation type EI2.
  • Thermoplastic LSZH outer sheath type LTS3; thermosetting SW2-SW4 can be offered.
  • 2-, 3- and 4-core constructions.
  • Available conductor sizes: 1.5 mm² and 2.5 mm².
  • Operating temperature: -30°C to +90°C.
  • Installation temperature: -20°C to +50°C.
  • Minimum bending radius: 6 × overall diameter.

STANDARD & FIRE PERFORMANCE

BS 7629-1 is the basic design standard for this cable. The fire-performance references below describe the circuit-integrity, mechanical-shock, water-spray, flame-spread, halogen and smoke characteristics listed for the product.

Performance

Referenced Test / Standard

Circuit integrity

IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814 (FE180); BS 8434-1 (30 min); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS229-1; NBN C 30-004 (F3); NF C32-070-2.3 (CR1)

Circuit integrity with mechanical shock

EN 50200 (PH60); CEI 20-36/4-0

Circuit integrity with mechanical shock & water spray

EN 50200 Annex E

System circuit integrity

DIN 4102-12, E30 depending on lay system

Flame retardance – single vertical wire

EN/IEC/BS EN 60332-1-2 and listed equivalents

Reduced fire propagation – bundled cables

EN/IEC/BS EN 60332-3-24 (Cat. C) and listed equivalents

Halogen free

IEC 60754-1 and listed equivalents

No corrosive gas emission

IEC 60754-2 and listed equivalents

Minimum smoke emission

IEC 61034-1&2 and listed equivalents

No toxic gases

NES 02-713; NF C 20-454

CABLE CONSTRUCTION

Voltage Rating

300/500V

Conductor

Plain annealed copper, solid IEC/EN 60228 Class 1

Insulation

Fire-resistant silicone-rubber compound type EI2

Cabling

Cores cabled together in concentric layers with suitable non-hygroscopic fillers

Outer Sheath

Thermoplastic LSZH LTS3; optional thermosetting LSZH SW2-SW4

Sheath Colour

Orange; other colours on request

PRODUCT APPLICATIONS

  • Emergency-service control circuits.
  • Fire-circuit control systems.
  • Life-safety control circuits requiring fire-resistant silicone-rubber insulation.
  • Building and infrastructure control circuits requiring LSZH cable.
  • Fixed installations requiring 2-, 3- or 4-core fire-resistant control cable.
No. of Cores × Cross Section Insulation mm Sheath mm Overall Diameter mm Approx. Weight kg/km
2x1.5 0.7 0.9 7.4 70
2x2.5 0.8 1.0 8.8 105
3x1.5 0.7 0.9 7.9 93
3x2.5 0.8 1.0 9.4 141
4x1.5 0.7 1.0 8.8 122
4x2.5 0.8 1.1 10.4 183

Request the Complete Data Sheet

If you need a specific product catalogue or related standard file, please contact us.

From Production to Delivery

From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.

cable production line with finished cable being wound onto a reel

Production

Solid Class 1 plain annealed copper conductors are insulated with fire-resistant silicone rubber, cabled with suitable fillers and finished with the specified LSZH outer sheath.

Cable and conductor quality inspection and testing

Inspection

Inspection focuses on conductor construction, silicone-rubber insulation, core identification, sheath integrity, dielectric test, insulation resistance, overall dimensions and required fire-performance documentation.

Overhead conductors packed on wooden drums for shipment

Packaging

Finished cables are wound onto suitable drums according to ordered size and length. Cable ends are secured and protected, and drum identification can include cable type, conductor size, core count, length and project reference.

Wooden drums of overhead conductors loaded into shipping container

Shipping

Before shipment, cable drums and accompanying technical documents are checked against the order and packing list. Test records, product identification and project documentation can be prepared according to customer requirements.

Frequently Asked Questions

What is the rated voltage?

300/500V.

Solid IEC/EN 60228 Class 1 copper conductors.

Fire-resistant silicone-rubber compound type EI2.

No. This product is an unscreened SR insulated fire-resistant control cable.

2, 3 and 4 cores.

6 times the overall cable diameter.

Request for Free Consultation

Contact Information

Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.

Explore More

Related Products
Cast Resin T-Joint for Low-Voltage Cable Branching
Gel Straight-Through Cable Joint for Low Voltage Power Cables
Cast Resin Straight-Through Joint for Low Voltage Power Cables
Compatible Hardware
Cast Resin T-Joint for Low-Voltage Cable Branching
Gel Straight-Through Cable Joint for Low Voltage Power Cables
Cast Resin Straight-Through Joint for Low Voltage Power Cables
Knowledge Articles
Customer Visits Our Factory for Product Inspection and Quality Verification
AAAC all aluminium alloy conductor stranded wire
AAAC Conductor Selection Guide: How to Choose the Right AAAC for Overhead Lines
International Airport Expansion Project in Saudi Arabia

For Immediate Assistance, Please Contact us Now!