Single Core Medium Voltage Power Cable to IEC 60502-2
This single core cable is designed for distribution of electrical power with nominal voltages ranging from 1.8/3kV to 26/35kV and frequency 50Hz. Manufactured in full compliance with IEC 60502, it is suitable for installation in power supply stations, indoors and in cable ducts, outdoors, underground and in water, as well as on cable trays for industries, switchboards and power stations.
Key Advantages
Optional Aluminium Wire Armour
Metallic Screen
Single Core Design
IEC 60502 Part 2(3.6/6KV to 18/30KV)
Construction
| Conductor | Copper or Aluminium conductor, round stranded or Compacted, Class 2 to IEC 60228, BS EN 60228. For smaller sizes, solid conductor, Class 1 as per IEC 60228, BS EN 60228 can also be supplied upon request. |
| Insulation | Insulation is of polyvinyl chloride (PVC) intended for 1.8/3kV and 3.6/6kV Power Cable, cross-linked polyethylene compound (XLPE) or ethylene propylene rubber (EPR/HEPR) |
| Conductor Screen | The conductor screen consists of an extruded layer of non metallic, semi-conducting compound firmly bonded to the insulation to exclude all air voids. The conductor screen is not necessary for both PVC and EPR/HEPR insulated 1.8/3kV and 3.6/6kV Power Cable. |
| Insulation Screen | The insulation screen consists of an extruded layer of non metallic, semi-conducting compound extruded over the insulation. The extruded semi-conducting layer shall consist of bonded or cold strippable semi-conducting compound capable of removal for jointing or terminating. As an option, a semi-conducting tape may be applied over the extruded semi-conducting layer as a bedding for the metallic layer. The minimum thickness is 0.3 mm and the maximum resistivity is 500 Ohm-m at 90°C. The screen is tightly fitted to the insulation to exclude all air voids and can be easily hand stripped on site. The insulation screen is not necessary for both PVC and EPR/HEPR insulated 1.8/3kV and 3.6/6kV Power Cable. The screen may be covered by semi-conductive water blocking swellable tape to ensure longitudinal watertightness. |
| Metallic Layer | The metallic layer may be applied over the individual cores or the core assembly collectively.The following types of metallic layers are provided:1) Metallic Screen2) Concentric Conductor3) Metallic Sheath4) Metallic armor |
| Separation Sheath (for armored cable) | The separation sheath comprises a layer of extruded PVC, PE or LSZH, applied under the armor. The nominal thickness is calculated by 0.02Du + 0.6mm where Du is the fictitious diameter under the sheath in mm. For Power Cable without a lead sheath, the nominal separation sheath thickness shall not be less than 1.2mm. For Power Cable where the separation sheath is applied over the lead sheath, the nominal separation sheath thickness shall not be less than 1.0mm. |
| Lapped Bedding (for armored lead sheathed cable) | The lapped bedding consists of either impregnated/synthetic compounded paper tapes or a combination of two layers of these paper tapes followed by a few layers of compounded fabulous materials. The thickness is around 1.5mm. |
| Armour (for armored cable) | The Armour consists of round aluminum wire armour applied helically over an extruded separation sheath. |
| Over Sheath | Overall sheath comprises a layer of extruded thermoplastic compound (PVC, PE or LSZH can be offered as an option.) or elastomeric compound (polychloroprene CSP or chlorosulfonated PE). The nominal oversheath thickness is calculated by 0.035D+1 where D is the fictitious diameter immediately under the oversheath in mm. For unarmored Power Cable and Power Cable with the oversheath not applied over the armor, metallic screen or concentric conductor, the nominal oversheath thickness shall not be less than 1.4mm. And for Power Cable with oversheath applied over the armor, metallic screen or concentric conductor, the nominal oversheath thickness shall not be less than 1.8mm. |
| Physical Properties | Operating Temperature: up to 70°C (PVC insulation); up to 90°C (XLPE or EPR insulation)Temperature Range: -5°C (PVC sheath); -20°C (PE sheath)Short Circuit Temperature (5 seconds maximum duration): 140-160°C (PVC insulation), 250°C (XLPE or EPR insulation)Bending Radius: 12 × OD |
Parameters
| Nom. Cross-Section Area | Nom. Insulation Thickness | Copper Wire Screen Area | Unarmoured Cables | Aluminium Wire Armoured Cables | |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nom. Bedding Thickness | Armour Wire Size | Nom. Sheath Thickness | Approx. Weight | |||||
| CU | AL | CU | AL | ||||||||
| mm² | mm | mm² | mm | mm | kg/km | mm | mm | mm | kg/km | ||
| 10 | 2.5 | 16 | 1.8 | 16 | 320 | 260 | 1.2 | 1.6 | 1.8 | 610 | 550 |
| 16 | 2.5 | 16 | 1.8 | 16 | 390 | 290 | 1.2 | 1.6 | 1.8 | 680 | 580 |
| 25 | 2.5 | 16 | 1.8 | 18 | 500 | 340 | 1.2 | 1.6 | 1.8 | 810 | 660 |
| 35 | 2.5 | 16 | 1.8 | 19 | 610 | 400 | 1.2 | 1.6 | 1.8 | 940 | 730 |
| 50 | 2.5 | 16 | 1.8 | 20 | 750 | 450 | 1.2 | 1.6 | 1.8 | 1100 | 810 |
| 70 | 2.5 | 16 | 1.8 | 22 | 970 | 550 | 1.2 | 1.6 | 1.8 | 1350 | 930 |
| 95 | 2.5 | 16 | 1.8 | 23 | 1250 | 660 | 1.2 | 1.6 | 1.9 | 1670 | 1080 |
| 120 | 2.5 | 16 | 1.8 | 25 | 1500 | 760 | 1.2 | 1.6 | 1.9 | 1950 | 1200 |
| 150 | 2.5 | 25 | 1.8 | 26 | 1790 | 860 | 1.2 | 1.6 | 2 | 2270 | 1350 |
| 185 | 2.5 | 25 | 1.8 | 28 | 2160 | 1000 | 1.2 | 2 | 2.1 | 2770 | 1620 |
| 240 | 2.6 | 25 | 1.9 | 31 | 2770 | 1250 | 1.2 | 2 | 2.2 | 3440 | 1930 |
| 300 | 2.8 | 25 | 2 | 34 | 3400 | 1500 | 1.2 | 2 | 2.2 | 4120 | 2210 |
| 400 | 3 | 35 | 2.1 | 38 | 4280 | 1850 | 1.3 | 2.5 | 2.4 | 5250 | 2820 |
| 500 | 3.2 | 35 | 2.1 | 41.5 | 5325 | 2240 | 1.4 | 2.5 | 2.6 | 6550 | 3520 |
| 630 | 3.2 | 35 | 2.2 | 45.3 | 6745 | 2750 | 1.5 | 2.5 | 2.7 | 7960 | 4020 |
| 800 | 3.2 | 50 | 2.4 | 49.4 | 8290 | 3310 | 1.5 | 2.5 | 2.8 | 9660 | 4820 |
| 1000 | 3.2 | 50 | 2.5 | 54.2 | 10256 | 3990 | 1.5 | 2.5 | 3 | 11690 | 5540 |
| Nom. Cross-Section Area | Nom. Insulation Thickness | Copper Wire Screen Area | Unarmoured Cables | Aluminium Wire Armoured Cables | |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nom. Bedding Thickness | Armour Wire Size | Nom. Sheath Thickness | Approx. Weight | |||||
| CU | AL | CU | AL | ||||||||
| mm² | mm | mm² | mm | mm | kg/km | mm | mm | mm | kg/km | ||
| 16 | 3.4 | 16 | 1.8 | 18 | 450 | 350 | 1.2 | 1.6 | 1.8 | 770 | 670 |
| 25 | 3.4 | 16 | 1.8 | 20 | 560 | 400 | 1.2 | 1.6 | 1.8 | 910 | 750 |
| 35 | 3.4 | 16 | 1.8 | 21 | 680 | 460 | 1.2 | 1.6 | 1.8 | 1040 | 820 |
| 50 | 3.4 | 16 | 1.8 | 22 | 810 | 520 | 1.2 | 1.6 | 1.8 | 1190 | 900 |
| 70 | 3.4 | 16 | 1.8 | 24 | 1050 | 620 | 1.2 | 1.6 | 1.9 | 1470 | 1040 |
| 95 | 3.4 | 16 | 1.8 | 25 | 1320 | 730 | 1.2 | 1.6 | 2 | 1780 | 1190 |
| 120 | 3.4 | 16 | 1.8 | 27 | 1580 | 840 | 1.2 | 2 | 2 | 2150 | 1410 |
| 150 | 3.4 | 25 | 1.9 | 28 | 1880 | 960 | 1.2 | 2 | 2.1 | 2480 | 1560 |
| 185 | 3.4 | 25 | 1.9 | 30 | 2250 | 1100 | 1.2 | 2 | 2.1 | 2890 | 1730 |
| 240 | 3.4 | 25 | 2 | 33 | 2870 | 1350 | 1.2 | 2 | 2.2 | 3570 | 2050 |
| 300 | 3.4 | 25 | 2.1 | 35 | 3490 | 1580 | 1.2 | 2 | 2.3 | 4230 | 2330 |
| 400 | 3.4 | 35 | 2.2 | 39 | 4350 | 1920 | 1.3 | 2.5 | 2.4 | 5320 | 2890 |
| 500 | 3.4 | 35 | 2.2 | 39.9 | 5325 | 2240 | 1.4 | 2.5 | 2.5 | 6510 | 3530 |
| 630 | 3.4 | 35 | 2.3 | 43.7 | 6675 | 2765 | 1.5 | 2.5 | 2.6 | 7960 | 4050 |
| 800 | 3.4 | 50 | 2.5 | 48.6 | 8225 | 3330 | 1.5 | 2.5 | 2.7 | 9670 | 4850 |
| 1000 | 3.4 | 50 | 2.6 | 52.9 | 10210 | 4030 | 1.6 | 2.5 | 2.9 | 11710 | 5570 |
| Nom. Cross-Section Area | Nom. Insulation Thickness | Unarmoured Cables | Aluminium Wire Armoured Cables | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nom. Bedding Thickness | Armour Wire Size | Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | ||||
| CU | AL | CU | AL | ||||||||
| mm² | mm | mm | mm | kg/km | mm | mm | mm | mm | kg/km | ||
| 25 | 4.5 | 1.8 | 22 | 640 | 480 | 1.2 | 1.6 | 1.8 | 28 | 1020 | 860 |
| 35 | 4.5 | 1.8 | 23 | 760 | 540 | 1.2 | 1.6 | 1.9 | 29 | 1170 | 950 |
| 50 | 4.5 | 1.8 | 24 | 900 | 610 | 1.2 | 1.6 | 1.9 | 30 | 1340 | 1040 |
| 70 | 4.5 | 1.8 | 26 | 1140 | 710 | 1.2 | 1.6 | 2 | 32 | 1610 | 1190 |
| 95 | 4.5 | 1.8 | 27 | 1420 | 830 | 1.2 | 2 | 2.1 | 35 | 2020 | 1430 |
| 120 | 4.5 | 1.9 | 29 | 1700 | 950 | 1.2 | 2 | 2.1 | 36 | 2310 | 1570 |
| 150 | 4.5 | 1.9 | 31 | 1990 | 1070 | 1.2 | 2 | 2.2 | 38 | 2660 | 1740 |
| 185 | 4.5 | 2 | 32 | 2380 | 1230 | 1.2 | 2 | 2.2 | 39 | 3070 | 1920 |
| 240 | 4.5 | 2.1 | 35 | 3010 | 1490 | 1.2 | 2 | 2.3 | 42 | 3750 | 2240 |
| 300 | 4.5 | 2.1 | 37 | 3620 | 1720 | 1.3 | 2.5 | 2.4 | 46 | 4590 | 2690 |
| 400 | 4.5 | 2.2 | 41 | 4490 | 2070 | 1.3 | 2.5 | 2.5 | 49 | 5550 | 3120 |
| 500 | 4.5 | 2.3 | 43 | 5460 | 2460 | 1.3 | 2.5 | 2.6 | 52 | 6590 | 3600 |
| 630 | 4.5 | 2.4 | 48 | 6790 | 2590 | 1.4 | 2.5 | 2.7 | 57 | 8060 | 4110 |
| 800 | 4.5 | 2.6 | 52 | 8420 | 3570 | 1.5 | 2.5 | 2.8 | 61 | 9800 | 4970 |
| 1000 | 4.5 | 2.7 | 55 | 10330 | 4180 | 1.6 | 2.5 | 3 | 65 | 10850 | 5710 |
| Nom. Cross-Section Area | Nom. Insulation Thickness | Copper Wire Screen Area | Unarmoured Cables | Aluminium Wire Armoured Cables | |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nom. Bedding Thickness | Armour Wire Size | Nom. Sheath Thickness | Approx. Weight | |||||
| CU | AL | CU | AL | ||||||||
| mm² | mm | mm² | mm | mm | kg/km | mm | mm | mm | kg/km | ||
| 25 | 5.5 | 16 | 1.8 | 24 | 720 | 560 | 1.2 | 1.6 | 1.8 | 1200 | 980 |
| 35 | 5.5 | 16 | 1.8 | 25 | 840 | 620 | 1.2 | 1.6 | 1.9 | 1350 | 1070 |
| 50 | 5.5 | 16 | 1.8 | 26 | 990 | 690 | 1.2 | 2 | 2 | 1550 | 1250 |
| 70 | 5.5 | 16 | 1.8 | 28 | 1230 | 800 | 1.2 | 2 | 2.1 | 1840 | 1420 |
| 95 | 5.5 | 16 | 1.9 | 30 | 1530 | 940 | 1.2 | 2 | 2.1 | 2160 | 1570 |
| 120 | 5.5 | 16 | 2 | 31 | 1810 | 1050 | 1.2 | 2 | 2.2 | 2470 | 1730 |
| 150 | 5.5 | 25 | 2 | 33 | 2110 | 1190 | 1.2 | 2 | 2.2 | 2810 | 1890 |
| 185 | 5.5 | 25 | 2.1 | 35 | 2510 | 1360 | 1.2 | 2 | 2.3 | 3240 | 2090 |
| 240 | 5.5 | 25 | 2.1 | 38 | 3130 | 1610 | 1.3 | 2.5 | 2.4 | 4150 | 2580 |
| 300 | 5.5 | 25 | 2.2 | 40 | 3760 | 1860 | 1.3 | 2.5 | 2.5 | 4800 | 2890 |
| 400 | 5.5 | 35 | 2.3 | 43 | 4650 | 2220 | 1.4 | 2.5 | 2.6 | 5780 | 3350 |
| 500 | 5.5 | 35 | 2.4 | 46 | 5530 | 2545 | 1.5 | 2.5 | 2.7 | 6850 | 3850 |
| 630 | 5.5 | 35 | 2.5 | 50 | 6700 | 3100 | 1.5 | 2.5 | 2.9 | 8380 | 4400 |
| 800 | 5.5 | 50 | 2.6 | 55 | 8580 | 3690 | 1.6 | 2.5 | 3 | 10130 | 5270 |
| 1000 | 5.5 | 50 | 2.7 | 59 | 10620 | 4450 | 1.7 | 2.5 | 3.1 | 12180 | 6000 |
| Nom. Cross-Section Area | Nom. Insulation Thickness | Copper Wire Screen Area | Unarmoured Cables | Aluminium Wire Armoured Cables | |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nom. Bedding Thickness | Armour Wire Size | Nom. Sheath Thickness | Approx. Weight | |||||
| CU | AL | CU | AL | ||||||||
| mm² | mm | mm² | mm | mm | kg/km | mm | mm | mm | kg/km | ||
| 50 | 8 | 16 | 2 | 31 | 1250 | 960 | 1.2 | 2 | 2.2 | 1910 | 1640 |
| 70 | 8 | 16 | 2 | 34 | 1510 | 1090 | 1.2 | 2 | 2.3 | 2240 | 1820 |
| 95 | 8 | 16 | 2.1 | 35 | 1830 | 1240 | 1.2 | 2 | 2.3 | 2570 | 1980 |
| 120 | 8 | 16 | 2.1 | 37 | 2110 | 1360 | 1.3 | 2.5 | 2.4 | 3060 | 2310 |
| 150 | 8 | 25 | 2.2 | 38 | 2420 | 1510 | 1.3 | 2.5 | 2.5 | 3430 | 2510 |
| 185 | 8 | 25 | 2.2 | 40 | 2830 | 1680 | 1.3 | 2.5 | 2.5 | 3890 | 2720 |
| 240 | 8 | 25 | 2.3 | 43 | 3500 | 1980 | 1.4 | 2.5 | 2.6 | 4630 | 3120 |
| 300 | 8 | 25 | 2.4 | 45 | 4150 | 2250 | 1.4 | 2.5 | 2.7 | 5330 | 3430 |
| 400 | 8 | 35 | 2.5 | 49 | 5070 | 2640 | 1.5 | 2.5 | 2.8 | 6360 | 3930 |
| 500 | 8 | 35 | 2.6 | 52 | 5945 | 2965 | 1.6 | 2.5 | 2.9 | 7670 | 4490 |
| 630 | 8 | 35 | 2.7 | 56 | 7445 | 3555 | 1.7 | 2.5 | 3 | 8870 | 5020 |
| 800 | 8 | 50 | 2.8 | 61 | 9060 | 4180 | 1.9 | 2.5 | 3.2 | 10790 | 5980 |
| 1000 | 8 | 50 | 2.9 | 65 | 11140 | 4980 | 2 | 2.5 | 3.3 | 12860 | 6730 |
| Nom. Cross-Section Area | Nom. Insulation Thickness | Copper Wire Screen Area | Unarmoured Cables | Aluminium Wire Armoured Cables | |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nom. Bedding Thickness | Armour Wire Size | Nom. Sheath Thickness | Approx. Weight | |||||
| CU | AL | CU | AL | ||||||||
| mm² | mm | mm² | mm | mm | kg/km | mm | mm | mm | kg/km | ||
| 50 | 9.3 | 16 | 2 | 35.7 | 1526 | 1239 | 1.2 | 2 | 2.3 | 2331 | 2116 |
| 70 | 9.3 | 16 | 2.1 | 37.6 | 1809 | 1393 | 1.2 | 2.5 | 2.4 | 2680 | 2325 |
| 95 | 9.3 | 16 | 2.2 | 39.4 | 2123 | 1555 | 1.2 | 2.5 | 2.5 | 2981 | 2482 |
| 120 | 9.3 | 16 | 2.2 | 40.8 | 2405 | 1688 | 1.4 | 2.5 | 2.5 | 3487 | 2867 |
| 150 | 9.3 | 25 | 2.2 | 42.3 | 2733 | 1838 | 1.4 | 2.5 | 2.6 | 3870 | 3055 |
| 185 | 9.3 | 25 | 2.3 | 44.7 | 3216 | 2082 | 1.4 | 2.5 | 2.6 | 4420 | 3370 |
| 240 | 9.3 | 25 | 2.4 | 46.9 | 3766 | 2333 | 1.4 | 2.5 | 2.7 | 4981 | 3676 |
| 300 | 9.3 | 25 | 2.4 | 49.3 | 4408 | 2605 | 1.4 | 2.5 | 2.8 | 5661 | 3971 |
| 400 | 9.3 | 35 | 2.5 | 52.3 | 5473 | 3057 | 1.6 | 2.5 | 2.9 | 6865 | 4550 |
| Nom. Cross-Section Area | Nom. Insulation Thickness | Copper Wire Screen Area | Unarmoured Cables | Aluminium Wire Armoured Cables | |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Nom. Sheath Thickness | Approx. Overall Diameter | Approx. Weight | Nom. Bedding Thickness | Armour Wire Size | Nom. Sheath Thickness | Approx. Weight | |||||
| CU | AL | CU | AL | ||||||||
| mm² | mm | mm² | mm | mm | kg/km | mm | mm | mm | kg/km | ||
| 50 | 10.5 | 16 | 2.1 | 38.3 | 1689 | 1402 | 1.2 | 2.5 | 2.5 | 2580 | 2395 |
| 70 | 10.5 | 16 | 2.2 | 40.2 | 1980 | 1564 | 1.2 | 2.5 | 2.5 | 2937 | 2611 |
| 95 | 10.5 | 16 | 2.2 | 41.8 | 2283 | 1714 | 1.2 | 2.5 | 2.6 | 3206 | 2737 |
| 120 | 10.5 | 16 | 2.3 | 43.4 | 2588 | 1871 | 1.4 | 2.5 | 2.6 | 3753 | 3177 |
| 150 | 10.5 | 25 | 2.3 | 44.9 | 2923 | 2028 | 1.4 | 2.5 | 2.7 | 4143 | 3371 |
| 185 | 10.5 | 25 | 2.4 | 47.3 | 3415 | 2281 | 1.4 | 2.5 | 2.7 | 4694 | 3693 |
| 240 | 10.5 | 25 | 2.5 | 49.6 | 3975 | 2542 | 1.4 | 2.5 | 2.8 | 5258 | 4005 |
| 300 | 10.5 | 25 | 2.5 | 51.9 | 4625 | 2822 | 1.4 | 2.5 | 2.9 | 5940 | 4301 |
| 400 | 10.5 | 35 | 2.6 | 54.9 | 5704 | 3288 | 1.6 | 2.5 | 3 | 7155 | 4894 |
| Nom. Cross-Section Area | Buried Direct in Ground | Laid in Single Way Duct | Laid in Air | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Trefoil | Flat Spaced | Trefoil | Flat Touching | Trefoil | Flat Touching | Flat Spaced | ||||||||
| CU | AL | CU | AL | CU | AL | CU | AL | CU | AL | CU | AL | CU | AL | |
| mm² | A | A | A | A | A | A | A | |||||||
| 10 | 84 | 59 | 87 | 62 | 78 | 55 | 98 | 56 | 103 | 75 | 106 | 77 | 122 | 88 |
| 16 | 109 | 84 | 113 | 88 | 103 | 80 | 104 | 81 | 125 | 97 | 128 | 99 | 150 | 116 |
| 25 | 140 | 108 | 144 | 112 | 132 | 102 | 133 | 103 | 163 | 127 | 167 | 130 | 196 | 153 |
| 35 | 166 | 129 | 172 | 134 | 157 | 122 | 159 | 123 | 198 | 154 | 203 | 157 | 238 | 185 |
| 50 | 196 | 152 | 203 | 157 | 186 | 144 | 188 | 146 | 238 | 184 | 243 | 189 | 286 | 222 |
| 70 | 239 | 186 | 246 | 192 | 227 | 176 | 229 | 178 | 296 | 230 | 303 | 236 | 356 | 278 |
| 95 | 285 | 221 | 293 | 229 | 271 | 210 | 274 | 213 | 361 | 280 | 369 | 287 | 434 | 338 |
| 120 | 323 | 252 | 332 | 260 | 308 | 240 | 311 | 242 | 417 | 324 | 426 | 332 | 500 | 391 |
| 150 | 361 | 281 | 366 | 288 | 343 | 267 | 347 | 271 | 473 | 368 | 481 | 376 | 559 | 440 |
| 185 | 406 | 317 | 410 | 324 | 387 | 303 | 391 | 307 | 543 | 424 | 550 | 432 | 637 | 504 |
| 240 | 469 | 367 | 470 | 373 | 447 | 351 | 453 | 356 | 641 | 502 | 647 | 511 | 745 | 593 |
| 300 | 526 | 414 | 524 | 419 | 504 | 397 | 510 | 402 | 735 | 577 | 739 | 586 | 846 | 677 |
| 400 | 590 | 470 | 572 | 466 | 564 | 451 | 571 | 457 | 845 | 673 | 837 | 676 | 938 | 769 |
| 500 | 650 | 530 | 672 | 546 | 604 | 504 | 661 | 537 | 935 | 773 | 938 | 776 | 1118 | 919 |
| 630 | 700 | 600 | 882 | 646 | 654 | 554 | 771 | 617 | 1045 | 883 | 1048 | 886 | 1318 | 1089 |
| 800 | 750 | 660 | 1002 | 756 | 694 | 594 | 871 | 717 | 1145 | 983 | 1148 | 986 | 1528 | 1279 |
| 1000 | 800 | 720 | 1112 | 856 | 724 | 644 | 971 | 807 | 1235 | 1083 | 1238 | 1086 | 1738 | 1469 |
| Nom. Cross-Section Area | Buried Direct in Ground | Laid in Single Way Duct | Laid in Air | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Trefoil | Flat Spaced | Trefoil | Flat Touching | Trefoil | Flat Touching | Flat Spaced | ||||||||
| CU | AL | CU | AL | CU | AL | CU | AL | CU | AL | CU | AL | CU | AL | |
| mm² | A | A | A | A | A | A | A | |||||||
| 10 | 81 | 57 | 83 | 58 | 74 | 52 | 94 | 53 | 94 | 68 | 97 | 70 | 110 | 79 |
| 16 | 106 | 82 | 109 | 84 | 99 | 77 | 100 | 78 | 116 | 90 | 119 | 92 | 138 | 107 |
| 25 | 136 | 105 | 140 | 109 | 128 | 99 | 129 | 100 | 153 | 119 | 156 | 121 | 181 | 141 |
| 35 | 162 | 126 | 167 | 130 | 153 | 118 | 154 | 120 | 186 | 144 | 190 | 147 | 221 | 171 |
| 50 | 192 | 149 | 198 | 153 | 181 | 140 | 183 | 142 | 224 | 174 | 229 | 178 | 266 | 207 |
| 70 | 234 | 182 | 242 | 188 | 222 | 172 | 224 | 174 | 280 | 218 | 287 | 223 | 334 | 259 |
| 95 | 280 | 217 | 289 | 224 | 266 | 206 | 269 | 208 | 343 | 266 | 352 | 273 | 409 | 317 |
| 120 | 319 | 247 | 329 | 256 | 303 | 235 | 306 | 238 | 398 | 309 | 407 | 317 | 474 | 368 |
| 150 | 357 | 277 | 369 | 287 | 341 | 264 | 344 | 267 | 454 | 352 | 465 | 361 | 540 | 419 |
| 185 | 403 | 314 | 417 | 325 | 386 | 300 | 390 | 303 | 522 | 406 | 534 | 417 | 621 | 484 |
| 240 | 467 | 364 | 484 | 377 | 449 | 350 | 454 | 354 | 619 | 483 | 634 | 495 | 736 | 575 |
| 300 | 526 | 411 | 545 | 426 | 509 | 397 | 515 | 401 | 712 | 556 | 728 | 570 | 843 | 659 |
| 400 | 597 | 471 | 618 | 487 | 580 | 456 | 588 | 462 | 825 | 651 | 843 | 667 | 977 | 770 |
| 500 | 657 | 531 | 718 | 567 | 620 | 509 | 678 | 542 | 915 | 751 | 849 | 767 | 1157 | 920 |
| 630 | 707 | 601 | 928 | 667 | 670 | 559 | 788 | 622 | 1025 | 862 | 1054 | 876 | 1357 | 1090 |
| 800 | 757 | 661 | 1048 | 777 | 710 | 599 | 888 | 722 | 1125 | 961 | 1154 | 977 | 1567 | 1280 |
| 1000 | 807 | 721 | 1158 | 877 | 740 | 649 | 988 | 812 | 1215 | 1061 | 1244 | 1077 | 1777 | 1470 |
Request the Complete Data Sheet
Application
The single core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 1.8/3KV to 26/35KV andfrequency 50Hz.
They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as forinstallation on cable trays for industries, switchboards and power stations.




From Production to Delivery
From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.
Production
Stranded annealed copper conductors are insulated with XLPE, assembled into the required multicore configuration, optionally filled and bound with polyester tape, then covered with the specified black PVC sheath.
Inspection
Inspection focuses on conductor construction, insulation condition, core identification, sheath integrity, overall diameter, conductor resistance and test-voltage requirements against the approved technical schedule.
Packaging
Finished cable is wound on suitable drums according to ordered size, weight and length. Cable ends are protected and drum identification can include cable type, conductor size, core count, length and project reference.
Shipping
Before shipment, cable drums and technical documents are checked against the order. Inspection records, identification data and requested test documentation can be prepared for the customer.
faq
What is the voltage range of these single core medium voltage cables?
These single core cables are designed for distribution of electrical power with a nominal voltage Uo/U ranging from 1.8/3kV up to 26/35kV, at a frequency of 50Hz.
What insulation options can I choose from?
Three insulation types are offered:
PVC (Polyvinyl Chloride) — for 1.8/3kV and 3.6/6kV cables, a cost-effective and reliable option
XLPE (Cross-Linked Polyethylene) — high temperature rating (90°C), superior electrical performance and current-carrying capacity
EPR/HEPR (Ethylene Propylene Rubber) — excellent flexibility, cold resistance, and mechanical resilience
Why is aluminium wire armour (AWA) used for single core cables instead of steel?
Single core cables carry alternating current, which would induce eddy currents in steel armour, causing overheating and energy loss. Aluminium Wire Armour (AWA) is non-magnetic, eliminating these issues while still providing the mechanical protection needed for direct burial and harsh installation conditions. Armour is available as an optional feature.
When should I choose single core cables over three core cables?
Single core cables are typically preferred for:
High-current circuits where individual phase installation is required
Single-phase systems
Applications requiring easier cable pulling and installation
Circuits where individual phase replacement or maintenance may be needed
Large conductor sizes where three-core construction becomes impractical
Can you manufacture custom cable specifications?
Yes, we offer extensive customization options to meet specific project requirements including:
- Special core configurations (e.g., 3+1E, 3+2E, 4+1E, custom multi-core)
- Custom outer sheath colors (red, blue, grey, etc. for identification)
- Special print marking with customer logo, project name, or custom text
- Low smoke zero halogen (LSZH) versions for special fire safety requirements
- UV-stabilized formulations for extreme outdoor exposure
- Oil-resistant and chemical-resistant sheath compounds
- Custom length drums and packaging
Custom orders typically require MOQ and may have slightly longer lead times. Contact our sales team with your specific requirements for a quote.
What is the typical lead time for orders?
Typical production lead times:
- Standard specifications (common sizes): 7-15 working days after order confirmation
- Custom specifications or special requirements: 15-25 working days
- Large volume orders: production schedule confirmed at time of order
We also maintain inventory of fast-moving standard sizes for immediate shipment. Transit time depends on destination port and shipping method. We can ship by sea (most cost-effective for large orders), air (urgent shipments), or rail (for Central Asian destinations).