UL 1277 CU PE/PVC Shielded PVC Jacket Control Cable 600V

UL 1277 CU PE/PVC Shielded PVC Jacket Control Cable is a 600V multi-conductor industrial control cable with Class B compressed bare-copper conductors, dual-layer polyethylene and polyvinyl chloride (PE/PVC) insulation, a 5 mil tape shield and a polyvinyl chloride (PVC) outer jacket. It is intended for wet and dry industrial control circuits requiring tray-cable construction and an overall shielding layer.

PRODUCT OVERVIEW

The cable uses 7-strand Class B compressed bare-copper conductors, 20 mil PE plus 10 mil PVC insulation, a 5 mil tape shield and a PVC overall jacket. Polypropylene filler is used on cables with five or fewer conductors, while cables with more than five conductors use a polyester flat-thread binder tape. A rip cord is included for easier jacket removal.

The supplied product schedule lists 600V service in wet and dry areas, conduits, ducts, troughs, trays, direct burial and messenger-supported aerial routes. It states maximum conductor temperatures of 90°C for normal operation, 130°C for emergency overload and 250°C for short-circuit conditions. Exact certification marks, flame-test designations and project-specific cable markings should be confirmed for the ordered construction.

KEY FEATURES

  • UL 1277 electrical power and control tray-cable product basis.
  • 600V multi-conductor copper control cable.
  • 7-strand Class B compressed bare-copper conductors.
  • Dual-layer PE/PVC insulation: 20 mil PE plus 10 mil PVC.
  • 5 mil tape shield with PVC outer jacket.
  • Silicone-free construction.
  • 90°C normal / 130°C emergency overload / 250°C short-circuit conductor temperatures stated in the source.
  • Suitable for trays, troughs, conduits, ducts, direct burial and messenger-supported aerial installations as stated in the source.
  • CSA marking is available upon request, as stated in the source.
  • Exact UL certification, flame-test and installation markings must be confirmed for the ordered construction.

CABLE CONSTRUCTION

Conductor

7-strand Class B compressed bare copper; source references ASTM B3 and ASTM B8

Insulation

Polyethylene (PE) 20 mil plus Polyvinyl Chloride (PVC) 10 mil

Insulation Thickness

Total 30 mil insulation system stated for all listed cable sizes

Filler

Polypropylene filler on cables with 5 or fewer conductors

Binder

Polyester flat-thread binder tape on cables with more than 5 conductors

Shielding

5 mil tape shield

Rip Cord

Included for ease of jacket removal

Overall Jacket

Polyvinyl Chloride (PVC)

Voltage Rating

600V

Silicone Free

Yes, stated in the source

UL 1277 TYPE TC DESIGN FOCUS

Focus

How It Relates to This Product

Complete Multiconductor Cable

Compressed copper conductors, dual-layer PE/PVC insulation, filler/binder system, 5 mil tape shield and PVC jacket

Tray / Raceway Installations

Source lists trays, troughs, conduits and ducts

Direct Burial

Stated in the product application

Wet / Dry Locations

Both are stated, with 90°C normal operation

Aerial Use

Messenger-supported aerial installation is stated

Flame Performance

IEEE 1202 FT4, ICEA T-29-520 and VW-1 are cited in the supplied product schedule

Certification Marking

Confirm the exact UL certification and cable surface marking for the ordered construction

WHY 5 MIL TAPE SHIELDING?

The defining product feature in this version is the 5 mil tape shield applied over the assembled insulated conductors. The shield provides an overall metallic barrier for control circuits where interference control is required, while the PVC jacket protects the completed cable construction.

Shield continuity, grounding, bonding and termination details depend on the project wiring method and equipment design. State the required shield construction and termination practice in the inquiry, and confirm the exact certification, test documents and cable marking before approval.

PRODUCT APPLICATIONS

  • Industrial 600V multi-conductor control circuits.
  • Wet and dry areas.
  • Conduits, ducts, troughs and trays.
  • Direct-burial installations.
  • Messenger-supported aerial routes.
  • Projects requiring dual-layer PE/PVC insulation, a 5 mil overall tape shield and a PVC jacket.
  • CSA marking is available upon request, subject to the confirmed ordered construction.
  • Project-specific UL certification and surface marking must be confirmed before approval.

Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.

AWG Cores Cond. Dia. in Insul. mil Jacket mil OD in Cu Wt lb/kft Cable Wt lb/kft DC R Ω/kft AC R @90°C Ω/kft Min Bend in Amp 60°C Amp 75°C Amp 90°C
10 2 0.111 30 45 0.431 65 124 1.040 1.300 1.7 30 30 30
10 3 0.111 30 45 0.459 97 165 1.040 1.300 1.8 30 30 30
10 4 0.111 30 45 0.502 130 210 1.040 1.300 2.0 24 28 30
10 5 0.111 30 60 0.581 162 273 1.040 1.300 2.3 24 28 30
10 6 0.111 30 60 0.632 194 323 1.040 1.300 2.5 24 28 30
10 7 0.111 30 60 0.632 227 358 1.040 1.300 2.5 21 24 28
10 8 0.111 30 60 0.685 259 410 1.040 1.300 2.7 21 24 28
10 9 0.111 30 60 0.736 291 461 1.040 1.300 2.9 21 24 28
10 10 0.111 30 60 0.803 324 519 1.040 1.300 3.2 15 17 20
10 12 0.111 30 60 0.830 389 600 1.040 1.300 3.3 15 17 20
10 15 0.111 30 80 0.964 486 777 1.040 1.300 3.9 15 17 20
10 19 0.111 30 80 1.014 615 941 1.040 1.300 5.1 15 17 20
10 20 0.111 30 80 1.067 648 1001 1.040 1.300 5.3 15 17 20
10 25 0.111 30 80 1.184 810 1236 1.040 1.300 5.9 13 15 18
10 30 0.111 30 80 1.254 971 1450 1.040 1.300 6.3 13 15 18
10 37 0.111 30 80 1.355 1198 1755 1.040 1.300 6.8 12 14 16

Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.

AWG Cores Cond. Dia. in Insul. mil Jacket mil OD in Cu Wt lb/kft Cable Wt lb/kft DC R Ω/kft AC R @90°C Ω/kft Min Bend in Amp 60°C Amp 75°C Amp 90°C
12 2 0.087 30 45 0.384 41 90 1.660 2.075 1.5 20 20 20
12 3 0.087 30 45 0.408 61 118 1.660 2.075 1.6 20 20 20
12 4 0.087 30 45 0.445 81 148 1.660 2.075 1.8 16 20 20
12 5 0.087 30 45 0.487 102 181 1.660 2.075 1.9 16 20 20
12 6 0.087 30 45 0.532 122 214 1.660 2.075 2.1 16 20 20
12 7 0.087 30 45 0.532 143 237 1.660 2.075 2.1 14 17 20
12 8 0.087 30 60 0.607 163 288 1.660 2.075 2.4 14 17 20
12 9 0.087 30 60 0.651 183 324 1.660 2.075 2.6 14 17 20
12 10 0.087 30 60 0.709 204 365 1.660 2.075 2.8 10 12 15
12 12 0.087 30 60 0.732 244 419 1.660 2.075 2.9 10 12 15
12 15 0.087 30 60 0.813 305 516 1.660 2.075 3.3 10 12 15
12 19 0.087 30 80 0.896 387 657 1.660 2.075 3.6 10 12 15
12 20 0.087 30 80 0.942 407 699 1.660 2.075 3.8 10 12 15
12 25 0.087 30 80 1.043 509 860 1.660 2.075 5.2 9 11 13
12 30 0.087 30 80 1.104 611 1005 1.660 2.075 5.5 9 11 13
12 37 0.087 30 80 1.191 753 1211 1.660 2.075 6.0 8 10 12

Physical and electrical data reproduced from the supplied product schedule. Units are retained as provided in the source.

AWG Cores Cond. Dia. in Insul. mil Jacket mil OD in Cu Wt lb/kft Cable Wt lb/kft DC R Ω/kft AC R @90°C Ω/kft Min Bend in Amp 60°C Amp 75°C Amp 90°C
14 2 0.070 30 45 0.349 26 68 2.630 3.288 1.4 15 15 15
14 3 0.070 30 45 0.378 38 92 2.630 3.288 1.5 15 15 15
14 4 0.070 30 45 0.403 51 109 2.630 3.288 1.6 14 15 15
14 5 0.070 30 45 0.440 64 132 2.630 3.288 1.8 14 15 15
14 6 0.070 30 45 0.479 77 155 2.630 3.288 1.9 14 15 15
14 7 0.070 30 45 0.479 90 171 2.630 3.288 1.9 12 15 15
14 8 0.070 30 45 0.519 102 195 2.630 3.288 2.1 12 15 15
14 9 0.070 30 60 0.588 115 236 2.630 3.288 2.4 12 15 15
14 10 0.070 30 60 0.638 128 266 2.630 3.288 2.6 9 11 12
14 12 0.070 30 60 0.659 154 303 2.630 3.288 2.6 9 11 12
14 15 0.070 30 60 0.730 192 371 2.630 3.288 2.9 9 11 12
14 19 0.070 30 60 0.768 243 446 2.630 3.288 3.1 9 11 12
14 20 0.070 30 60 0.808 256 475 2.630 3.288 3.2 9 11 12
14 25 0.070 30 80 0.937 320 619 2.630 3.288 3.7 8 9 11
14 30 0.070 30 80 0.991 384 719 2.630 3.288 4.0 8 9 11
14 37 0.070 30 80 1.067 474 862 2.630 3.288 5.3 7 8 10

Request the Complete Data Sheet

If you need a specific product catalogue or related standard file, please contact us.

From Production to Delivery

From raw material preparation to final shipmen, every stage is caretuly controled to ensure consistent conductor quality, reliable pertormance,and sae delivery. Our roduction,
inspection, packaging, and logistics processes are managed in accordance with applicable standards and project requirements.

cable production line with finished cable being wound onto a reel

Production

Class B compressed bare-copper conductors are prepared, insulated with 20 mil PE and 10 mil PVC, assembled with polypropylene filler or polyester binder according to the number of conductors, shielded with the specified 5 mil tape, fitted with the rip cord and finished with the PVC jacket.

Cable and conductor quality inspection and testing

Inspection

Inspection focuses on conductor construction, PE/PVC insulation and jacket thickness, tape-shield construction and continuity, overall diameter, conductor and cable weight, DC/AC resistance, bending-radius data, cable marking and project-specified test documentation.

Overhead conductors packed on wooden drums for shipment

Packaging

Finished cable is wound on reels or drums suitable for its diameter, weight and ordered length. Product identification can include conductor size, core count, standard reference, length and project number.

Wooden drums of overhead conductors loaded into shipping container

Shipping

Before shipment, cable marking, packing, inspection records and requested standard/test documents are checked against the order and project approval requirements.

Frequently Asked Questions

What is the practical difference between this shielded cable and the unshielded PE/PVC version?

This version adds a 5 mil tape shield over the assembled insulated conductors. The unshielded PE/PVC version omits that metallic shielding layer. Select the shielded construction when the project requires an overall screen and confirm its grounding and termination method with the system designer.

The source construction identifies a 5 mil tape shield. The catalogue does not provide a shielding-effectiveness value, coverage percentage or detailed alloy description, so those properties should be confirmed in the technical offer when required by the project.

Shield grounding and termination depend on the control system, noise environment, equipment manufacturer and project wiring rules. Define single-point or multi-point bonding, gland/connector requirements and shield continuity before production and installation.

Use the column permitted by the project conductor/termination temperature rating, then apply code-required derating for ambient temperature, grouping and installation conditions. The table values are source product data and are not a substitute for the governing electrical-code calculation.

The supplied product schedule lists 14, 12 and 10 AWG conductors. Select the required conductor size and core count only from the configurations shown in the technical table, or request engineering confirmation for a size not listed.

We provide a wide range of cable materials and electrical products, including aluminum conductors, aluminum rods, aluminum wires, overhead conductors, medium and low voltage power cables, cable insulation materials, filling materials, shielding materials, and cable manufacturing consumables.We provide customized solutions according to different cable manufacturing requirements.

Request for Free Consultation

Contact Information

Send us your cable requirements and our team will respond quickly with product recommendations, technical support and quotation details.

Explore More

Related Products
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Compatible Hardware
GD link fitting with central eye and transverse bolted connections for overhead line hardware
Twisted Link Plates — Type GD
LT and EB tower attachment fitting with upper bolted connection and lower eye for insulator strings
Tower Attachment Fittings — Types LT & EB
DIN VDE 0814 LiYCY TP 250V shielded twisted pair signal and control cable
DIN VDE 0814 LiYCY TP Shielded Signal and Control Cable 250V
Knowledge Articles
Customer Visits Our Factory for Product Inspection and Quality Verification
AAAC all aluminium alloy conductor stranded wire
AAAC Conductor Selection Guide: How to Choose the Right AAAC for Overhead Lines
International Airport Expansion Project in Saudi Arabia

For Immediate Assistance, Please Contact us Now!